Door Control Board: Board 1Ø4
®
for PM/SSC
Product Instruction
© 2000 KONE Inc.
61111-149
All rights reserved.
12
(R3) 2000-08-31
ADJUST DOOR CLOSING FORCE
1.
Toggle TEST-RUN switch to TEST position.
2.
Stop doors at mid-point in closing direction by
toggling O-OFF-C switch to OFF position.
3.
Turn CCL (close current limit) potentiometer fully
counter-clockwise until doors stall.
4.
Turn CCL potentiometer clockwise until desired
door close operation is achieved. Door closing
force should be less than 30 pound maximum
allowed by Code.
5.
To check door pressure, physically stall door at
midpoint in closing direction.
6.
Place rubber end of a pressure gauge (1) on
edge of power-driven car door (3). Read pounds
of force (2) on gauge and record results.
7.
Open and close doors with O-OFF-C switch
several times.
8.
Physically stall doors again in closing direction
and re-check door closing force with pressure
gauge.
If door closing force CANNOT be kept
under 30 pounds, contact the door
factory.
A604-021 (9/2000)