FURTHER SPECIFICATIONS TO BE CONSIDERED 
 

The central heating cooker works with the combustion chamber in depression; 

it is essential that the 

exhaust pipe is hermetically sealed. 

We recommend using rigid stainless steel pipes, with sealing gaskets having a minimum diameter of 
120 mm. 

The pipes must be double-walled or adequately insulated with rock wool. The maximum 
temperature of the pipe must not exceed 70 °C. 

 

TO ENSURE PROPER FUME DISCHARGE PROVIDE FOR AN INITIAL VERTICAL TRACT OF AT 
LEAST 1.5 METRES. 
 

Each change of direction must be carried out with a T-shaped fitting and inspection cap. 
Pipes must ensure sealing against smoke leakage via gaskets resistant to 250 °C. 
Fix the pipes to the wall with suitable relevant metal collars to avoid any vibration. 
 

WARNING: IT IS FORBIDDEN TO INSTALL DRAUGHT REGULATING VALVES

 (BUTTERFLY 

VALVES). 
 
There are two solutions for the connection to the flue: 
 

SOLUTION 1 

– REAR FLUE GAS OUTLET 

 

 

 

Содержание SMART 120

Страница 1: ...Pellet fired central heating cooker SMART 120 INSTALLATION USE AND MAINTENANCE USEFUL TIPS User guide EN...

Страница 2: ...2...

Страница 3: ...chimney of a building from a furnace or from any fixed boiler if located in a designated smoke control area It is also an offence to acquire an unauthorised fuel for use within a smoke control area un...

Страница 4: ...r NQA B 0002 29 NQA B 0002 30 NQA B 0002 31 NQA B 0002 32 Copyright All rights reserved The reproduction of any part of this manual in any form without the explicit written permission of KLOVER Srl is...

Страница 5: ...t water Costruttore Manufacturer KLOVER s r l Via A Volta 8 37047 San Bonifacio VR Ente Laboratory NB 1880 ACTECO S R L I 33084 Cordenons PN Via Amman 41 Le norme armonizzate o le specifiche tecniche...

Страница 6: ...21 Control of a three way motorised valve for the DHW system 21 Connection to room thermostat 22 Pipe connection 23 Connection examples 24 Cleaning and Maintenance 25 Precautions before cleaning 25 Ro...

Страница 7: ...iance and its elements Do not leave flammable containers and substances in the room where the central heating cooker is installed Do not use the appliance as incinerator or in any other way different...

Страница 8: ...EXTERNAL AIR VENT AND THE CORRECTNESS OF THE SOLUTIONS SUGGESTED FOR INSTALLATION ALL THE SAFETY STANDARDS CONTAINED IN THE SPECIFIC LAW IN FORCE OF THE STATE WHERE THE THERMO STOVE IS INSTALLED MUST...

Страница 9: ...NING TECHNICAL COMPARTMENT 2 BRUSHES FOR FLUE GAS TURN CLEANING 65 mm and 40 mm diameter This manual is an integral part of the machine Should the central heating cooker be sold the manual must be pro...

Страница 10: ...10 MAIN ON OFF SWITCH SAFETY THERMOSTAT MANUAL RESET SYSTEM PUMP FLUE PRESSURE SWITCH FLUE GAS INTAKE DEVICE TECHNICAL COMPARTMENT...

Страница 11: ...already connected power supply cable to anti disturbance filter AIR VENT MANUAL VALVE ANTI DISTURBANCE FILTER WITH 2 INCORPORATED FUSES 4A 250V AND ATTACHMENT FOR POWER SUPPLY CABLE SAFETY VALVE CALIB...

Страница 12: ...ONNECTION CLAMP AIR INTAKE PIPE FLUE EXHAUST RETURN ATTACHM ENT DOMESTIC COLD WATER INLET ONLY ON MOD WITH SET UP SYSTEM LOAD AND BOILER BODY DOMESTIC HOT WATER OUTLET ONLY ON SET UP MOD FLOW CONNECTI...

Страница 13: ...F GAS SYSTEM FLOW R M GAS SYSTEM RETURN C 14 mm DOMESTIC HOT WATER OUTLET on prepared models only F 14 mm DOMESTIC COLD WATER INLET S 100 mm M FLUE OUTLET A 50 mm AIR SUCTION DEVICE 955 250 70 350 295...

Страница 14: ...F GAS SYSTEM FLOW R M GAS SYSTEM RETURN C 14 mm DOMESTIC HOT WATER OUTLET on prepared models only F 14 mm DOMESTIC COLD WATER INLET S 100 mm M FLUE OUTLET A 50 mm AIR SUCTION DEVICE 350 295 235 170 6...

Страница 15: ...ure recommended bar 2 5 1 5 Minimum chimney draught at nominal input reduced Pa 12 6 10 Combustion gas flow at nominal input reduced g s 16 2 9 4 Exhaust flue gas temperature at nominal input reduced...

Страница 16: ...iance with international standards such as EN 14961 2 Wood pellet class A1 A2 maximum moisture level of 10 should be indicated on the packaging Packages are intact as pellet tends to absorb humidity H...

Страница 17: ...materials must be at least 200 mm from the sides and back of the central heating cooker Spaces around and above the central heating cooker The figure below shows the minimum measures to be met when po...

Страница 18: ...rages fuel stores or businesses involving a fire hazard Do not connect the external air vent to the central heating cooker through piping If there are other heating or suction appliances in the room a...

Страница 19: ...e cement pipes to connect the appliances to the flue Exhaust channels must not pass through rooms in which the installation of combustion appliances is forbidden When mounting exhaust channels make su...

Страница 20: ...imum temperature of the pipe must not exceed 70 C TO ENSURE PROPER FUME DISCHARGE PROVIDE FOR AN INITIAL VERTICAL TRACT OF AT LEAST 1 5 METRES Each change of direction must be carried out with a T sha...

Страница 21: ...4 cm duct the flue using a stainless steel pipe properly insulated with rock wool or vermiculite and sized according to the route The connection to the flue must be properly sealed When mounting the f...

Страница 22: ...iler stops This is to make sure that you do not have to add up the heat output in the two appliances installed in the system This is why our set up intervenes on the coupled boiler when the pellet cen...

Страница 23: ...emperature set on SET H2O and displaying T H2O ECONOMY on the screen 4 The central heating cooker will now automatically switch off if there is at least one of the following conditions If it remains i...

Страница 24: ...el equipped with a device for stopping fuel loading a safety manual reset thermostat and an audible alarm activated if temperatures are too high The central heating cooker can be installed in the same...

Страница 25: ...EXAMPLE WITH DOMESTIC HOT WATER STORAGE COUPLING These diagrams are for guidance only and do not imply any commitment or liability by KLOVER s r l and its partners The final design and subsequent impl...

Страница 26: ...e gloves goggles and dust masks as directed in eu 89 391 EEC Cleaning frequency depends on the type and quality of pellets burnt Therefore the schedule reported below may vary Any central heating coo...

Страница 27: ...that is deposited under the brazier Empty the ash drawer WARNING Use suitable bin vacuum cleaners with a fine mesh filter to prevent part of the ash from being discharged into the environment and dama...

Страница 28: ...28 Extraordinary cleaning 2 To be performed at least every 30 days Carry out routine cleaning 2 1 1 2 1 2...

Страница 29: ...29 Dismantle the outlet on the cooking plate and suck the ash deposit above the oven Properly re position the outlet after cleaning ensuring it is flue gas sealed 2 1 3 2 2 1...

Страница 30: ...30 Dismantle the outlet underneath the oven and suck the ash deposit below it and on its side Properly re position the outlet after cleaning ensuring it is flue gas sealed 2 2 2 2 2 3...

Страница 31: ...31 2 3 1 2 3 2...

Страница 32: ...he combustion chamber and clean the internal flue gas turn with the brush provided with the equipment Suck the ash deposit in the part below Properly re position the outlet after cleaning ensuring the...

Страница 33: ...33 After removing the ash drawer extract the underlying base and using a suitable suction device suck the deposit inside Then re position the base and ash drawer 1 2 2 4 1 2 4 2...

Страница 34: ...34 Suck the sawdust deposit from the tank base The pellet tank must be emptied at the end of every season 2 5 1...

Страница 35: ...35 Yearly cleaning To be performed at least once a year Carry out routine cleaning Carry out extraordinary cleaning Remove the left side as in the above photo 1 2 3 1 1...

Страница 36: ...TEE and clean the entire flue pipe with a brush sucking any soot deposit Properly re position the cap after cleaning ensuring it is flue gas sealed The rear TEE is only available in models with upper...

Страница 37: ...37 Remove the cooking plate by loosening the ten screws all around it after dismantling the upper cleaning outlet 3 3 1 3 3 2...

Страница 38: ...38 Remove the flue deflector located between the combustion chamber and the cooking oven 3 4 1 3 4 2...

Страница 39: ...39 Scrape around the oven sides using the supplied brush and vacuum any soot deposit Re position the flue deflector and cooking plate after cleaning ensuring the latter is flue gas sealed 3 5 1 3 5 2...

Страница 40: ...ot performed the operation of the central heating cooker and its components may be impaired The frequency of the central heating cooker and flue cleaning depends on the quality of the pellets used USE...

Страница 41: ...ONO THERMOSTAT the LED lights up when at least one start up and switch off program is active START UP RESISTANCE the LED lights up when start up resistance is active SCREW CONVEYOR the LED lights up w...

Страница 42: ...is active 7 the LED is not currently used The following figure shows the display when setting or programming operating parameters Set 1 2 3 4 5 6 The INPUT area shows the entered programming values Th...

Страница 43: ...ker working output In menu It moves to the next menu item Programming It switches to the next submenu item by storing the changes 6 It increases output 4 Working off It increases the DHW thermostat te...

Страница 44: ...he times set according to the following table where OFF requires the clock to ignore the command MENU LEVEL SELECTION MEANING POSSIBLE VALUES 02 02 02 START 1 Ignition time Time OFF 02 02 03 STOP 1 Sw...

Страница 45: ...02 03 33 WEDNESDAY PROG 4 On off 02 03 34 THURSDAY PROG 4 On off 02 03 35 FRIDAY PROG 4 On off 02 03 36 SATURDAY PROG 4 On off 02 03 37 SUNDAY PROG 4 On off Sub menu 02 04 week end program It allows...

Страница 46: ...ooker with the boiler temperature only disable the room sensor on the remote control stove settings menu Enable room sensor OFF The room sensor is automatically disabled if no external remote control...

Страница 47: ...nd signal is only available on the central heating cooker board and not on the external remote control 7 Menu 07 Initial load It allows pre loading pellets for 90 with the central heating cooker off a...

Страница 48: ...and mains connection Perform the following steps Connect the central heating cooker to the electrical system using the cable supplied Put the main ON OFF switch see fig on page 9 located inside the t...

Страница 49: ...Working output set at 5 Working output automatically changes to 4 when temperature reaches 71 C Working output automatically changes to 3 when temperature reaches 72 C Working output automatically ch...

Страница 50: ...f the flow switch If water is particularly hard it is essential to install an anti limescale device at the heat exchanger inlet to be chosen according to the water characteristics Cooking plate oven o...

Страница 51: ...pending on the type of pellet burnt and frequency of cleaning the flue gas turn The temperature may fall by about 20 30 C if food is put into the oven The temperatures were measured starting with the...

Страница 52: ...5 C or H2O Temperature SET H2O Pr43 is exceeded Room Temperature Press key 2 and select SET ROOM TEMP to change the room temperature Then press keys 1 and 2 During this operation the display appears...

Страница 53: ...NTAKE DEV ACTIVE ALARM Faulty intake device When the intake device speed measured by an in built encoder tachometer is equal to 0 Each alarm condition causes an immediate shutdown After the time set o...

Страница 54: ...orking it will go into the NO PELLET alarm sudden shutdown It is therefore necessary to reset the thermostat before restarting the central heating cooker lack of power black out If an outage occurs fo...

Страница 55: ...OFF Minutes 0 20 10 Pr40 M 9 4 03 Ignition pre load time IGNIT PRE LOAD Seconds 0 225 85 Pr41 M 9 4 04 Stand by time after pre load AFTER PRE STAND BY Seconds 0 255 210 Pr42 M 9 4 05 Intake device sp...

Страница 56: ...lue gas intake speed in output 1 working mode P 1 FLUE GAS SPEED Revs min 500 2800 1600 Pr19 M 9 6 19 Flue gas intake speed in output 2 working mode P 2 FLUE GAS SPEED Revs min 500 2800 1750 Pr20 M 9...

Страница 57: ...ONTROL OF ANT COUPLED BOILER SCAM AUX ALT P HEATING SYSTEM PUMP CONNECTOR FOR SERIAL OR EXPANSION BOARD I055 CONNECTION CR2032 3Volts CHRONO THERMOSTAT CLOCK BATTERY BROWN ON CABLE BLACK ON CABLE BLUE...

Страница 58: ...uipment and any other removable component where it cannot be proved it is a manufacturing defect and not normal wear Electrical and electronic parts whose failure can be related to a non standard elec...

Страница 59: ...59...

Страница 60: ...d PELLET WOOD FIRED THERMAL FIREPLACES CENTRAL HEATING COOKERS THERMAL STOVES BOILERS Via A Volta 8 37047 San Bonifacio VR Italy Tel 045 6101859 Fax 045 6101858 Internet www klover it e mail klover kl...

Отзывы: