4.7
Replacing the battery
4.7.1
Unscrew Battery retaining cap situated at the front right of the fire and
remove the battery
4.7.2
Replace in the reverse order using a 1.5V AA Alkaline Battery.
4.8
Removing the Oxy-Pilot Assembly
Note : Because this appliance is fitted with an atmosphere sensing ‘Oxy-Pilot’ it is not
possible to replace the thermocouple separately, because the thermocouple position
is factory set to a tight tolerance. Any replacement of parts on the pilot requires a
complete new pilot assembly.
4.8.1
Remove the burner assembly as in section 4.1
4.8.2
Unscrew and remove the thermocouple retaining nut from the end of the
control tap, disconnect the ignition lead from the pilot electrode and the
two inline leads from the microswitch.
4.8.3
Unscrew and remove the two pozi-drive screws which secure the pilot
assembly to the burner. Remove the pilot.
4.8.4
Re-assemble in reverse order and carry out a gas tightness test.
4.9
Replacing the Control Cable
4.9.1
The control lever operating cable can be seen running across the base
of the fire, below the burner. To release the cable, unscrew the cable
securing screw located in the centre of the aluminium operating arm
and pull the cable out from its fixing hole. Release the other end of the
cable by pushing the cable towards the right i.e. into the operating arm
so as to release the tension. Pull the cable nipple out of the retaining
hole and remove the cable through the slot in the operating arm.
See figure 26 below.
Fig. 26
32