KONICS DPU Series Скачать руководство пользователя страница 9

DPU 

Series

E-10

 Input type

 RMS display

 Input selection

 AUTO/MANUAL selection by terminal input(DI) 

    [no. 7, 11 terminal]

Type

Parameter

AUTO
input

Analog 
input

Current

4-20mA

Input 
impedance
100

Ω

4-20

0-20mA

0-20

Voltage

1-5VDC

Input 
impedance
25

Ω

1-5

0-5VDC

0-5

0-10VDC

0-10

ON/OFF
input

Voltage 
pulse

0/12VDC

SSR

No-voltage 
pulse

ON/OFF

-

Com. input RS485

-

-

COM

MANUAL input

Inside VR

10k

Ω

-

-

Outside VR  3 to 10k

Ω

-

-

This unit measures and displays RMS for accuracy. 

 Ex) At pure resistance load, in normal control, when 

input is 4-20mA and rating is 220V,

 

Output slope manual adjustment [ 

A-GA

] as 

OFF

 

   

 : Select the input by the inside 3-level slide switch

When the AUTO/MAN terminal input is ON(close), it 
is AUTO input operation. When it is OFF(open), it is 
MAN(manual) input operation. 

When the AUTO/MAN terminal input is OFF(open) 
(MANUAL operation), only INT or EXT input selected by 
the 3-level slide switch is available.

In AUTO input, select it at control input type[ 

IN-P

] at 

setting mode1.

In MANUAL input, set output slope manual adjustment 
[

A-GA

] in operating mode as OFF and select the input 

by the inside 3-level slide switch.

In case of static voltage or static current, voltage and 
current displays as below.

Ex) At pure resistance load, in feedback control, when 

input is 4-20mA and rating is 220V or 50A,

Input

4mA

8mA

12mA

16mA

20mA

MV

0%

25%

50%

75%

100%

Display 
voltage

0.0V

70V

155.5V

209.7V

220.0V

Input

4mA

8mA

12mA

16mA

20mA

MV

0%

25%

50%

75%

100%

Display voltage

(static voltage 

control)

0.0

55.0

110.0

165.0

220.0

Display voltage

(static current 

control)

0.0

12.5

25.0

37.5

50.0

Type

Description

MAN

INT

Adjust output slope with the inside VR

MAN

EXT

Adjust output slope with an outside VR

AUTO

No function

 RUN lamp: Turns ON in RUN, turns OFF in STOP

 AUTO lamp: Turns ON in AUTO, turns OFF in MANUAL

 EVT lamp

: Turns ON in Digital Input (DI-1 to 3) ON, 

fl

 ashes in alarm output

 R, S, T lamp

: Turns ON differently by displayed value in display part
Ex) When R, S turn ON, it displays voltage between R-S line

 Display part

: Displays selected display value content in RUN mode, 
displays parameter and set value in SET mode

 V, A lamp

: V lamp turns ON when displaying voltage, 
  A lamp turns ON when displaying current, 
  V, A lamps turn ON when displaying power, 
  V, A lamps turn OFF when displays resistance and input 
  value

 Bar display

: Turns ON as 0 to 100% ratio for selected display value

 

 key

: Used to enter parameter mode, monitoring mode and to 
move between parameters

   ,  key: Used to move setting modes and to set parameters.

 

 key: Used to return to RUN mode from SET mode

<1-phase>

<3-phase>

MAN

MAN

Part descriptions

Control input

Содержание DPU Series

Страница 1: ...control part separately Applicable load all loads such as super kanthal platinum molybdenum carbon halogen lamp chrome nickel etc Number of phases Item Rated current capacity Size Power supply Option DPU Digital Power Controller Unit R RS485 communication D Remote Display Unit A Remote Display Unit RS485 communication N No option 1 110 V 2 220 V 3 380 V 4 440 V 1 1 phase 3 3 phase 1 phase 3 phase ...

Страница 2: ... Display method Display value and SV display 7Segment 4digit Status display 4LED Display value percentage display 11LED Bar Display value and SV display 7Segment 4digit Status display 6LED Display value percentage display 11LED Bar Output accuracy Static voltage feedback control Within 3 F S of rated voltage within variable 10 F S of rated voltage Static current feedback control Within 3 F S of ra...

Страница 3: ...y power for effective noise DI input switch should be for low current and ON resistance should be max 20 Ω including cable resistance DI input terminals are COM DI 1 to 3 RUN AUTO For remote display unit option model use connection cable as our standard cable When connecting it operates as MANUAL When connecting it operates AUTO R S U F G R S U F G R S U F G R S U F G Inside VR 10kΩ 3 level slide ...

Страница 4: ...nductive noise it is recommended to use shielded cable at high frequency power for effective noise DI input switch should be for low current and ON resistance should be max 20Ω including cable resistance DI input terminals are COM DI 1 to 3 RUN AUTO For remote display unit option model use connection cable as our standard cable When connecting it operates as MANUAL When connecting it operates AUTO...

Страница 5: ...A 25 40 50 70 25A 40A 50A are not attached a fan B Size DPU1 B 80 100 120 150 180 200 80 135 154 209 5 110 147 170 60 Fixed 4 M5 82 P1 97 40 150 P2 260 30 3 120 Fixed 4 M5 127 P1 140 50 150 P2 280 30 3 120 135 222 241 5 121 5 151 174 Dimensions ...

Страница 6: ...ze DPU1 C 250 350 D Size DPU1 D 400 500 600 In case of remote display unit RS485 communication option It is recommended for remote panel cable to use max 5 m to prevent noise Check the length when ordering it 250 278 160 494 156 195 Fixed 4 M6 261 P1 278 40 200 P2 280 90 212 418 345 38 4 213 160 365 132 163 Fixed 4 M6 193 P1 213 50 200 P2 179 338 300 38 4 Panel cut out 53 5 0 5 0 100 5 0 5 0 55 10...

Страница 7: ...P2 63 5 26 306 160 235 6 138 200 239 199 183 160 364 176 217 278 Fixed 4 M6 195 P1 213 200 P2 40 280 365 43 1 Panel cut out 53 5 0 5 0 100 5 0 5 0 In case of remote display unit RS485 communication option It is recommended for remote panel cable to use max 5 m to prevent noise Check the length when ordering it 55 102 ...

Страница 8: ...ure transmitter H Temp transmitter I Thermometer J Pressure gauge K Accessories DPU DPUS C Size DPU3 C 250 350 D Size DPU3 D 400 500 600 Fixed 4 M6 261 P1 278 200 P2 280 40 140 5 92 5 450 370 40 125 5 160 489 173 5 227 5 311 Fixed 4 M8 405 P1 427 330 P2 453 66 5 160 746 204 5 275 5 404 5 204 5 167 167 528 463 32 5 ...

Страница 9: ...w Ex At pure resistance load in feedback control when input is 4 20mA and rating is 220V or 50A Input 4mA 8mA 12mA 16mA 20mA MV 0 25 50 75 100 Display voltage 0 0V 70V 155 5V 209 7V 220 0V Input 4mA 8mA 12mA 16mA 20mA MV 0 25 50 75 100 Display voltage static voltage control 0 0 55 0 110 0 165 0 220 0 Display voltage static current control 0 0 12 5 25 0 37 5 50 0 Type Description MAN INT Adjust out...

Страница 10: ...hod setting phase control or cycle control it operates as phase control Set range for start limit 0 to 110 of output Set range for start limit time 0 to 100 sec 0 sec not using this function This function is to adjust manually inside or outside VR output value ratio for control input When AUTO operation and output slope manual adjustment A GA is set as ON SLOP is not able to set It displays slope ...

Страница 11: ...e controls according to control input as the inside VR adjustment or an outside VR adjustment When selecting AUTO close the front AUTO lamp turns ON or selecting MANUAL open the front AUTO lamp turns OFF Select RUN close STOP open operation status by terminal input RUN mode operates as the set contents by control input STOP mode is standby status When selecting RUN close the front RUN lamp turns O...

Страница 12: ...trol or overshoot or hunting After selecting HOLD function and digital input is ON close output and display value of this unit is hold it operates hold when digital input maintains ON close status Proportional constant set P It compensates error from the target value proportionally If proportional constant value is small response is fast and it may cause overshoot or hunting If proportional consta...

Страница 13: ... Current alarm CAL Continues operation Automatically cleared within the set range Heater break alarm HBK Bar Graph display value content selection BAR BAR Load resistance display method DRES DRES You can select display value content for the bar graph Selectable display value content load voltage U V V W W U load current LA U LA V LA W power KW control input REF This function is for display load re...

