I/O Terminal /
MANUAL CONFIGURATION
29
Byte
Bit
Value
Description
GSE file
0
bin
In multi-configuration mode, the coupler
sets the Stat_Diag bit in the diagnostic
data if the configuration is not
consistent, and does not yet enter data
exchange (default).
3
6
1
bin
In multi-configuration mode the coupler
also enters data exchange even when
the configuration is not consistent,
although Standard-Bus cycles are not
yet executed (see Multi-configuration
mode)
Extended
0
bin
2-byte PLC interface not activated
(default)
5
0
1
bin
2-byte PLC interface is active (see 2-
byte PLC interface)
Extended
0
bin
Response to Standard-Bus error:
manual Standard-Bus reset (default)
(see Standard-Bus interruption)
7
0
1
bin
Response to Standard-Bus error:
automatic Standard-Bus reset
Standard
0
bin
Terminal diagnosis is not active (default)
(see Terminal diagnosis)
7
1
1
bin
Terminal diagnosis is active
Standard
0
bin
Diagnostic data for digital terminals
included in process image (default) (see
Terminal diagnosis)
7
4
1
bin
Diagnostic data of digital terminals not
in the process image (default)
Standard
0
bin
Analog modules are mapped in compact
form (only showing the input and/or
output user data) (this is the default,
only relevant when CfgData checking
has been deactivated, otherwise the
terminals are set by means of the
CfgData) (see Deactivation of CfgData
checking)
9
2
1
bin
Analog modules are mapped in complex
form (with control/status for register
access and with the same data length in
inputs and outputs) (only relevant when
CfgData checking has been
deactivated, otherwise the terminals are
set by means of the CfgData)
Extended
9
3
0
bin
Representation in INTEL format
Standard