Space in which your massage cabin is located (bathroom), must be designed
according to the national regulations in force. In zones 0, 1, 2 there should be
no switches, sockets or connections placed at your fingertips. They should be
located at least 0.6 m from the massage cabin and of a height of 2.25 m, as
shown in figure below: Picture 2:
ASSEMBLY INSTRUCTIONS
All massage shower enclosures manufactured by Kolpa d.d. should be assembled by
a person authorized by the seller, from whom the enclosure in question was
purchased. In Slovenia, the task is carried out by the official repair service of Kolpa
d.d., while other countries are covered by the official Kolpa d.d. product distributor for
that particular country. Before the arrival of the assembly crew tasked with
assembling and connecting the massage shower enclosure, the space where the
enclosure is to be installed must be properly prepared. The water, electricity and
outflow connection points must be correctly located in line with the enclosed plans for
each massage shower enclosure. While minor deviations in connection point
locations are allowed, major deviations should be discussed with the seller or with the
Kolpa d.d. repair service. If the space is not prepared in a suitable manner, the
person in charge of the assembly shall have the right to refuse carrying out the
assembly until the space is appropriately prepared. In addition, the person in charge
of the assembly has the right to refuse completing the assembly it the required
assembly height is not enabled at the spot where the massage shower
enclosure/massage column is to be installed.
ELECTRICAL WIRING AND FITTINGS
To ensure electrical safety, please adhere to the instructions in this section and
warnings in the
PRECAUTIONS FOR USE
section.
The massage shower enclosure may only be connected by a suitably qualified
company with official authorization to perform this task (i.e. concession).
All Kolpa san massage shower enclosures are compliant with the EN 15200
standard. All electrical wiring within the building where the massage shower
enclosure is to be assembled must comply with the IEC 60364-7-701 standard and
local regulations in effect in individual countries regarding electrical wiring safety.
The massage shower enclosure must be permanently connected to the power supply
network, i.e. plugging it into a socket is PROHIBITED. The connection must be made
via a fault current protection switch (I∆n
30mA) and protected with a 16A safety fuse
(3500 W max.). In addition, it must be possible to break this circuit with a multipole
switch, i.e. a BALLAST. The device enabling the separation of all poles from the
power supply network must be integrated within the electrical wiring in line with the
national wiring-related regulations. For connection, use a conductor with dimensions
3x2.5 mm
2
and double insulation.
The additional earth conductor (cross-section = 6 mm
2
) must be
connected to the connection point for equipotential bonding, which is
marked with the symbol shown on the right:
Содержание Kolpa-San ZEPHYR 1680 3F
Страница 2: ...1 www kolpasan eu PICTURE 1a ...
Страница 3: ...2 www kolpasan eu PICTURE 1b ...
Страница 4: ...3 www kolpasan eu PICTURE 2 ...
Страница 5: ...4 www kolpasan eu PICTURE 3 ...
Страница 6: ...5 www kolpasan eu PICTURE 4 ...
Страница 7: ...6 www kolpasan eu PICTURE 5 ...
Страница 8: ...7 www kolpasan eu PICTURE 6 ...
Страница 18: ...www kolpasan eu ...
Страница 19: ...www kolpasan eu ...
Страница 21: ...ARIA SIMPLE radio ARIA QUAT A0 radio ARIA QUAT A3 radio MELBA SIMPLE radio MELBA M1 radio MELBA M3 radio ...
Страница 22: ...1 www kolpasan eu BILD 1a ...
Страница 23: ...2 www kolpasan eu BILD 1b ...
Страница 24: ...3 www kolpasan eu BILD 2 ...
Страница 25: ...4 www kolpasan eu BILD 3 ...
Страница 26: ...5 www kolpasan eu BILD 4 ...
Страница 27: ...6 www kolpasan eu BILD 5 ...
Страница 28: ...7 www kolpasan eu BILD 6 ...
Страница 38: ...www kolpasan eu ...
Страница 39: ...www kolpasan eu ...