     6 

Installation Guide, Rev. E

FCU—4 Pipe, Modulating

FCU 4-PIPE MODULATING LAYOUT

CSE-1102

Air Differential Pressure Switch

VEB-43 Valves with 

MEP-4002V Actuators

SET SWITCHES FOR...

OPERATION: CCW

FAIL-SAFE: CW

INPUT RANGE: 2–10 VDC

SET SWITCHES FOR...

OPERATION: CW

INPUT RANGE: 0–10 VDC

SET SWITCHES FOR...

OPERATION: CCW

INPUT RANGE: 0–10 VDC

XEE-6311-050 Transformer

REE-3112 Control Relay

XEE-6311-050 Transformer

REE-3211 or CVR11C-0/LD96200 Multi-Voltage Relays

VEB-43 Fail-Safe Valve with MEP-4x52V Actuator

Output 

Terminals

FCU Output 

Connections

BACnet 

Objects

    

Analog 9

AO9

  GND

Ground (for 

analog output 

terminals 7–9)

    Analog 8

Heat Valve 

(HTV)

AO8 

    Analog 7

Cool Valve 

(CLV)

AO7

    Analog  6

Optional 

Humidification 

Valve (HUM or 

HUMV)

AO6

   GND

Ground (for 

analog output 

terminals 4–6)

    

Analog  5

AO5

    

Analog  4

 

AO4

    Relay 3

Fan 3

BO3

  SC 1–3

24 VAC (for 

relay terminals 

1–3)

 

    Relay 2

Fan 2

BO2

    Relay 1

Fan 1

BO1

 APPLICATION
DEGREES SCALE: °F

APP:

OPT: 4–PIPE
ADDITIONAL SETUP

FAN COIL

 

ADDITIONAL SETUP

FAN

HUMIDITY
OPTIMUM START
SENSORS
VALVE

Input Terminals

FCU Input Connections

BACnet Objects

       IN9

Opt. Remote CO

2

 Sensor*

AI9

       IN8

AI8

       IN7

Opt. Remote Temp. Sensor*

AI7

       IN4

AI4

       IN3

AI3

     GND

Ground

       IN2

Optional Fan Status (FST)*

AI2

  *Fan Status (FST) and (not shown on the diagram) remote temp./CO

2

 

   sensors are optional inputs. Set pull-up resistor switch positions 

   appropriately (see the Input Connections section).

NOTE:  Do not use REE-3211/

CVR11C-0/LD96200 

relays

 with 

analog

 outputs! See Output 

Connections on page 3.

NOTE:  In firmware earlier than R2.1.0.18, an option 

for a DAT on IN2 was available for a built-

in trend log. For later firmware, use KMC 

Connect or TotalControl to create a custom 

trend if this is desired.

Содержание FlexStat BAC-12xx36 Series

Страница 1: ...from heat sources sunlight windows air vents and air circulation obstructions e g curtains furniture Additionally for a model with an occupancy sensor option install it where it will have unobstructed view of the most typical traffic area See the FlexStat Application Guide for more information If replacing an existing thermostat label wires as needed for reference when removing the existing thermo...

Страница 2: ...e 82760 or equivalent together at each device Use a wire nut or the S terminal in KMC BACnet controllers FlexStats however do not have an S terminal Connect the cable shield to a good earth ground at one end only NOTE The S terminal in KMC controllers is provided as a connecting point for the shield The terminal is not connected to the ground of the controller When connecting to controllers from o...

Страница 3: ...ched relay Common connec tion in place of the GND terminal used with analog outputs See Illustration 6 For the relay circuit the phase side of the AC should be connected to the SC terminal Illustration 6 Switched Relay Common and Relays CAUTION Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relay s switched common See the backplate s terminal label for the co...

Страница 4: ... 24 VAC only Do not connect line voltage to the relays Do not mistakenly connect 24 VAC to an analog output ground NOTE Since the KMC REE 3211 is discontin ued use Core Components CVR11C 0 LD96200 in its place Do not use either with analog outputs See Output Connec tions on page 3 NOTE For Bill of Materials listings of the various accessories shown in the sample diagrams see the FlexStat Applicati...

