background image

33

Insert the tube to connect as far as the
tube stopper contacts the tubes. Pull the
tube to confirm the connection.
For tube removal, push the release ring
forward parallel to the ring, and pull the
tube out.

Tube installation and removal

Either nylon or urethane tubes can be
used. Use tubes that are not scratched on
their outer surface.
The tube’s outer diameter tolerance
should be within 

±

0.1mm [

±

0.004in.] of

the nominal dimension, and within 0.2mm
[0.008in.] for the ellipticity (difference
between long and short diameter).

Tubes

Caution: Do not excessively bend the tube near

fittings.

Subsonic speed flow when 
P

1

0.1013

1.89 (P

2

0.1013)

Q

226S 

Δ

P (P

2

0.1013)

Sonic speed flow when 
P

1

0.1013

1.89 (P

2

0.1013)

Q

113S (P

1

0.1013)

Q: Air flow rate

R

/min (ANR)

S: Effective area

mm

2

Δ

P: Pressure drop P

1

P

2

MPa

P

1

: Upstream pressure

MPa

P

2

: Downstream pressure

MPa

Corrections for variances in air temperature

Multiply the flow rate calculated in the formula
above by the coefficients in the table below.

Since the 1(P) and exhaust ports are on
both ends of the manifold, piping direction
can be selected depending on the
application (excluding some models).
At shipping, plugs are temporarily
screwed in ports at one end, but are not
firmly tightened. Regardless of which end
piping is connected, always remove the
plugs, use sealing tape or apply other
sealing agent, and securely tighten the
plugs into the unused ports.

1.

Sealing tape wrapping method

q

Before piping, use air blowing (flushing)
or cleaning to eliminate any machining
chips, cutting oil, or dust, etc., remain-
ing inside the pipes.

w

When screwing in piping or fittings,
caution should be taken to avoid letting
machining chips or sealing materials
from entering into the valves. When
using sealing tape, wrap it so that 1.5

2 screw threads remain.

Piping

Remain about 2 screw

 theads

Sealing tape

Wrapping direction

How to find the flow rate

Air temperature
°C [°F]
Correction
coefficient

–20

[–4]

1.08

–10

[14]

1.06

0

[32]

1.04

10

[50]

1.02

30

[86]

0.98

40

[104]

0.97

50

[122]

0.95

60

[140]

0.94

M3
M5

×

0.8

Rc (PT )1/8
Rc (PT)1/4
Rc (PT) 3/8
Rc (PT) 1/2
Rc (PT) 3/4
Rc (PT) 1
Rc (PT) 1 1/4
Rc (PT) 1 1/2

59 (6) [5.2]
157 (16) [13.9]
686

883 (70

90) [60.8

78.1]

1177

1373 (120

140) [104

122]

2157

2354 (220

240) [191

208]

2746

2942 (280

300) [243

260]

2746

2942 (280

300) [243

260]

3530

3727 (360

380) [313

330]

3923

4119 (400

420) [347

365]

4707

4903 (480

500) [417

434]

2.

Tightening torque for piping

1.

While any mounting direction is
allowed, be sure to avoid strong shocks
or vibrations applied directly to the
body. Also, avoid strong shocks in the
lateral direction when using a mounting
base for installation. For the order code,
see the Additional Parts item under
each series.

2.

Avoid using in the locations and
environment listed below, as it could
result in malfunction of the valve. If use
in such conditions is unavoidable,
always provide a cover or other
adequate protective measures.

Location directly exposed to water
drops or oil drops

Environment where a valve body is
subject to dew condensation

Location directly exposed to machining
chips, dust, etc

3.

Install a muffler, etc. in the exhaust port
to prevent dust from entering into the
piping.

4.

In piping connection with valves, flush

the tube completely (by blowing
compressed air) before piping.
Intrusion of machining chips or sealing
tape, rust, etc., generated during
plumbing could result in air leaks and
other defective operations.

5.

When mounting a valve unit inside the
control panels or when the operation
requires long energizing periods,
consider providing heat radiation
measure such as ventilation.

6.

Never use the valve with the 4(A) and
2(B) ports vent to atmosphere.

Mounting

Can be used without lubrication. When the
actuator requires lubrication, use Turbine
Oil Class 1 (ISO VG32) or the equivalent.
Avoid using spindle oil or machine oil.

Lubrication

1.

Use air for the media. For the use of
any other media, consult us.

2.

Air used for the cylinder should be
clean air that contains no deteriorated
compressor oil, etc. Install an air filter
(filtration of 40 µm or less) near the
valve to remove collected liquid or dust.
In addition, drain the air filter
periodically.

3.

When supply pressure is low, use
piping for the 1(P) port with sufficient
tube size.

Media

The product cannot be used when the
media or ambient atmosphere contains
any of the substances listed below.
Organic solvents, phosphate ester type
hydraulic oil, sulphur dioxide, chlorine gas,
or acids, etc.

Atmosphere

To close the unused stations, use a block-
off plate.
For the order code, see the Additional
Parts item under each series.

Block-off plate

Cautions: 1. For the 1(P) port piping, use a size

that matches the manifold’s piping
connection port.

2. When installing piping or mufflers to

the exhaust port, ensure there will
be minimum exhaust resistance.

3. On rare occasions, exhaust can

interfere with other valves and
actuators. In this case, let exhaust
from the R ports on both ends.

4. When a multiple number of valves

are operating simultaneously on a
multi-unit manifold, or during high
frequency applications, supply air
from the 1(P) ports on both ends,
and let exhaust from the R ports on
both ends.

5. Since the twin solenoid valve uses 2

stations, it cannot be mounted on
the final station.

6. In the 025 series, the seal between

the valve and manifold is used
reversed top-to-bottom, in accord-
ance with the valve function (NC or
NO). Install the seal as the mark
(NC or NO) is located on the valve
side and matches the valve function.

General Precautions

Suitable tightening torque 

N

cm (kgf

cm) [in

lbf]

Connection 

thread

Содержание 180 Series

Страница 1: ...INSTRUCTION MANUAL Ver 1 0 BK UV002 Ver 1 0 SOLENOID VALVES 180 SERIES Air Valve BK UV002 Ver 1 1 Ver 1 1 ...

Страница 2: ...using in the locations and environment listed below as it could result in malfunction of the valve If use in such conditions is unavoidable always provide a cover or other adequate protective measures Location directly exposed to water drops or oil drops Environment where a valve body is subject to dew condensation Location directly exposed to machining chips dust etc 3 Install a muffler etc in th...

Страница 3: ...r wire DC12V Black DC24V Black w and e are for with DIN connector Order code 39 w and e are for with DIN connector Order code 39 w e Short circuit protection diode Solenoid Flywheel diode Lead wire DC12V Brown Lead wire Black DC24V Red LED indicator Red Lead wire Black Lead wire DC12V Brown LED indicator Light Emitting Diode DC24V Red Solenoid Lead wire AC100V Yellow Varistor or w e e w or AC200V ...

Страница 4: ...n the clockwise direction as far as position A This achieves the same conditions as when the 14 SA side is energized and the manual override button manual lever is locked in place For the 12 SB side turn it in the counterclockwise direction as far as position B To release the lock return the manual override button manual lever to the 0 position A spring mechanism returns the manual override button...

Страница 5: ...g types variety of made to order ol and wiring types the nd 3L is wiring type 39 A compact connector that is highly resistant to dust and water splashes Employs a self stripping method that eliminates the need for de sheathing the lead wire LED indicator L The LED indicator for confirmation of operation is also available without a plug connector This creates a clean monoblock look with a compact c...

Отзывы: