background image

BAC-120063CW-ZEC FlexStat 

     7 

Installation and Configuration Guide, Rev. G

Illustration 7—MS/TP Network End-Of-Line Termination

Illustration 8—EOL/Pull-Up Switch Positions

10K 

0-12 V

Input Pull-Up Switches

ON

OFF

Switch 

Pushed 

Right 

IN2

IN3

IN4

IN7

IN8

IN9

NOTE:  10K 

 inputs

  are configurable for
  Type II or Type III
  thermistors in
  FlexStat’s menu.

NOTE:  EOL = End
  Of Line of BACnet
  MS/TP network.

EOL Switches

Switch 

Pushed 

Left 

Network EOL (End-Of-Line) Termination

The controllers/thermostats on the physical ends of 

an EIA-485 wiring segment must have end-of-line 

termination installed for proper network operation. 

(See Illustrations 7 and 8.) If a FlexStat is at the physi-

cal 

end

 of the MS/TP network line, set 

both

 the EOL 

termination switches to 

On

 (to the 

right

) on the back 

of the circuit board. If not on the end, ensure that 

both switches are Off (to the left).

 WED 7/30 

 

       5:33 PM

 

 

      

COOL:

 

 

      OCC:

 

 

      FAN:

                                   

COOL CALLS 5

Configuration and Operation

Illustration 9—FlexStat Display and Button Functions

Right 

(Menu)

Left

(Override)

Down

Up

NOTE:  For additional information, see the relevant 

parts of the Configuration section in the 

FlexStat Operation Guide

 (but not all 

things apply to this model).

NOTE:

  Settings and adjustments may require a 

password.

DAT

Zone Information (# of 

Zones, # of Zones Calling 

for Cooling, and # of Zones 

Calling for Heating)

Configure the Application and Address

To access the menus, press the right button. 

Navigate 

the menus and change settings by pressing a combi

-

nation of buttons.

 Press the:

• 

Enter

 button to select and/or exit value editing.

• 

Up/Down

 button to move among 

entries

 (up/

down lines).

• 

Left/Right

 button to move among 

value fields 

(left/right spaces).

• 

Left

 button to return to the Home screen.

Configure the 

application

 through the menu system. 

From the Main Menu, select 

ADVANCED

 (enter 

password if needed) and then 

APPLICATION

 APPLICATION
DEGREES SCALE: °F

APP:

OPT: 2H/2C
ADDITIONAL SETUP
ZONE DEV INS RANGE

ROOF TOP

 

ADDITIONAL SETUP

DAMPER

FAN
SENSORS
ZONE HYSTERESIS: 2
VALVE HT OR CL: HEAT
DEVICE TYPE: 0-10V
STAGING

Содержание FlexStat BAC-120063CW-ZEC

Страница 1: ...mounting screws supplied by KMC Controls Using other screws may damage the FlexStat Do not turn screws in farther than necessary to remove the cover 2 If the cover is locked on the backplate turn the hex screws in the bottom and top of the FlexStat CLOCKWISE until they just clear the cover See Illustration 1 Pull the cover away from the backplate mounting base 3 Route the wiring through the backpl...

Страница 2: ...or Ethernet Cable Up to 75 Feet Long MS TP Network STE 8x01 Room Temp Sensor and Configuration Tool Supply Air to Room Supply Air from RTU Zone 1 MAC 3 Device Instance 1000001 RTU Controller MAC 20 Device Instance 1000000 Zone 16 MAC 19 Device Instance 1000016 Illustration 2 Sample Networked RTU Installation CSP 4702 To HI Port DAT Displayed Roof Top Unit RTU Supply Air Return Air STE 140x Temp Se...

Страница 3: ...tional AI9 IN8 Unused in this application AI8 IN7 Unused in this application AI7 IN4 Unused in this application AI4 IN3 Unused in this application AI3 GND Ground IN2 DAT AI2 NOTE The DAT sensor is configured for IN2 in the ADVANCED APPLICATION ADDITIONAL SETUP SENSORS menu NOTE Although typical terminal code letters are shown check the schematics of your unit for wiring details CAUTION Relays are ...