Страница 5: ...Fan 1 BO1 APPLICATION DEGREES SCALE F APP OPT 2 PIPE ADDITIONAL SETUP FAN COIL ADDITIONAL SETUP FAN OPTIMUM START SENSORS VALVE NOTE Do not use REE 3211 CVR11C 0 LD96200 relays with analog outputs See Output Connections on page 3 NOTE In firmware earlier than R2 1 0 18 an option for a DAT on IN2 was available for a built in trend log For later firmware use KMC Connect or TotalControl to create a c...

Страница 6: ...UMV AO6 GND Ground for analog output terminals 4 6 Analog 5 AO5 Analog 4 AO4 Relay 3 Fan 3 BO3 SC 1 3 24 VAC for relay terminals 1 3 Relay 2 Fan 2 BO2 Relay 1 Fan 1 BO1 APPLICATION DEGREES SCALE F APP OPT 4 PIPE ADDITIONAL SETUP FAN COIL ADDITIONAL SETUP FAN HUMIDITY OPTIMUM START SENSORS VALVE Input Terminals FCU Input Connections BACnet Objects IN9 Opt Remote CO2 Sensor AI9 IN8 AI8 IN7 Opt Remot...

Страница 7: ...als 4 6 Analog 5 AO5 Analog 4 Optional Fan Speed AO4 Relay 3 Heat 1 W1 BO3 SC 1 3 24 VAC for relay terminals 1 3 Relay 2 Cool 1 Y1 BO2 Relay 1 Fan 1 G BO1 If optional Outside Air Damper is used must also have DAT OAT inputs AHU Air Handler Unit 1 Heat and 1 Cool APPLICATION DEGREES SCALE F APP OPT 1H 1C ADDITIONAL SETUP AIR HANDLER ADDITIONAL SETUP DAMPER FAN HUMIDITY OPTIMUM START SENSORS Input T...

Страница 8: ...ing Valve CLV AO7 Analog 6 Optional Humidifier Valve HUM or HUMV AO6 GND Ground for analog output terminals 4 6 Analog 5 AO5 Analog 4 Optional Fan Speed AO4 Relay 3 Optional Heat 2 W2 BO3 SC 1 3 24 VAC for relay terminals 1 3 Relay 2 Heat 1 W1 BO2 Relay 1 Fan 1 G BO1 If optional Outside Air Damper is used must also have DAT OAT inputs APPLICATION DEGREES SCALE F APP OPT 2H MOD C ADDITIONAL SETUP A...

Страница 9: ...V AO8 Analog 7 AO7 Analog 6 Optional Humidifier Valve HUM or HUMV AO6 GND Ground for analog output terminals 4 6 Analog 5 AO5 Analog 4 Optional Fan Speed AO4 Relay 3 Optional Cool 2 Y2 BO3 SC 1 3 24 VAC for relay terminals 1 3 Relay 2 Cool 1 Y1 BO2 Relay 1 Fan G BO1 If optional Outside Air Damper is used must also have DAT OAT inputs APPLICATION DEGREES SCALE F APP OPT MOD H 2 C ADDITIONAL SETUP A...

Страница 10: ... terminals 7 9 Analog 8 Heating Valve HTV AO8 Analog 7 Cooling Valve CLV AO7 Analog 6 Optional Humidifier Valve HUM or HUMV AO6 GND Ground for analog output terminals 4 6 Analog 5 AO5 Analog 4 Optional Fan Speed AO4 Relay 3 BO3 SC 1 3 24 VAC for relay terminals 1 3 Relay 2 BO2 Relay 1 Fan BO1 If optional Outside Air Damper is used must also have DAT OAT inputs APPLICATION DEGREES SCALE F APP OPT M...

Страница 11: ...e harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation A BAC 12xxxx Class B digital apparatus complies with Canadian ICES 003 A BAC 13xxxx 14xxxx Class A digital apparatus com plies with Canadian ICES 003 Class A CAUTION This document is for 3 relay 6 analog output 6 external input BAC 12xx36 13xx36 14xx36 series onl...

Отзывы: