background image

 

 

TEMON 4-C 

Doc. N°

 MO-0368-ING 

 

Microener. - Copyright 2010  

 

 

2.1 

Date 

01.12.2008

 

Rev. 

 

Pag. 

12

 

of 

14

 

 

 

10. Modality Of Tripping And Restore 

 

10.1 - 

Alarm 

 

At  the  overcoming  of  1°C  of  the  value  of  threshold  set on  the  input,  after  5  seconds,  on  the  channel  where  the 
threshold value has been exceeded, the  ALARM relay  is energized and the  ALARM  led  is on. The restore from 
the alarm condition with relay de-energized and the relative led off, happen when the temperature go down of 2°C 
respect at the threshold value set. 

 

 

10.2 - Trip 

 

At  the  overcoming  of  1°C  of  the  value  of  threshold  set on  the  input,  after  5  seconds,  on  the  channel  where  the 
threshold  value  has  been  exceeded,  the  TRIP  relay  is  energized  and  the  TRIP  led  is  on.  The  restore  from  the 
alarm  condition  with  relay  de-energized  and  the  relative  led  off,  happen  when  the  temperature  descend  of  2°C 
respect at the threshold value set. 

 

 

10.3 - To silence alarm 

 

If  the  Hold  function  is  disabled  it’s  possible  to  silence  the  alarm  condition  that  there  is  on  the  measure  input. 
When there is an alarm condition the ALARM relay and the “ALARM” optical signalling are enabled. Pressing the 
Reset  button  the  relay  is  de-energized  while  the  optical  signalling  of  the  alarm  condition  become  flash.  If  the 
temperature  increase  up  to  reach  the  TRIP  temperature  minus  1°C,  the  relay  and  the  optical  signalling  are 
enabled  another  time.  If  after  the  reset,  the  temperature  go  down  under  the  threshold  value  set,  the  flashing 
optical signalling will be automatically deleted. 

 

 
11. Diagnostic 

 

The device is provided of the thermic probes diagnostic function. 
The condition controlled on the measure input are: 
Probe Pt100 interrupted: signalling on the display of the message O P E (open). 
Probe in short circuit: signalling on the display of the message S H r (short circuit). 
Probe out of order for temperature reading wrong: signalling on the display of the message FDC. 
When the device switch on the auto-diagnostic FAULT relay commute and it remain in the status of energized until 
one of the conditions above described appears, for a failure of the device or if the power supply is absent. 
The anomaly condition is signalled also by the FAULT led on. 
Every time that a probe of a channel is out of order because it

’s interrupted (OPE) or in short circuit (SHR) or the 

delta of temperature is too much elevated (FDC), the led of the corresponding channel flash until stopping  of the 
anomaly. The alarm of interrupted probe (SHR) or open probe (OPE) will be reset automatically while the alarm for 
the delta of temperature (FDC) disappears only pressing the ENTER key, and to keep it pressed, to press the 

+

 

key at least 5 seconds. 
The status of the contact of the relay (all available with exchange contact) is showed in the following table: 
 

RELAY 

DISABLE STATUS 

ENABLE STATUS 

UNPOWERED STATUS 

ALARM 

ALARM OFF: CLOSED 29-30 

ALARM ON:   CLOSED 29-31 

CLOSED 29-30 

TRIP 

TRIP OFF:     CLOSED 32-33 

TRIP ON:       CLOSED 32-34 

CLOSED 32-33 

FAN 

FAN OFF:      CLOSED 35-36 

FAN ON:        CLOSED 35-37 

CLOSED 35-36 

FAULT 

FAULT OFF:  CLOSED 38-40 

FAULT ON:    CLOSED 38-39 

CLOSED 38-39 

 

Содержание MICROENER TEMON 4-C

Страница 1: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 FW 2 1 Date 01 12 2008 Rev 0 TEMPERATURE MONITOR DEVICE TYPE TEMON 4 C OPERATION MANUAL...

Страница 2: ...entification for the communication of the serial port MODBUS RTU protocol ____________________ 9 9 9 Selection of baud rate ____________________________________________________________________________...

Страница 3: ...are available two levels of alarm alarm tripped that active the commutation of the relative output relay for signalling at distance or to disable the machine under control On front of the instrument...

Страница 4: ...noises it s necessary to use the following indication for the wires of measure of the Pt100 to use probes with shielded wire connected at earth and wires twisted to separate the wires of the probes fr...

Страница 5: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 2 1 Date 01 12 2008 Rev 0 Pag 5 of 14 7 Wiring Connection...

Страница 6: ...annels 5 LED FAULT of indication failure device or thermometric probes 6 LED HOLD of indication function of manual reset activated 7 LED FAN of indication activation output of ventilation 8 push butto...

Страница 7: ...in the menu programming SET in this phase of programming the HOLD led switch on The Hold function allows to store the alarm condition that can be rearmed only manually with the RESET button when the...

Страница 8: ...it s necessary to select the modality of functioning ventilation 9 5 Selection threshold of disable ventilation The FAN led on with fixed light indicates this phase of programming With and keys to se...

Страница 9: ...ion of address network identification for the communication of the serial port MODBUS RTU protocol NOTE This set haven t mean for the models without the serial output RS485 option installed This phase...

Страница 10: ...the highest temperature With and keys to select the set choice Confirm with ENTER 9 12 Configuration of output signal NOTE This set haven t mean for the models without the analogical output option in...

Страница 11: ...n temperature FDC min 5 C max 30 C and after the time in which to do the control FDC min 10 max 90 period in seconds The key is used to increase the values while the key to decrease Confirm with ENTER...

Страница 12: ...old value set the flashing optical signalling will be automatically deleted 11 Diagnostic The device is provided of the thermic probes diagnostic function The condition controlled on the measure input...

Страница 13: ...inputs 1 and 2 On the right display on the front panel will appear the temperature of the measure channel hotter between the inputs 3 and 4 To come back in the standard modality of measure visualizat...

Страница 14: ...m depth 120mm Enclosure thermoplastic self extinguishing as UL94 V0 working temperature 10 55 C humidity max 90 storing temperature 25 80 C standards electromagnetic compatibility CEI EN 50081 2 CEI E...

Отзывы: