3
Troubleshooting
(continued)
45
Table 3-4
(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Outlet MRHL
(cont’d)
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
The outlet water temperature has exceeded
the setting of the manual reset high limit.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
• If the system pump is a variable speed pump, ensure
that the system flow is not less than the boiler flow.
• If operating on something other than an outlet sensor,
check temperature setting of the main control board.
• Check resistance of water sensors and compare to
Table 3-2A of this manual. Replace sensor if
necessary.
• Replace the main control board if necessary.
Fan Speed
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
The actual fan RPM is 30% lower or higher
than the fan speed target.
• Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 3 - General Venting of the
Knight Fire Tube Boiler Installation and Operation
Manual for proper lengths.
• Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
• Check the wiring connections at the fan and at the
main control board.
• Check the fan using the fan test tool.
• Replace the fan.
• Replace the main control board.
Blown fuse.
• Replace fuse F2 on the control board.
Inlet, Outlet, or
Flue Sensor Fault
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
Either the flue, inlet water, or outlet water
temperature sensor has been disconnected
or shorted.
• Check the sensors and their associated wiring.
Repair or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare
the resistance to the tables in the Checking
Temperature Sensors Section of this manual.
• Replace the sensor if necessary.
Service Manual
Содержание 100 Series
Страница 51: ...51 Service Manual Notes ...