DVZ K04/0810
Wetted parts
Sensor housing:
PPS, fibreglass-reinforced
Sensor:
PVDF
Connections:
brass (from 32 L/min nickel plated
from 40 L/min blank) or
stainless steel 1.4404
Bluff body:
PPS, fibreglass-reinforced or
oxide ceramic (non-wear version)
Seal:
NBR, EPDM or FPM
DVZ-...S300, DVZ-…S30D
Display:
duo-LED for switching condition
and when range limit is exceeded
Switching output:
relay changeover, max. 1 A/30 V
DC
or active 24 V
DC
, N/C / N/O
Switch point:
measuring range beginning from 90% f.s.
in 10%-steps
can be configured by the customer using a
rotary switch
Power supply:
24 V
DC
± 20%
Power consumption:
12 mA
Electrical connection:
plug M12x1.5 pole
Measuring range overflow:
flash of the DUO-LED (red/green)
from 105 % of f.s.
DVZ-...F300, DVZ-…F390
Impulse output:
PNP, Open Collector, max. 200 mA
Frequency at f.s.
500 Hz (…F300)
50…1000 Hz (F390)
Power supply:
24 V
DC
± 20%
Power consumption:
5 mA
Electrical connection:
plug M12x1
Measuring range overflow:
F
out
approx. 2 kHz from 105 % of f.s.
DVZ-...L303; DVZ-...L343
Output:
0(4)-20 mA, 3-wire
Max. load:
500
Ω
Power supply:
24 V
DC
± 20%
Electrical connection:
plug M12x1
Measuring range overflow:
I
out
approx. 20,5 mA from 103 % of f.s.
DVZ-...L443 (usage with AUF-3000)
Output:
4-20 mA, 3-wire
Max. load:
500
Ω
Power supply:
24 V
DC
± 20%
Electrical connection:
plug DIN 43650
Measuring range overflow:
I
out
approx. 20,5 mA from 103 % of f.s.
Содержание DVZ series
Страница 1: ...Operating Instructions for Compact Vortex Flow Meter Model DVZ ...
Страница 23: ...DVZ DVZ K04 0810 page 23 DVZ sensor with fixed connection measuring range from 40 L min AF o ...
Страница 25: ...DVZ DVZ K04 0810 page 25 DVZ sensor with strengthened connection measuring range from 40 L min o AF ...
Страница 28: ...DVZ page 28 DVZ K04 0810 13 2 Dimensions Electronics DVZ S30x DVZ F3x0 DVZ L3x3 DVZ L443 ...
Страница 29: ...DVZ DVZ K04 0810 page 29 DVZ C3xx ...
Страница 30: ...DVZ page 30 DVZ K04 0810 DVZ Exxx DVZ Gxxx ...