11
6.3 Boiler and loader system (F3/F4)
6.3.1 The F3 KEY: "PYROT Parameters"
(mask number) parameter (factory setting)
(01) Storage unit temperatures ( - ):
Indication of all the storage unit temperatures
(Indication only for storage unit option)
(02) Return flow, boiler (70°C):
Set point value for boiler backflow circuit valve
(03) Forward flow, boiler (80°C):
Set point value for boiler temperature
(04) Exhaust gas, boiler (200°C):
Limit of maximum exhaust gas temperature
(05) Exhaust gas, residual O2 (7%):
Set point value for residual oxygen for air vent
control
(06) O2-control (ON):
If the lambda sensor is defective, the O2-control
system can be switched off (emergency opera-
tion).
(07) Air vents without O2-control system
(100%):
Position of the air vents with O2-control switched
off (only with O2-control system switched off)
(08) Carry away excess heat at (95°C):
Limit temperature for carrying away excess heat
(10) Load storage unit with oil/gas operation to
(storage unit at bottom):
To which heat storage sensor should the storage
unit be loaded with oil/gas operation?
(Indication only with option of storage unit and
oil/gas burner on PYROT ECO)
(11) Load storage unit with oil/gas operation to
(70°C):
To what temperature should the storage unit be
heated up with oil/gas operation?
(Indication only with option of storage unit and
oil/gas burner on PYROT ECO)
(12) System Temperature Set Point Minimum
(50°C):
Minimum forward flow temperature for heat distri-
bution provided by customer (only if System Tem-
perature Set Point Minimum YES
Æ
Service
Menu)
(14) Load storage unit to (STORAGE UNIT AT
BOTTOM):
To which heat storage sensor should the storage
unit be loaded with wood operation?
(Indication only for storage unit option)
(15) Load storage unit to (80°C):
To what storage unit temperature should the stor-
age unit be heated up with wood operation?
(Indication only for storage unit option)
(16) Storage Unit Management, Temperature,
Storage Unit Average (80°C):
Set point value, average temperature, storage unit
Æ
boiler output is reduced according to loading of
storage unit.
(Indication only for storage unit option)
(17) Start boiler when the system temperature
is fallen short of. Set point (accumulator sen-
sor at bottom):
When the accumulator sensor falls short of the
system set point, the boiler will be heated up.
(Indication only for storage unit option)
(20) External release for boiler (NO):
Is the boiler to be switched on and off by an ex-
ternal floating contact?
(Indication only with the option "Automatic Start,
External Prompt".)
(21) Material take-back larger with air vent po-
sitioning (50%):
Material take-back by means of adjustable air
vent positioning.
(23) Feed auger cycle heat-up (5%):
Insertion of material after ignition
(24) Feed auger, maximum (100%):
Maximum insertion of material
(25) Pneumatic boiler tube cleaning system
(500 s):
Cleaning cycle for the pneumatic cleaning system
(28) Wood operation, load ( 0 ):
Operating hours/minutes, full load, PYROT
(30) Oil/Gas operation ( 0 ):
Operating hours/minutes, oil/gas operation, PY-
ROT ECO
(31) Date/Year (current):
Set year
(32) Date/Month (current):
Set month
(33) Date/Day (current):
Set day
(34) Date/Day of week (current):
Set day of week
(35) Date/Hours (current):
Set hours
(36) Date/Minutes (current):
Set minutes
(40) Enter permanent code (-):
(41) Measurement operation (NO):
This activates measurement operation for chim-
ney sweep measurements.
IMPORTANT: The control of output is then not
functioning: provide for sufficient thermal accep-
tance.
Содержание KOB PYROT SERIES
Страница 1: ...Operation and Maintenance Instructions PYROT 100 to 540 ID 106811 H English ...
Страница 29: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...
Страница 30: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...
Страница 31: ...Leerseite für Notizen Blank page for notes Page en blanc pour des notationes ...