Страница 14: ...ntage Displays frequency of power IN 10 0 LD V 22 0 LD A 5 0 KW 1 00 RES 50 FREQ 6 00 P P P P P P Input value Load voltage Load current Load power Load resistance Power frequency V V A A 1 For ON OFF input or SSR pulse input it displays 0 or 100 Set range Within 0 0 to 100 0 Monitors measured voltage at load within the rated voltage range Monitors measured current at load within the rated current ...

Страница 15: ...only for static voltage static current static power in phase control Set range 0 to 100 Displayed only when DI 1 of ST 1 is set SP M Set slow up time Set range 0 to 999sec Not displayed when C MD mode is set as cycle control Set slow down time Set range 0 to 999sec Not displayed when C MD mode is set as cycle control OP H OL 50 ST T C LM S LM SP1 S LT SP2 A GA SP3 SLOP SP4 B UP SP5 UP T SP6 DN T P...

Страница 16: ...NA Enables to write DISA Disables to write OP ST 1 DRES 4 20 IN P P F LD C MD ADDR DI 1 BAUD DI 2 COMW DI 3 LOCK IN B SPAN DISP BAR Operating Mode Setting Mode 1 Control input type Control method DI 1 function DI 3 function DI 2 function Input correction Input slope correction Display value content Bar content Load resistance display method Full load auto recognition Com address Com speed Com writ...

Страница 17: ... A FUSE Operating Mode Setting Mode 2 Setting Mode 1 Overcurrent alarm value Element error alarm CH Heat sink overheating alarm CH Fuse break alarm CH Overvoltage alarm CH Overvoltage delay time Overvoltage alarm value Current alarm CH Overcurrent alarm CH Overcurrent delay time Heater break alarm value Heater break alarm CH AL2 AL1 NON AL2 AL1 NON AL2 AL1 NON 1 Displays setting mode 2 RUN mode Pr...

Страница 18: ...default 38400 Data length 8Bit Stop Bit 1Bit Parity Even Max connections 32 units Protocol MODBUS 1 1 RTU Function code 3 0 03 Read holding resisters Master Slave 0 01 0 03 0 00 0 00 0 00 0 16 Add Com mand Start add Number of data CRC 16 High Low High Low High Low Slave Master 0 01 0 83 Address Response command Exception code CRC 16 Slave Master 0 01 0 03 0 10 0 03 0 E8 0 03 0 E8 Add Response comm...

Страница 19: ...73 Reserved Reserved 30117 0074 Reserved Reserved 30118 0075 Coil start address 0 30119 0076 Coil quantity 0 30120 0077 Input start address 0 30121 0078 Input quantity 0 30122 0079 Holding reg start address 0 30123 007A Holding reg quantity 32 30124 007B Input reg start address 0 30125 007C Input reg quantity 5 Input resisters 3 phase Address Item Factor 30001 0000 Load voltage between U V line di...

Страница 20: ...3 Load detector alarm value 0 1 1 to 2000 40021 0014 Display content selection 0 to 3 40022 0015 Bar display mode 0 to 3 40023 0016 Control integer KP value 0 to 9999 40024 0017 Control integer KI value 0 1 1 to 999 9 40025 0018 Output control mode 0 to 6 40026 0019 Event input 1 mode 0 to 4 40027 001A Event input 2 mode 0 to 4 40028 001B Event input 3 mode 0 to 4 40029 001C Auto ref input selecto...

Страница 21: ...BAR 4 LA V 5 LA W 6 KW 7 REF 40023 0016 Proportional value P 1 to 2000 1 40024 0017 Integral value I 0 1 to 999 9 0 1 40025 0018 Control method C MD 1 to 6 1 1 F CY 2 ONOF 3 PA 4 V FB 5 C FB 6 W FB 40026 0019 Digital input 1 DI 1 0 to 5 1 0 SP M 1 SP 1 2 SP 2 3 SP 3 4 RST 5 HOLD 40027 001A Digital input 2 DI 2 1 to 5 1 1 SP 1 2 SP 2 3 SP 3 4 RST 40028 001B Digital input 3 DI 3 5 HOLD 40029 001C Co...

Отзывы: