4.1. 

Troubleshooting 

 

 

 Only qualified staff is allowed to

 

carry out these works! 

Trouble 

Cause 

Repair    

by authorized Service Station

 

only 

a/c is not 
running 

thermostat open 

check inside temperature   

re-adjust thermostat   

electric connections disconnected 

check electric connections at switchboard 

relay defective 

check relay, replace if necessary 

defrost thermostat has switched off 

check evaporator blower, replace if neces-
sary 

outside temperature too low (possible 
icing of evaporator) 

switch on "ventilation" only 

evaporator coil dirty 

clean evaporator coil with compressed air 

magnetic clutch 

check connections at magnetic clutch 

compressor does not compress 

check high and low pressure, replace com-
pressor if necessary 

excess pressure (pressure too high) 

check axial fans  
check fuses at switchboard 
clean condenser coil with compressed air 

excess pressure caused by high out-
side temperature 

run unit until pressure has stabilized  

leakage in a/c unit, lack of refrigerant  check a/c unit for leakages, refill refrigerant 
low pressure, dryer clogged 

replace dryer 

low pressure, screen of expansion 
valve clogged 

clean screen; replace dryer 

Loud noise 
at compres-
sor 

defective bearing at compressor 

replace either bearing or entire compressor  

slack V-belt 

check V-belt at compressor drive 

 

 

By operator

 

 

5. 

Warranty Conditions 

The current „General Warranty Conditions KONVEKTA AG“ will apply. A copy will be furnished by 
the warranty department. Please contact 

[email protected]

 

Содержание UL500

Страница 1: ...chwalmstadt Germany 49 0 66 91 76 0 49 0 66 91 76 200 Info konvekta com www konvekta com Operating Instructions for KONVEKTA Air Conditioning units UL500 UL700 UL800 with Wabco control system R134a 24 Volt DC ID BBA KL6U022AA Version A03 ...

Страница 2: ...ction of the keys 6 3 1 1 Flap for windshield floor 6 3 1 2 Desired value of front box temperature 6 3 1 3 Blower speed 6 3 1 4 Smog 6 3 1 5 Heater passenger s compartment 7 3 1 6 Additional heater 7 3 1 7 Reheat 7 3 1 8 Driver s seat air conditioning 7 3 1 9 General 7 4 Wartung 7 4 1 Troubleshooting 8 5 Warranty Conditions 8 6 Waste disposal in accordance with legal provisions 9 7 History of modi...

Страница 3: ...increases operation reliability and service life of the air conditioning unit and reduces life cycle costs Please complete these instructions by adding the national provi sions for prevention of accidents and environmental protection These instructions are part of the air conditioning unit Always have a copy at hand in the driver s cabin You will certainly understand that we will not recognize any...

Страница 4: ...t may differ in some parts of description In case your product is equipped with details not shown or described in the operating in struction your KONVEKTA Service Station will always be at disposal for informing you about correct operation In the course of further developments we reserve the right to technical modifications without no tice Guarantee and liability conditions of KONVEKTA AG s genera...

Страница 5: ... and aluminium components cannot be ruled out The cupper and aluminium components of the KONVEKTA systems are not suitable for such extreme application conditions We indicate emphatically that corrosion is not subject to warranties for defects KONVEKTA does not take over any warranties for defect neither for corrosion nor for consequential damage resulting there from nor for damages caused by clea...

Страница 6: ...osition Air circulation is split up between floor and windshield Arrow up flap for windshield The whole air is lead to the windshield Symbol windshield defrost Water valve completely opened air to windshield max imal blower speed The conversion is realized via characteristic curves which also facilitate intermediate positions 3 1 2 Desired value of front box temperature The blowout temperature of ...

Страница 7: ...nce works we refer to our maintenance instructions BWA KL6U022AA which have been written exclusively for maintenance personal Please arrange regular dates for maintenance works and services with a KONVEKTA service station as indicated in maintenance schedule bus no WP07050618 Only qualified staff is allowed to carry out these works For general instructions on repair and maintenance works please co...

Страница 8: ... magnetic clutch compressor does not compress check high and low pressure replace com pressor if necessary excess pressure pressure too high check axial fans check fuses at switchboard clean condenser coil with compressed air excess pressure caused by high out side temperature run unit until pressure has stabilized leakage in a c unit lack of refrigerant check a c unit for leakages refill refriger...

Страница 9: ...of the Council for ma terials that affect the ozone layer Resolution to prohibit certain ozone destroy ing halogen hydrocarbons The used refrigerant endangers the environment When dealing with refrigerants the existing pre scriptions and regulations are to be followed Only qualified staff is allowed to carry out these works Water endangering substances acc to 19g 19l are solid liquid and gaseous s...

Отзывы: