Description

Air Quality Sensor KNX AQS-UP basic

 • Version: 24.03.2016 • Technical changes reserved. Errors reserved.

1.

Description

The 

Air Quality Sensor KNX AQS-UP basic

 measures the CO

2

 concentration in the

room. The sensor can receive an external CO

2

 value via the bus and process it with the

own data to an overall value (mixed value, e.g. room average).

The 

KNX AQS-UP basic

 provides four switching outputs with adjustable threshold

values. The switching outputs and further communication objects can be linked by
AND and OR logic gates. Additionally, an integrated actuating variable comparator can
compare and output values that are received via communication objects.
An integrated PI controllers allows for control of ventilation depending on CO

2

 concen-

tration.

The housing is completed with a frame of the switching series installed in the building
and thus merges with the interior.

Functions:

Measurement of 

CO

2

 concentration

 of the air

Mixed value

 from own measured value and external value (proportions can 

be set in percentage) 

PI controller for ventilation

 depending on CO

2

 concentration: 

dehumidification/humidification (one step) or dehumidification (one or two 
step)

4 switching outputs

 with adjustable threshold values (Threshold values can 

be set by parameter or via communication objects)

8 AND and 8 OR logic gates

 with each 4 inputs. Every switching incident as 

well as 8 logic inputs (in the form of communication objects) may be used as 
inputs for the logic gates. The output of each gate may optionally be configured 
as 1 bit or 2 x 8 bits

2 actuating variable comparators

 for output of minimum, maximum or 

average values. Each with 5 inputs (for values received via communication 
objects)

Configuration is made using the KNX software ETS. The 

product file

 can be down-

loaded from the Elsner Elektronik website on 

www.elsner-elektronik.de

 in the “Ser-

vice” menu.

1.0.1. Scope of delivery

Housing with display, buttons and sensor board

CO

2

 sensor unit

Base plate

You will need

 in addition

 (not supplied):

Socket Ø 60 mm, 42 mm deep 

Frame (for element 55 x 55 mm), suitable for the switching programme used in 
the building

Содержание AQS-UP basic

Страница 1: ...Installation and Adjustment KNX AQS UP basic Air Quality Sensor Article numbers 70224 white 70225 aluminium 70226 anthracite 70227 stainless steel EN...

Страница 2: ...ssembly of the sensor 7 2 5 Notes on mounting and commissioning 7 3 Transfer protocol 9 3 1 List of all communications objects 9 4 Parameter setting 13 4 1 Behaviour on power failure restoration of po...

Страница 3: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 4: ...own measured value and external value proportions can be set in percentage PI controller for ventilation depending on CO2 concentration dehumidification humidification one step or dehumidification one...

Страница 5: ...period After this the CO2 sensor will recalibrate every two weeks by defining the lowest meas ured value captured during that period without interruption of the bus voltage as a reference for fresh a...

Страница 6: ...be used for its intended purpose Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediate...

Страница 7: ...om ducts which lead from other rooms or from the outside to the junction box in which the sensor is mounted Measurement variations from such sources of interference must be corrected in the ETS in ord...

Страница 8: ...e metal frame so that sensor and frame are fixed 2 5 Notes on mounting and commissioning Never expose the device to water e g rain or dust This can damage the electronics You must not exceed a relativ...

Страница 9: ...8 Installation and commissioning Air Quality Sensor KNX AQS UP basic Version 24 03 2016 Technical changes reserved Errors reserved...

Страница 10: ...ut 9 008 C R T 101 CO2 maximum value request Input 1 017 C W 102 Maximum CO2 reading Output 9 008 C R T 103 Reset CO2 maximum value Input 1 017 C W 104 CO2 threshold value 1 Absolute value Input Outpu...

Страница 11: ...hreshold value 4 Absolute value Input Output 9 008 C R W T U 123 CO2 threshold value 4 1 0 Input 1 002 C W 124 CO2 threshold value 4 Switching delay from 0 to 1 Input 7 005 C W 125 CO2 threshold value...

Страница 12: ...le Input 5 Input 5 010 C W 147 Comparator 2 actuating variable Out put Output 1 001 C R T 148 Comparator 2 actuating variable Block Input 1 002 C W 149 AND logic 1 1 bit switching output Output 1 002...

Страница 13: ...ut Output 1 002 C R T 182 OR logic 1 8 bit output A Output 5 010 C R T 183 OR logic 1 8 bit output B Output 5 010 C R T 184 OR logic 1 Block Input 1 002 C W 185 OR logic 2 1 bit switching output Outpu...

Страница 14: ...5 010 C R T 207 OR logic 7 8 bit output B Output 5 010 C R T 208 OR logic 7 Block Input 1 002 C W 209 OR logic 8 1 bit switching output Output 1 002 C R T 210 OR logic 8 8 bit output A Output 5 010 C...

Страница 15: ...be saved and sent to the bus Use the Reset CO2 max value object to reset the value to the current reading Note The values are not retained after a reset Send delay after power up and programming for...

Страница 16: ...hold value must be defined which will be valid un til the 1st communication of a new threshold value For units which have already been taken into service the last communicated threshold value can be u...

Страница 17: ...LV above 1 LV hysteresis below 0 LV above 0 LV hysteresis below 1 LV below 1 LV hysteresis above 0 LV below 0 LV hysteresis above 1 Delays can be set via objects in seconds No Yes Switching delay fro...

Страница 18: ...is setting The status object shows the current status of the output variable 0 OFF 0 ON and can for example be used for visualisation Switching output sends on change Do not send message Send switchin...

Страница 19: ...e limit A set target value will be retained until a new value or a change is transferred The cur rent value is saved in EEPROM so that this is retained in the event of a power supply failure and will...

Страница 20: ...longer until the necessary variable for the target value deviation is reached You should set the time appropriate to the ventilation system at this point follow the manufacturer s instructions Now det...

Страница 21: ...ri odically Send cycle is only sent if periodically is selected 5 s 10 s 30 s 5 min 2 h From change of is only sent if on change is selected 1 2 5 10 20 25 Analysis of the blocking object at value 1 b...

Страница 22: ...ue 0 1 Logic output sends two 8 bit objects Type of objects Value 0 255 Percent 0 100 Angle 0 360 Scenario load 0 127 if logic 1 object A value Setting dependent on type of object if logic 0 object A...

Страница 23: ...do not send message send value for logic 0 send value for logic 1 Value of the parameter Send behaviour Settings options Behaviour of the switching output on release on change of logic do not send me...

Страница 24: ...tput CO2 3 Switching output CO2 3 inverted Switching output CO2 4 Switching output CO2 4 inverted CO2 controller status ventilation 1 CO2 controller status ventilation 1 inverted CO2 controller status...

Страница 25: ...24 Parameter setting Sensor KNX AQS UP basic from software 3 1 Status 24 03 2016 Technical changes reserved Errors reserved AND logic output 8 inverted...

Страница 26: ...GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0...

Отзывы: