VIII. Maintenance

Kooltronic Water-Cooled Air Conditioners require no maintenance. Air-Cooled Air Conditioners are
designed to require only the routine cleaning of air filters to assure unimpeded airflow through the
condenser heat exchanger. It is not possible to recommend specific filter cleaning intervals since the
level and the nature of airborne particulate matter differs widely with each installation. It is generally
sufficient to remove and wash the reusable aluminum mesh air filters when the outer surfaces of these
filters appear covered with a thin layer of dust or lint. Filter recoating adhesive is recommended.
Appropriate disposable filters are available from Kooltronic.

If filter service is neglected or delayed, the air conditioner will not perform at its design capacity. The first
indication of excessively clogged air filters is usually a gradual increase of temperature within the
equipment cabinet. If operation is continued under these conditions, the compressor will be shut off by
the thermal overload device. The compressor will restart when its external temperature drops below the
protector threshold setting and the compressor will continue to cycle on and off. Continued operation
under these conditions will cause damage, shorten compressor life and void the warranty.

A. Filter Removal and Service

Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning.

CAUTION

1) Lift the filter, using the attached tab, to clear the lower filter retainer. Pull filter toward you and

downward until the top of the filter clears the upper filter retainer.

2) After removal, the filters should be flushed under warm running water with the clean side

up, driving contaminants out the dirty side of the filter. If the accumulated dirt is oily, washing in
a detergent bath is recommended, followed by a warm water rinse as above.

3) The filters may be sprayed with 

Kooltronic A-16 Filter Recoating Adhesive

to trap fine airborne

contaminants, or they may simply be dried and reinstalled as strainer type filters. 

Recoating is

recommended for best results.

4) Reinstall the filter: (a) keeping the tab at the bottom, slide filter into the upper retainer, (b) press

filter against the unit and (c) slide down into lower retainer.

Do not operate the Air Conditioner for extended periods of time with the filter

removed. The condenser coil may become clogged with dust or lint from the air
entering the face. A clogged condenser coil is not readily detected and will give

the same reaction as a clogged filter. A clean filter is the best protection.

Содержание ACCESS Series

Страница 1: ...E READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 105 5 21 CDR 20322 Find additional information...

Страница 2: ...tronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit FILTER P N FUS...

Страница 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Страница 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Страница 7: ...enser blower to cycle on off during this period 8 Turn off the electrical power source and disconnect the air conditioner from the power source 9 If any cover plug is removed to adjust the unit make c...

Страница 8: ...URE PANEL 15 49 393 4 TYP 7 50 190 5 56 14 2 TYP 21 72 551 6 TYP 5 59 141 9 2 PLACES 135 TYP 4 03 102 3 1 25 31 7 1 69 42 9 0 11 45 290 8 7 38 187 4 1 51 38 3 6 21 157 7 49 12 4 TYP 7 99 202 9 TYP 11...

Страница 9: ...GURATION INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING REAR PANEL L BRACKETS 2 1 KA4C2DSP23L K2A4C2DSP23L KNA4C2DSP23L K2NA4C2DSP23L INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING FRONT...

Страница 10: ...OPTION R 11 2 8 38 9 5 26 6 6 1 37 34 7 R 19 4 7 11 80 299 7 20 75 527 1 7 48 190 0 1 03 26 2 70 17 8 CONDENSER AIR OUTLET 2 1 115 VOLT MODEL 230 VOLT MODEL DIGITAL THERMOSTAT EVAPORATOR AIR INLET NOT...

Страница 11: ...8 0718 40 0718 38 0718 40 Technical Data KA4C2DSP23L 2000 2373 122 20 115 60 5 03 15 K2A4C2DSP23L 2000 2360 122 20 230 60 2 87 15 K2A4C2DSP23L 2000 2170 122 20 230 50 2 3 15 KNA4C2DSP23L 2000 2373 122...

Страница 12: ...ff Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet...

Страница 13: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 14: ...mostat improperly set Low Temperature Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Uni...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: