AS-10.22.027
50 (54)
(-) 2006-11-10
KONE MonoSpace®
Maintenance Instruction
© 2006 KONE Corporation
All rights reserved.
Disclosure prohibited
*)
NOTE! For other motor types and special versions apply field support.
3
If F0102 is still active, measure
the voltage between LOPCB
motor current test pins TP1 and
TP2:
Is the voltage over 0.5V when
the elevator is not running?
Defective V3F16L.
NOTE!
When elevator is not running
the voltage should be around
0.4V-0.5V.
When elevator is running the
value is dependent on the type
of elevator but could be like
1.5V to light direction and 4V to
heavy direction.
Replace the defective
V3F16L.
Step
Check
Possible cause
Action