KAL-EX
Seite 6
KAL-EX K05/0322
6. Mechanical Connection
6.1 Before installation
Make sure that the actual flow speed corresponds to the switching range of the
device. Make sure that the maximum process pressures and service temperatures
specified for the device will not be exceeded. (See section
12
, “Technical details”)
6.2 Installation
Mount the sensor in the piping and ensure that the tip is covered by the liquid to be
monitored. The sensor tip must extend at least 5 mm (better > 5 mm) into the pipe
(see below).
6.3 Mounting position
The sensors can be mounted in any position,
provided that the piping is completely filled
with the liquid to be monitored. The
installation position must be free of swirling
and turbulence (the recommended inlet and
outlet area: 4x the diameter of the pipe with
straight pipe sections immediately upstream
and downstream of the sensor). If it is
expected that the liquid will leave deposits in
the piping, the illustrated mounting position is
recommended (see figure at the left).
Caution: Improper installation can result in zone carry-over.
Danger of explosion!
Ablagerungen
Deposits
Содержание KAL-0312 EX
Страница 1: ...Operating Instructions for Flow sensor model KAL Ex with Electronic Analyzer Model KAL E Ex...
Страница 17: ...KAL EX KAL EX K05 0322 page 17 16 EC type examination certificate...
Страница 18: ...KAL EX page 18 KAL EX K05 0322...
Страница 19: ...KAL EX KAL EX K05 0322 page 19 17 IECEx certificate...
Страница 20: ...KAL EX page 20 KAL EX K05 0322...
Страница 21: ...KAL EX KAL EX K05 0322 page 21...
Страница 22: ...KAL EX page 22 KAL EX K05 0322...
Страница 23: ...KAL EX KAL EX K05 0322 page 23...