DPU
Series
E-22
■
Address mapping table
Holding resisters [3-phase]
Address
Item
Parameter
Factor
40001(0000)
Reference value
IN
0.0 to 100.0 (*0.1)
40002(0001)
Soft start time
ST-T
0 to 100 (*1)
40003(0002)
Start limit
S-LM
0.0 to 110.0 (*0.1)
40004(0003)
Start limit time
S-LT
0 to 100 (*1)
40005(0004)
High output limit
H-OL
0.0 to 110.0 (*0.1)
40006(0005)
Low output limit
L-OL
0.0 to 110.0 (*0.1)
40007(0006)
SP1
SP-1
0.0 to 100.0 (*0.1)
40008(0007)
SP2
SP-2
0.0 to 100.0 (*0.1)
40009(0008)
SP3
SP-3
0.0 to 100.0 (*0.1)
40010(0009)
SP4
SP-4
0.0 to 100.0 (*0.1)
40011(000A)
SP5
SP-5
0.0 to 100.0 (*0.1)
40012(000B)
SP6
SP-6
0.0 to 100.0 (*0.1)
40013(000C)
Slow up
UP-T
0 to 999 (*1)
40014(000D)
Slow down
DN-T
0 to 999 (*1)
40015(000E)
Current limit
C-LM
0.0 to 110.0 (*0.1)
40016(000F)
Over current value
OC-V
0.0 to 120.0 (*0.1)
40017(0010)
Over current time
OC-T
0 to 100 (*1)
40018(0011)
Over voltage value
OV-V
0.0 to 300.0 (*0.1)
40019(0012)
Over voltage time
OV-T
0 to 100 (*1)
40020(0013)
Heater break value
HB-V
10.0 to 500.0 (*0.1)
40021(0014)
Display selected contents
DISP
0 to 7 (*1)
0: U-V
1: V-W
2: W-U
3: LA-U
40022(0015)
Bar graph's content
BAR
4: LA-V
5: LA-W
6: KW
7: REF
40023(0016)
Proportional value
P
1 to 2000 (*1)
40024(0017)
Integral value
I
0.1 to 999.9 (*0.1)
40025(0018)
Control method
C-MD
1 to 6 (*1)
1: F-CY
2: ONOF
3: PA
4: V-FB
5: C-FB
6: W-FB
40026(0019)
Digital input 1
DI-1
0 to 5 (*1)
0: SP-M
1: SP-1
2: SP-2
3: SP-3
4: RST
5: HOLD
40027(001A)
Digital input 2
DI-2
1 to 5 (*1)
1: SP-1
2: SP-2
3: SP-3
4: RST
40028(001B)
Digital input 3
DI-3
5: HOLD
40029(001C)
Control input type
IN-P
0 to 6 (*1)
0: 4-20
1: 0-20
2: 1-5
3: 0-5
4: 0-10
5: SSR
6: COM
40030(001D)
Load resistance display method selection
DRES
0 to 1(*1)
0: DOWN
1: UP
40031(001E)
Operation status
-
Bit0...
Bit1...
Bit2...
Bit3...
Bit4...
Bit5...
Bit6...
Bit7...
Bit8...
Bit9...
Bit10...
Bit11...
Bit12...
Fault
I-OC
Over current
Over volt
Over temp
Fuse cut
Phase loss
Load open
Over SCR
Over Freq
Run/Stop
Auto/Manual
EMS Power
40032(001F)
Output slope
SLOP
0.000 to 1.000 (*0.001)
40033(0020)
Base up setting
B-UP
0.0 to 100.0 (*0.1)
40034(0021)
Input correction
IN-B
-99.9 to +99.9 (*0.1)
40035(0022)
Span
SPAN
-99.9 to +99.9 (*0.1)
40036(0023)
Over current alarm
OC-A
0 to 2 (*1)
40037(0024)
Current alarm
C-AL
40038(0025)
Over voltage alarm
OV-A
40039(0026)
Burn out fuse alarm
FUSE
0: NON
1: AL1
40041(0028)
Heat sink temperature abnormal condition alarm
HEAT
2: AL2
40042(0029)
Thyristor abnormal condition alarm
SCR
40044(002B)
Heater break alarm
HB-A