background image

7

VI. Pre-Installation Testing

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping integrity of
the system. Please follow the steps below prior to installation.

CAUTION

1.

Allow the unit to sit in a upright position at a room temperature of 65°F minimum, allowing the system to warm-up.
This is particularly important in winter months.

2.

Refer to the nameplate for proper electrical voltage and current requirements. Then connect the power cord to a
properly grounded and fused electrical supply. Leave the electrical power off.

3.

Note the factory thermostat setting which is 75°F.

4.

Turn electrical power on.

5.

Verify that the evaporator blower or fan is running.

6.

Observe the temperature on the digital display. The thermostat must be set a minimum of 10°F below this
temperature for the compressor to operate (the factory setting is 75°F). Refer to page 6 for instructions on adjustment
of the thermostat.

7.

Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or vibration
should be evident. Both the evaporator and condenser fans or blowers should be delivering air through their
respective discharge ports. The cool air discharged should be less than 70°F when the room temperature is
between 70 and 80°F. It is normal for the condenser blower to cycle on/off during this period. 

8. Turn off the electrical power source, and disconnect the air conditioner from the power source.

9. If any cover plug is removed to adjust the unit, make certain to put it back in place to maintain the integrity of the

closed-loop airflow system.

NOTE:

Before shipment all Kooltronic Air Conditioners are subjected to a performance test.

VII. Specific Model Data
Mounting

The Kooltronic Special Purpose Air Conditioners K_A4C2DSP23L have been engineered to be installed easily. The air
conditioner is designed for two mounting options - external and internal. 

NOTE: Prior to mounting of Air Conditioner units, refer to Mounting Drawings section of the Kooltronic website:

Access Series DSP23 115 Volt Mounting Drawings

Access Series DSP23 230 Volt Mounting Drawings

Prior to cutting or drilling, make sure that cutouts and mounting holes do not interfere with components inside the cabinet. The
Mounting Drawings are also available on the following pages.

The air conditioner must be standing in its proper mounting position for a minimum of five

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to

the compressor. To avoid compressor damage do not tip the unit more than 45° from its

proper mounting position.

If the air conditioner is mounted to the cabinet door you must be sure that the door hinges will support

the additional weight of the air conditioner. Also be certain that when the door is opened fully, the cabinet

does not become unbalanced. 

Содержание ACCESS Series

Страница 1: ...E READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 105 5 21 CDR 20322 Find additional information...

Страница 2: ...tronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit FILTER P N FUS...

Страница 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Страница 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Страница 7: ...enser blower to cycle on off during this period 8 Turn off the electrical power source and disconnect the air conditioner from the power source 9 If any cover plug is removed to adjust the unit make c...

Страница 8: ...URE PANEL 15 49 393 4 TYP 7 50 190 5 56 14 2 TYP 21 72 551 6 TYP 5 59 141 9 2 PLACES 135 TYP 4 03 102 3 1 25 31 7 1 69 42 9 0 11 45 290 8 7 38 187 4 1 51 38 3 6 21 157 7 49 12 4 TYP 7 99 202 9 TYP 11...

Страница 9: ...GURATION INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING REAR PANEL L BRACKETS 2 1 KA4C2DSP23L K2A4C2DSP23L KNA4C2DSP23L K2NA4C2DSP23L INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING FRONT...

Страница 10: ...OPTION R 11 2 8 38 9 5 26 6 6 1 37 34 7 R 19 4 7 11 80 299 7 20 75 527 1 7 48 190 0 1 03 26 2 70 17 8 CONDENSER AIR OUTLET 2 1 115 VOLT MODEL 230 VOLT MODEL DIGITAL THERMOSTAT EVAPORATOR AIR INLET NOT...

Страница 11: ...8 0718 40 0718 38 0718 40 Technical Data KA4C2DSP23L 2000 2373 122 20 115 60 5 03 15 K2A4C2DSP23L 2000 2360 122 20 230 60 2 87 15 K2A4C2DSP23L 2000 2170 122 20 230 50 2 3 15 KNA4C2DSP23L 2000 2373 122...

Страница 12: ...ff Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet...

Страница 13: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 14: ...mostat improperly set Low Temperature Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Uni...