TS_622_02 PowerWAVE 9500DPA User Manual 26/2/19
74
10
Specification
10.1 Introduction
This system comprises a cabinet that can be populated with up to five 100kVA power modules that operate in
parallel within the cabinet to provide the cabinet’s rated output. Each power module is a self-contained UPS
and incorporates a rectifier, inverter and static bypass. Six of the cabinets shown can be connected together to
form a 3 MVA parallel system.
10.2 Mechanical data
10.2.1 UPS Cabinet
Maximum cabinet rating
500 kVA / 500kW (with 5 power modules fitted)
Dimensions (W x D x H) mm
1580 x 940 x 1975
UPS Type
On-line, transformerless, modular, decentralized parallel architecture
Parallel capability
Up to 6 frames (with up to 5 x 100 kVA modules in each frame)
Battery
Not included
Performance specification
VFI-SS-111
Weight
975 kg (with five power modules fitted)
Colour
Black (RAL 9005)
Positioning
Min. 200mm space required at the rear for ventilation
Min. 1500mm space required at front for access
Min. 400mm space required at the rear for ventilation
Input/output power cabling
From the top or bottom