I/O Terminal /
MANUAL CONFIGURATION
32
Function Module
Activation of the function
2-byte PLC interface
The 2-byte PLC interface is activated via the UserPrmData (byte
5, bit 0). By default it is not active.
Standard-Bus cycle
counter
The Standard-Bus cycle counter is activated via the UserPrmData
(byte 3, bit 3). By default it is not active.
Dummy output byte
The dummy output byte is activated via the UserPrmData (byte 3,
bit 5). By default it is not active.
6.2.3 Configuration of Complex Modules
After the DP modules for the activated functions of the Bus Coupler have been added to the
Bus Coupler in the DP configuration tool, the next step is for the complex terminals to be
added in the sequence in which they are plugged in, regardless of whether digital terminals
are plugged in between the complex terminals, or of how many there may be:
Complex Function
Module
Description
Associated CfgData (as hex code)
0xB4 (in GSE file)
0xB5 (alternatively)
AKT-CM-000-000
AKT-CM-000-000
0xF2 (alternatively)
0x51 (in GSE file)
AKT-AN-200-000
only the 16 bit input value of
each channel is transmitted
0x50, 0x50 (alternatively)
0x53 (in GSE file)
0x51, 0x51 (alternatively)
AKT-AN-400-000,
AKT-AN-410-000,
AKT-AN-420-000
only the 16 bit input value of
each channel is transmitted
0x50, 0x50, 0x50, 0x50
(alternatively)
0x61 (in GSE file)
AKT-AT-220-000
only the 16 bit input value of
each channel is transmitted
0x60, 0x60 (alternatively)
0x63 (in GSE file)
0x61, 0x61 (alternatively)
AKT-AT-410-000,
AKT-AT-420-000
only the 16 bit input value of
each channel is transmitted
0x60, 0x60, 0x60, 0x60
(alternatively)
0xB5 (in GSE file)
AKT-ENC-000-000
AKT-ENC-000-000
0xF2 (alternatively)