15. Use in Ex areas
15.1 General information
The flow meter is intended for commercial systems and may only be used in
accordance with the information in the technical documentation from Kobold and
the information on the nameplate. It is operated exclusively together with certified
products via an intrinsically safe circuit. They correspond to the applicable
standards and regulations. The installation regulations (e.g. EN 60079-14) for
systems in potentially explosive areas must be considered.
15.1.1
General safety information
The flow meter corresponds to the state of the art and is operationally safe. The
flow meter can bear a residual risk if it is used and operated improperly by
untrained personnel. Every person who is entrusted with the installation,
commissioning, maintenance or repair of the flow meter must have read and
understood the assembly instructions and in particular the safety instructions.
a) When selecting a product and using it as intended, follow the general rules of
technology.
b) All connected electrical and mechanical equipment must be suitable for the
respective application.
c) Observe the information in these operating instructions as well as the
conditions of use and permissible data that appear on the imprints /
nameplates of the respective products.
d) It must be ensured that only the product types of protection that correspond
to the zones are installed!
e) The product is only approved for appropriate and intended use in a normal
industrial atmosphere. Immersion in liquids is not permitted.
f) It must be ensured that no falling objects can hit the product. If there is a risk
of impact sparks, external housing parts made of light metal must be installed
in a protected manner.
g) The operator must ensure lightning protection for the entire system in
accordance with local regulations.
h) It is the responsibility of the installer to ensure that the flow meter functions
properly in connection with the individual evaluation devices and that it is
approved for the intended purpose.
i) A safe to operate and non-critical medium is elementary for this type of
protection and must be strictly adhered to!
15.1.2
Intended use
a) To ensure safe operation, the products may only be used in accordance
with the information in the assembly instructions. When using the device,
the legal and safety regulations required for the respective application
must also be considered. This also applies analogously to the use of
accessories.
Содержание DON-05
Страница 1: ...Operating Instructions for Oval Wheel Flowmeter High pressure Model DON H...
Страница 9: ...DON H DON H 01 0721 page 9 Note The electronic option H0 is available with reed switch output...
Страница 14: ...DON H page 14 DON H 01 0721 7 4 2 Wiring with ZOK ZxP a Circuit with Hall sensor b Circuit with Reed switch...
Страница 43: ...DON H DON H 01 0721 page 43 17 Statement of Conformity...
Страница 44: ...DON H page 44 DON H 01 0721...
Страница 45: ...DON H DON H 01 0721 page 45...
Страница 46: ...DON H page 46 DON H 01 0721...
Страница 47: ...DON H DON H 01 0721 page 47...
Страница 48: ...DON H page 48 DON H 01 0721 18 State of safeness...