Door Control Board: Board 1Ø4

® 

for PM/SSC

Product Instruction

© 2000 KONE Inc.

61111-149

All rights reserved.

4

(R3) 2000-08-31

FEATURES OF DOOR

OPERATORS WITH BOARD 1Ø4

®

Door operators with Board 1Ø4

®

 control have

following operations and features:

Door control power

Current control

Speed & travel limits

Acceleration & deceleration

Troubleshooting & switch adjusting

Auxiliary piloting

Other features

Door control power. Door operator control uses a
low voltage permanent magnet DC motor. DC motor
is powered by pulse width modulated power (high
speed switching - 20,000 Hz). Motor responds to
average voltage of high frequency pulses, and not
individual pulses.

Current control. Door operator control has a
current sensing circuit in both open and closed
directions to supply feedback to speed control
circuit. Current sensing circuit regulates door closing
force, and open/stall current caused by a hooked
interlock. Current sensing circuit also guarantees
that door operator control relay contacts do not
break or make when motor armature current is
present—helping to prevent damage to relay
contacts. Motor direction is controlled by reversing
armature connection using a conventional relay
system.

Speed & travel limits. Door operator control selects
speed and travel limits with cam operated
microswitches. These microswitches operate relays
tied into speed direction circuits.

Acceleration & deceleration. Door operator control
has an internal soft-start circuit which regulates
smooth acceleration and deceleration. Soft-start
circuit allows average motor voltage to change
gradually when speeds change.

Board 1Ø4

®

Equipment description

Solid state door operators with Board 1Ø4

®

  are described as follows.

Features of door operators with Board 1Ø4

®

Input & output terminals

149-001 (8/2000)

Troubleshooting & adjusting switches. Door
operator control has two small toggle switches
mounted on common circuit board. TEST/RUN
switch and
O-OFF-C switch are used to signal door opening or
closing from car top during troubleshooting and
adjusting; and to disconnect the door open and close
signals, and de-activate internal shutdown timer.

Auxiliary piloting. Door operator control also has a
Form “C” Open and a Form “C” Closed relay contact
for auxiliary piloting.

Other features. Additional items added to Solid
State door control.

Non-adjustable open current limit set at
5 amps.

Non-adjustable internal shutdown timer
removes power if doors do not open or
close within 20 to 30 seconds after a
direction signal is given. Shutdown
indicated by an illuminated LED 7.

F615-002 (3/97)

Содержание Board 1O4

Страница 1: ...Product Instruction Door Control Board Board 1 4 for PM SSC 61111 149 R3 2000 08 31...

Страница 2: ...One KONE Ct Moline IL 61265 Due to our policy of continuing improvement we reserve the right to alter design and specification without prior notice The right to make changes to product design and mat...

Страница 3: ...d 1 4 for PM SSC Equipment description 4 Features of door operators with Board 1 4 4 Input output terminals 5 Installing door operator control Board 1 4 6 Adjusting door operator control Board 1 4 8 M...

Страница 4: ...relay system Speed travel limits Door operator control selects speed and travel limits with cam operated microswitches These microswitches operate relays tied into speed direction circuits Accelerati...

Страница 5: ...ther times Optional DO3 to DO10 Auxiliary to O relay A relay across these terminals should be energized only when doors are opening DO7 to DO17 Auxiliary to C relay A relay across these terminals shou...

Страница 6: ...tor This does not apply to four board systems 4 Remove 45 VDC supply wires and motor wires from power board Mark wires for correct polarity 5 Remove wires connected to main terminal strip on common bo...

Страница 7: ...Door Control Board Board 1 4 for PM SSC Product Instruction 2000 KONE Inc 61111 149 All rights reserved 7 R3 2000 08 31...

Страница 8: ...f procedures as described stop and request assistance A604 017 2 97 Toggle switches To adjust and service door control use two toggle switches on door operator control Board 1 4 TEST RUN switch and O...

Страница 9: ...resistor located between heat sinks Q2 and D2 Viewing from TB1 side of control board right side of resistor R2 is and left side of resistor R2 is 2 Set voltmeter to a low range 1 volt or 2 5 volt 3 R...

Страница 10: ...n OF potentiometer clockwise just enough to move doors through OF speed zone When OSDL microswitch drops LED next to OF potentiometer goes out and LED next to OS potentiometer illuminates 7 Turn OS po...

Страница 11: ...Door Control Board Board 1 4 for PM SSC Product Instruction 2000 KONE Inc 61111 149 All rights reserved 11 R3 2000 08 31 Board 1 4...

Страница 12: ...clockwise until desired door close operation is achieved Door closing force should be less than 30 pound maximum allowed by Code 5 To check door pressure physically stall door at midpoint in closing d...

Страница 13: ...tion Replace door operator cover A604 SI7 2 97 ADJUST NUDGE SPEED 1 Simulate a nudge signal by placing a jumper on terminal strip TB 1 between L1A and DO4 2 Set the TEST RUN switch to TEST position 3...

Страница 14: ...ng CAM drops microswitch when car door clutch has just engaged both hoistway door rollers but should not drop microswitch if door interlock hangs up OSDL CAM drops OSDL microswitch when doors are appr...

Страница 15: ...Door Control Board Board 1 4 for PM SSC Product Instruction 2000 KONE Inc 61111 149 All rights reserved 15 R3 2000 08 31 Door in closed position Door in open position...

Страница 16: ...Door Control Board Board 1 4 for PM SSC Product Instruction 2000 KONE Inc 61111 149 All rights reserved 16 R3 2000 08 31 NOTES...

Отзывы: