3
Troubleshooting
(continued)
47
Table 3-4
(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Delta T High /
Delta T Limit
The temperature rise across the heat
exchanger has exceeded the set parameters
for the boiler.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the
Knight Fire Tube Boiler Installation and Operation
Manual for the proper piping methods for the Fire Tube
boiler.
• Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check the wiring
back to the main control board. Replace the main
control board if necessary.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
• Verify that the boiler pump is set to the proper speed
or that the pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight Fire Tube
Boiler Installation and Operation Manual for boiler
pump specifications.
Outlet Temp
High / Outlet
Temp Limit
Outlet water temperature has exceeded the
maximum outlet water temperature.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the
Knight Fire Tube Boiler Installation and Operation
Manual for the proper piping methods for the Fire Tube
boiler.
• Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check wiring back
to the main control board. Replace the main control
board if necessary.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
• Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight Fire Tube
Boiler Installation and Operation Manual for boiler
pump specifications.
• Replace the main control board.