92
Part Number STH063 9/17
Fan Cycle Control
Function
Cycles the fan motor on and off to maintain proper
operating discharge pressure.
The fan cycle control closes on an increase, and opens on a
decrease in discharge pressure.
Specifications
Model
Cut-In
(Close)
Cut-Out
(Open)
KT0300 KT0400
KT0420 KT0500
KT0700
335 psig ±5
2310 kPa ±5
275 psig ±5
1896 kPa ±5
KT1000
KT1700
385 psig ±5
2654 kPa ±5
305 psig ±5
2103 kPa ±5
Check Procedure
Disconnect electrical power to the ice machine at the
electrical service disconnect.
Verify fan motor windings are not open or grounded, and
fan spins freely.
Connect manifold gauge to ice machine.
Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
Reconnect electrical power to the ice machine and Cycle
the toggle switch On.
Wait until water flows over the evaporator then refer to
chart below.
System
Pressure:
Reading
Should Be:
Fan
Should Be:
above cut-in
0 volts
running
below cut-out
line voltage
off
Содержание KDT0300A
Страница 1: ...Part Number STH063 9 17 Koolaire KT Model Ice Machines Technician s Handbook ...
Страница 2: ......
Страница 26: ...26 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 46: ...46 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 114: ...114 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 146: ...146 Part Number STH063 9 17 ELECTRONIC CONTROL BOARD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 19 18 20 21 23 24 25 22 ...
Страница 150: ...150 Part Number STH063 9 17 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 151: ......