background image

Keep This  Manual

With Air Conditioner

AIR CONDITIONER

OPERATOR'S MANUAL

CAUTION

BEFORE INSTALLING AND

USING THIS AIR CONDITIONER,

IT IS IMPORTANT THAT THIS

MANUAL BE READ AND

UNDERSTOOD THOROUGHLY

KOOLTRONIC, INC.

30 Pennington-Hopewell Road

Pennington, NJ 08534

609 • 466-3400

FAX: 609 • 466-1114

www.kooltronic.com

900-039-105 (5/21)
(CDR: 20322)

Find additional information on this
model at kooltronic.com, or use the
Technical Documents QR code
below.

Technical

Documents

ACCESS SERIES

KA4C2DSP23L

K2A4C2DSP23L

KNA4C2DSP23L

K2NA4C2DSP23L

Содержание ACCESS Series

Страница 1: ...E READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 105 5 21 CDR 20322 Find additional information...

Страница 2: ...tronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes...

Страница 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Страница 4: ...or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit FILTER P N FUS...

Страница 5: ...bs the heat and is then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on t...

Страница 6: ...re the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET p...

Страница 7: ...enser blower to cycle on off during this period 8 Turn off the electrical power source and disconnect the air conditioner from the power source 9 If any cover plug is removed to adjust the unit make c...

Страница 8: ...URE PANEL 15 49 393 4 TYP 7 50 190 5 56 14 2 TYP 21 72 551 6 TYP 5 59 141 9 2 PLACES 135 TYP 4 03 102 3 1 25 31 7 1 69 42 9 0 11 45 290 8 7 38 187 4 1 51 38 3 6 21 157 7 49 12 4 TYP 7 99 202 9 TYP 11...

Страница 9: ...GURATION INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING REAR PANEL L BRACKETS 2 1 KA4C2DSP23L K2A4C2DSP23L KNA4C2DSP23L K2NA4C2DSP23L INSIDE ENCLOSURE OUTSIDE ENCLOSURE MOUNT AC UTILIZING FRONT...

Страница 10: ...OPTION R 11 2 8 38 9 5 26 6 6 1 37 34 7 R 19 4 7 11 80 299 7 20 75 527 1 7 48 190 0 1 03 26 2 70 17 8 CONDENSER AIR OUTLET 2 1 115 VOLT MODEL 230 VOLT MODEL DIGITAL THERMOSTAT EVAPORATOR AIR INLET NOT...

Страница 11: ...8 0718 40 0718 38 0718 40 Technical Data KA4C2DSP23L 2000 2373 122 20 115 60 5 03 15 K2A4C2DSP23L 2000 2360 122 20 230 60 2 87 15 K2A4C2DSP23L 2000 2170 122 20 230 50 2 3 15 KNA4C2DSP23L 2000 2373 122...

Страница 12: ...ff Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet...

Страница 13: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Страница 14: ...mostat improperly set Low Temperature Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Uni...

Страница 15: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Отзывы: