14
¥
Auto
+5°C
Point 1
-15°C
Point 2
(Diagram: Heating Curve)
e
The heating curve
The correspondence of the flow temperature to
the outdoor temperature can be set directly and
read directly. The setting is carried out by two
points:
Point 1:
Flow temperature at atmospheric temperature of
+5°C (setting range from 20°C to 90°C).
Point 2:
Flow temperature at atmospheric temperature of -
15°C (setting range from 20°C to 90°C).
I M P O R T A N T:
Point 2 always has to be set higher than Point 1!
The two points marked indicate the factory set-
ting. Point 1 is set to 43°C and Point 2 to 64°C.
This is equivalent to a steepness of approx. 1.5.
Room thermostat (ECO-ZR-QA):
The Model QAA 35 Room Thermostat can be
used with or without influence by the room tem-
perature.
Switch positions possible:
-
Position:
Heating operation according to clocked pro-
gramme as set in the ECOTRONIC.
-
Position:
Normal temperature continuously.
(The operating mode set in the ECOTRONIC
will be ignored.)
-
Position:
Reduced temperature continuously.
(The operating mode set in the ECOTRONIC
will be ignored.)