Страница 4: ...UP ZONE HEAT PUMP 1 or 2 Compressors with Auxiliary and Emergency Heat NOTE Although typical terminal code letters are shown check the schematics of your unit for wiring details CAUTION Relays are for Class 2 voltages 24 VAC only Do not connect line voltage to the relays Do not mistakenly connect 24 VAC to an analog output ground Illustration 4 HPU Application Connections Input Terminals HPU Input...

Страница 5: ... A IN4 IN3 GND IN2 Common C Phase R Analog 9 GND 7 9 Analog 8 Analog 7 Relay 6 SC 4 6 Relay 5 Relay 4 Relay 3 SC 1 3 Relay 2 Relay 1 Outputs Wiring Cutout in Backplate MS TP Network Inputs 24 VAC Wiring is dependent on application Inputs NOTE IN1 and IN5 6 are reserved for internal sensors NOTE SC Switched relay Common Output Connections Connect the device under control between the desired output ...

Страница 6: ...od practices when connecting an MS TP network see Planning BACnet Networks Application Note AN0404A For the bank of three relays there is one Switched relay Common connection in place of the GND ter minal used with analog outputs See Illustration 6 For the relay circuit the phase side of the AC should be connected to the SC terminal FlexStat relays are NO SPST Form A Do not attach a device that dr...

Страница 7: ...figuration and Operation Illustration 9 FlexStat Display and Button Functions Right Menu Left Override Down Up NOTE For additional information see the relevant parts of the Configuration section in the FlexStat Operation Guide but not all things apply to this model NOTE Settings and adjustments may require a password DAT Zone Information of Zones of Zones Calling for Cooling and of Zones Calling f...

Страница 8: ...tem is stand alone address the FlexStat for MAC 20 Device Instance 1000000 See Illustration 2 To set the FlexStat s BACnet Device Instance and optionally name and location 1 Select ADVANCED enter password if needed and then DEVICE 2 Change or confirm INSTANCE to 1000000 DEVICE INSTANCE NAME ZEC_FlexStat_1 LOCATION KMC Controls 1000000 To configure the MAC address from the Main Menu select ADVANCED...

Страница 9: ...Number of calls for heating AV25 at 1 minute intervals from SimplyVAVs 7 Duct static pressure AV103 at 1 minute intervals from an optional CSP 4702 8 Duct static pressure setpoint AV104 at 1 minute SETPOINTS COOL DAT SETPOINT HEAT DAT SETPOINT 130 F DUCT ST STPT 0 5 in H2O 55 F The optional duct static pressure setpoint is also in this menu NOTE The airflow minimum limit in each SimplyVAV controll...

Страница 10: ...ns for each zone s values are Call for Cooling Call for Heating No Call for Either Sequence of Operation NOTE The HPU and RTU sections of the FlexStat Application Guide have some basic generic information about HPU and RTU operation The BAC 120063CW ZEC FlexStat determines RTU HPU heating or cooling mode by majority rule of the number of heating and cooling calls from the SimplyVAV controllers If ...

Страница 11: ...hangeover on page 10 See also Sequence of Operation on page 10 See the relevant parts of the Troubleshooting section in the FlexStat Operation Guide Maintenance Remove dust as necessary from the holes in the top and bottom Clean the display with a soft damp cloth and mild soap Customization Additional customization can be done using KMC Connect KMC Converge or TotalControl For ex ample a fan statu...

Страница 12: ...rmation about this model FlexStat on the BAC 120063CW ZEC web page For general operation configuration troubleshoot ing and other information see the generic FlexStat Operation Guide and FlexStat Application Guide See also the BAC 8000 series for information about the VAV controller actuators See also the CSP 4702 page for information about the differential pressure controller actuator For remotel...

Отзывы: