Parameter setting
Sensor KNX AQS-UP basic
• from software 3.1 • Status: 24.03.2016 • Technical changes reserved. Errors reserved.
4.7.1. AND and/or OR logic 1/2/3/4/5/6/7/8
AND- and OR logic gates provide the same setting options. Assign the inputs to a
switching event and set the send behaviour.
If the logic output sends one 1-bit object:
If the logic output sends two 8-bit objects:
Block
Logic outputs can also be blocked using objects.
1. / 2. / 3. / 4. Input
• do not use
• all switching events which are available
to the sensor (see
AND logic connection
inputs
, page 22)
Logic output sends
• one 1-bit object • two 8-bit objects
Logic output sends
one 1 bit object
if logic = 1
object value
1 • 0
if logic = 0
object value
0 • 1
Logic output sends
two 8 bit objects
Type of objects
• Value (0 ... 255)
• Percent (0% ... 100%)
• Angle (0°... 360°)
• Scenario load (0 ... 127)
if logic = 1
object A value
Setting dependent on "type of object"
if logic = 0
object A value
Setting dependent on "type of object"
if logic = 1
object B value
Setting dependent on "type of object"
if logic = 0
object B value
Setting dependent on "type of object"
Send behaviour
• on change of logic
• on change of logic to 1
• on change of logic to 0
• on change of logic and periodically
• on change of logic to 1 and periodically
• on change of logic to 0 and periodically
• on change of logic + receipt of object
• on change of logic + receipt of object and
periodically
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s • 1 min • … • 2 h
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Blocking object value before 1st communi-
cation
0 • 1