19

KOLDWAVE 3AK (AIRMASTER)

CHECKOUT OF UNIT OPERATION

Koldwave Airmaster portable spot cooler
provides fan-only circulation and cooling
modes. This is accomplished by setting the
controls to operate in any of the following
positions:

FAN ONLY
Plug unit in, Depress the upper mode
selector rocker switch to the left for fan
operation. Rotate the lower fan speed
selector switch to the right for low fan speed,
to the middle for medium speed and to the
left for high speed.

COOLING CYCLE
The green-colored pilot light will illuminate
when mode selector rocker switch is
depressed to the left or right, indicating there
is power to the control panel.

The blue-colored light, indicating the cooling
mode of operation, will illuminate when the
upper mode selector switch is depressed to
the right and the thermostat calls for cooling.
When the blue light is on, the compressor,
and the condenser and evaporator blowers
will be running. Allow the unit to run with fan
speed set on high for twenty minutes and
then turn the thermostat to the desired set
point.

Note the temperature of the air entering the
filter and the temperature of the air leaving
the discharge grille. In a room of 85°F dry
bulb 50% relative humidity, the air
temperature coming from the grille should
be approximately 15°F cooler than the air
returning to the filter.

The red-colored light located below the
blue-colored light will illuminate when the
condensate tank is full. Refer to the
condensate reservoir tank on page 7.

TROUBLESHOOTING GUIDE

SERVICE PROCEDURES
Before troubleshooting this system, read this manual
to determine electrical power and installation
requirements to allow the spot cooler to perform at its
maximum efficiency. Refer to general description,
wiring diagrams and photographs to get an
understanding of how the unit functions.

Service other than routine maintenance should be
performed only by a qualified refrigeration service
person. In service/troubleshooting, there is no
substitute for a good understanding of the Koldwave
Airmaster modes of operation, control systems,
components and safety systems (see service
performance chart).

SYSTEM PERFORMANCE CHART
The chart below shows suction and discharge
pressures (PSIG), plus total amp draw with evaporator
fan on high speed, with condenser motor on high
speed and with condenser blower baffle. The
condenser discharge air is ducted into another area
with a 12" diameter, 10' long flexible duct.

Ambient Temperatures Versus

Suction and Discharge Pressures

Suction

Pressure

109

97

91

89

87

76

72

68

66

105

92.5

89.5

86

83.5

75

71

68

65

Room

Conditions

115°F DB/96°F WB

104°F DB/80°F WB

  95°F DB/83°F WB

  95°F DB/75°F WB

  95°F DB/71°F WB

  80°F DB/67°F WB

  75°F DB/62°F WB

  72°F DB/60°F WB

  67°F DB/57°F WB

115°F DB/96°F WB

104°F DB/80°F WB

  95°F DB/83°F WB

  95°F DB/75°F WB

  95°F DB/71°F WB

  80°F DB/67°F WB

  75°F DB/62°F WB

  72°F DB/60°F WB

  67°F DB/57°F WB

Discharge

Pressure

349

299

268

264

262

210

193

183

170

356

304

272

268

267

216

200

188

172

Use the above chart for reference when suction and discharge
pressure and total amps are a determining factor in analyzing the
problem. Refer to troubleshooting guide when above data can be
useful in determining overcharge or undercharge of unit.

Total

Amps

12.73

11.22

10.44

10.34

10.30

  9.15

  8.87

  8.70

  8.46

16.00

14.40

13.40

13.33

13.30

11.94

11.50

11.30

10.94

Model

3AK2412

3AK3012

Содержание AIRMASTER 3AK

Страница 1: ...ire refrigeration system electrical components condenser and evaporator housed in one attractively designed two tone enamel finish metal cabinet NOMENCLATURE 3 A K 30 1 2 5 Series 50 Hz Air Cooled 208...

Страница 2: ...500 15 500 9 65 95 F DB 75 F WB 40 RH 21 350 14 100 10 25 21 100 13 350 10 25 20 200 12 750 10 00 95 F DB 83 F WB 61 RH 21 900 8 800 10 45 21 700 8 550 10 45 20 850 8 450 10 25 104 F DB 80 F WB 36 RH...

Страница 3: ...30 RH 25 950 21 000 10 00 25 100 20 000 10 00 24 250 18 750 9 75 95 F DB 75 F WB 40 RH 26 550 17 950 10 20 25 800 17 000 10 25 25 050 16 250 10 05 95 F DB 83 F WB 61 RH 27 150 11 250 10 40 26 500 11 0...

Страница 4: ...to virtually any location SERVICEABILITY The Koldwave Airmaster has removable panels to provide full service accessibility The interior is divided into three accessible sections upper front lower fron...

Страница 5: ...selector rocker switch located on the control panel has three functions 1 To provide fan mode only operation when depressed to the left 2 To turn the unit off when set in the center position 3 To act...

Страница 6: ...l box located in the lower back section of the unit The electrical box encases the compressor s run capacitor a transformer the compressor contactor a freeze control a condenser fan speed selector and...

Страница 7: ...sate water from unit 1 With condensate tank and water level detection system which comes standard on unit See detailed drawing and discussion below 2 With optional condensate pump kit shown on page 16...

Страница 8: ...mpressor until temperature levels are safe again The approximate thermostat cut out cut in are 290 140 F HIGH PRESSURE CUT OUT The Koldwave Airmaster incorporates within the refrigeration system a man...

Страница 9: ...9 KOLDWAVE 3AK AIRMASTER ACCESSORIES...

Страница 10: ...ting into the false ceiling plus a duct collar to attach duct to the unit Installation of the flexible duct can be achieved in the following manner 1 Slip one end of the duct over the lay in ceiling p...

Страница 11: ...D 2411 Plenum installed with additional optional accessory kits on plenum inlet and unit discharge Installation Procedure 1 Remove seventeen 10 24 x 1 2 long phillips head screws securing left hand si...

Страница 12: ...12 KOLDWAVE 3AK AIRMASTER...

Страница 13: ...ive equipment production processes and personnel This can be accomplished by optional dual 6 diameter snozzles 23 long compressed and 31 long extended flexible air duct The snozzles are secured to a p...

Страница 14: ...ir duct part 040 C 0025 can be used with this kit for remote spot cooling The duct is secured to a 16 gauge light grey painted galvanneal mounting plate by a clamp part SA019 A 0067 The duct assembly...

Страница 15: ...Single 10 Diameter Evaporator Discharge Duct On application where one large cold air supply duct is desired a mounting plate with a single 10 diameter mounting flange is available which mounts just a...

Страница 16: ...MBLY 1 Disconnect unit power source 2 Open front lower hinged door 3 Pull out plastic drain hose form inside of tank and remove tank from hinged tray Do not drain hose from evaporator drain pan 4 Moun...

Страница 17: ...g provides convenient economical and energy efficient air conditioning in areas where cooling the entire environment is impractical The cool air is directed only where it is aimed or needed without wa...

Страница 18: ...e air conditioner spot cooler for any shipping damage Air conditioners are throughly inspected at the factory and carefully packed If any damage is evident file a claim with the delivering carrier imm...

Страница 19: ...l to determine electrical power and installation requirements to allow the spot cooler to perform at its maximum efficiency Refer to general description wiring diagrams and photographs to get an under...

Страница 20: ...evaporator coil 3 Ice on evaporator coil 4 Obstructed intake 5 Wrong speed on evaporator fan motor 6 Evaporator fan motor miswired 1 Refrigerant leak 2 Plugged cap tubes or strainer 1 Check external...

Отзывы: