FlexStat
23
Operation Guide, Rev. L
System Setup
SYSTEM
SYSTEM ENABLE:
OCC OVRIDE (HRS): 1.0
INACTIVITY (SECS): 60
DISPLAY BLANKING: NO
AUTO
To adjust the system configuration values, such as
system enable (auto, off, heat, or cool), occupancy
override time, and display inactivity time-out:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Up
/
Down
to increment/decrement value.
Occupancy Override on this menu
is the amount of
time (in hours) a manual change in the setpoint (via
the Up and Down buttons) will be allowed to over-
ride the scheduled setpoint.
When the time is set to
0, the override state will last until the next schedule
change.
NOTE: Occupancy override can also be removed
while on the Home screen by pushing the
left button, navigating to OCC, hitting Enter
twice, and changing ON to OFF. See
H/C,
Fan, Occupancy, and Override on page 4
.
When Display Blanking is enabled (Y),
the display
turns off at the same time the backlight goes off
(after reset, initial power-up, or time-out). When any
button is pressed, the display will reappear until the
time-out is reached again.
The menu/display/backlight time-out
(seconds
since the last button is pushed) is set in
Inactivity
.
Access to the Main Menu, setpoint adjust, and
System/Occupancy/Fan override have a default
password level of User. This level can be changed for
each function to None, Operator, or Administrator
through this screen. Passwords are set in the (Ad-
vanced) Passwords menu. See
(Advanced) Security
Levels and Passwords on page 17
.
Setpoints
SETPOINTS
COOL SETPT:
HEAT SETPT: 70° F
COOL SETBACK: 80° F
HEAT SETBACK: 64° F
CO2 SETPOINT (PPM): 600
74° F
In the Setpoints menu, setpoints and setbacks for
various values are set (The current room temperature
setpoint can also be manually changed from the
Home menu.)
To adjust the setpoints, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Up
/
Down
to increment/decrement value.
NOTE: In firmware version R2.0.0.6, Minimum
Setpoint Differential, was moved to
the Limits menu. See
(Advanced)
Temp. Setpoint Limits on page 16
. Also,
“Deadband” was separated into Heating
and Cooling Proportional Bands and
moved to the Loops menu. See
(Advanced)
PID Loop Configuration on page 17
.