FlexStat Malfunctions After Upgrade
• Check application configuration.
NOTE: Restoring to the factory defaults and
reconfiguring might be needed if how the
FlexStat operates changes.
Read all notes
accompanying the firmware update!
NOTE: If
custom
Control Basic programs are
installed
and set to autorun
, whenever the
firmware is updated
,
ALL (factory and
custom) programs are halted.
If
custom
Control Basic programs are installed
but NOT set to autorun, whenever the
firmware is updated, factory programs
are restarted but any (manual) running
custom programs are halted at restart.
• Change the state of each custom program by
using the Update Manager or loading/running
each program from the CB Programs menu (or
BACstage or TotalControl).
NOTE: See also
Control Basic Programs Do Not
Work on page 30
.)
NOTE:
Customized programs are the responsibility
of the user.
KMC Controls does not provide
support for such programs.
UPDATE MANAGER
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
NO
• Ensure firmware for the correct model is se-
lected
in the Firmware Upgrade Tool. If firmware
for the wrong model is accidentally installed, the
outputs will not match the applications/configu-
ration on the display.
NOTE:
Backing up
the existing settings and
firmware image
before or during the
upgrade process
(using the Firmware
Upgrade Tool, TotalControl, or BACstage)
is recommended practice.
NOTE: See also the HTO-1103/KMD-5699
Installation Guide, for more information.
(The KMD-5699 product number was
changed to HTO-1103 in August 2010.)