background image

18

Parameter setting

Sensor KNX AQS-UP basic

 • from software 3.1 • Status: 24.03.2016 • Technical changes reserved. Errors reserved.

Controller target value

The target values can be set directly in the application program using parameters, or
be defined via the bus using a communications object.

Target value setting using parameter:

Set the target value directly.

Setting a target value via communications object:

Enter how the target value will be received from the bus in advance. Basically, a new
value can be received, or simply a command to increase or decrease.

During initial commissioning, a target value must be provided which will be valid until
the 1st communication of a new target value. For units which have already been taken
into service, the last communicated target value can be used. Basically, an air humidity
range is given in which the target value can be changed (object value limit).

A set target value will be retained until a new value or a change is transferred. The cur-
rent value is saved in EEPROM, so that this is retained in the event of a power supply
failure and will be available once the power supply is restored.

Send status object(s)

• on change 
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically

Send cycle
(

is only sent if "periodically" is selected)

5 s • ... • 5 min • … • 2 h

Target value setpoint using

Parameter

 • Communications object

Target value in ppm

400…5000; 800

Threshold value setpoint using

Parameter • 

Communications object

The last communicated value should be 
retained

• never 
• after restoration of power
• after restoration of power and 
  programming

Start target value in ppm
valid till 1st communication

(not upon saving the target value after pro-
gramming)

400… 5000; 800

Object value limit (min) in 0.1°C

400…5000; 400

Object value limit (max) in 0.1°C

400…5000; 1500

Type of threshold change

Absolute value • Increase/decrease

Step size in ppm

(upon increase/decrease change)

1 • 2 • 5 • ... • 20 • ... • 100 • 200

Содержание AQS-UP basic

Страница 1: ...Installation and Adjustment KNX AQS UP basic Air Quality Sensor Article numbers 70224 white 70225 aluminium 70226 anthracite 70227 stainless steel EN...

Страница 2: ...ssembly of the sensor 7 2 5 Notes on mounting and commissioning 7 3 Transfer protocol 9 3 1 List of all communications objects 9 4 Parameter setting 13 4 1 Behaviour on power failure restoration of po...

Страница 3: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 4: ...own measured value and external value proportions can be set in percentage PI controller for ventilation depending on CO2 concentration dehumidification humidification one step or dehumidification one...

Страница 5: ...period After this the CO2 sensor will recalibrate every two weeks by defining the lowest meas ured value captured during that period without interruption of the bus voltage as a reference for fresh a...

Страница 6: ...be used for its intended purpose Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediate...

Страница 7: ...om ducts which lead from other rooms or from the outside to the junction box in which the sensor is mounted Measurement variations from such sources of interference must be corrected in the ETS in ord...

Страница 8: ...e metal frame so that sensor and frame are fixed 2 5 Notes on mounting and commissioning Never expose the device to water e g rain or dust This can damage the electronics You must not exceed a relativ...

Страница 9: ...8 Installation and commissioning Air Quality Sensor KNX AQS UP basic Version 24 03 2016 Technical changes reserved Errors reserved...

Страница 10: ...ut 9 008 C R T 101 CO2 maximum value request Input 1 017 C W 102 Maximum CO2 reading Output 9 008 C R T 103 Reset CO2 maximum value Input 1 017 C W 104 CO2 threshold value 1 Absolute value Input Outpu...

Страница 11: ...hreshold value 4 Absolute value Input Output 9 008 C R W T U 123 CO2 threshold value 4 1 0 Input 1 002 C W 124 CO2 threshold value 4 Switching delay from 0 to 1 Input 7 005 C W 125 CO2 threshold value...

Страница 12: ...le Input 5 Input 5 010 C W 147 Comparator 2 actuating variable Out put Output 1 001 C R T 148 Comparator 2 actuating variable Block Input 1 002 C W 149 AND logic 1 1 bit switching output Output 1 002...

Страница 13: ...ut Output 1 002 C R T 182 OR logic 1 8 bit output A Output 5 010 C R T 183 OR logic 1 8 bit output B Output 5 010 C R T 184 OR logic 1 Block Input 1 002 C W 185 OR logic 2 1 bit switching output Outpu...

Страница 14: ...5 010 C R T 207 OR logic 7 8 bit output B Output 5 010 C R T 208 OR logic 7 Block Input 1 002 C W 209 OR logic 8 1 bit switching output Output 1 002 C R T 210 OR logic 8 8 bit output A Output 5 010 C...

Страница 15: ...be saved and sent to the bus Use the Reset CO2 max value object to reset the value to the current reading Note The values are not retained after a reset Send delay after power up and programming for...

Страница 16: ...hold value must be defined which will be valid un til the 1st communication of a new threshold value For units which have already been taken into service the last communicated threshold value can be u...

Страница 17: ...LV above 1 LV hysteresis below 0 LV above 0 LV hysteresis below 1 LV below 1 LV hysteresis above 0 LV below 0 LV hysteresis above 1 Delays can be set via objects in seconds No Yes Switching delay fro...

Страница 18: ...is setting The status object shows the current status of the output variable 0 OFF 0 ON and can for example be used for visualisation Switching output sends on change Do not send message Send switchin...

Страница 19: ...e limit A set target value will be retained until a new value or a change is transferred The cur rent value is saved in EEPROM so that this is retained in the event of a power supply failure and will...

Страница 20: ...longer until the necessary variable for the target value deviation is reached You should set the time appropriate to the ventilation system at this point follow the manufacturer s instructions Now det...

Страница 21: ...ri odically Send cycle is only sent if periodically is selected 5 s 10 s 30 s 5 min 2 h From change of is only sent if on change is selected 1 2 5 10 20 25 Analysis of the blocking object at value 1 b...

Страница 22: ...ue 0 1 Logic output sends two 8 bit objects Type of objects Value 0 255 Percent 0 100 Angle 0 360 Scenario load 0 127 if logic 1 object A value Setting dependent on type of object if logic 0 object A...

Страница 23: ...do not send message send value for logic 0 send value for logic 1 Value of the parameter Send behaviour Settings options Behaviour of the switching output on release on change of logic do not send me...

Страница 24: ...tput CO2 3 Switching output CO2 3 inverted Switching output CO2 4 Switching output CO2 4 inverted CO2 controller status ventilation 1 CO2 controller status ventilation 1 inverted CO2 controller status...

Страница 25: ...24 Parameter setting Sensor KNX AQS UP basic from software 3 1 Status 24 03 2016 Technical changes reserved Errors reserved AND logic output 8 inverted...

Страница 26: ...GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0...

Отзывы: