58
AUTOMATION AND CONTROL SYSTEM FOR UNITS
EVO-T; EVO-T COMPACT
OPERATION AND MAINTENANCE MANUAL
2. EXECUTION STANDARD
2.1 Characteristics of the standard EVO-T and EVO-T COMPACT
control system:
• Wall-mounted Danfoss inverters installed near EVO-T
control cabinet
• Plastic EVO-T control cabinet, IP40-rated – internal version
Table no. 1
Electric Parameters of EVO-T (COMPACT)Control Cabinets
NAME
„2S”
„4S”
Rated voltage (Un)
400V, 50Hz
Insulation rated voltage (Ui)
500V
Rated surge with stand voltage (Uimp)
4kV
Assembly rated current (InA)
Chapter 13
Circuit rated current (InC)
Chapter 13
Rated short-duration with stand
current (Icw)
1,5 kA
Coordination of short-circuit protections
Chapter 13
Rated frequency (fn)
50Hz
Type of the grounding system
TN-S
Version
internal
Protection class
IP 40
EMC classification
Environment 2 [class A]
External impact protection
IK05
Contamination level
3
Operating conditions
10°C ÷ +40°C, (daily average 24h<
+35°C)
Dimensions
406x303x98 mm
406x303x98 mm
Weight
3,3 kg
3,6 kg
2.2 EVO-T (COMPACT) Control Cabinet content
• Power supply and control with the Modbus RS485 of the
AC (only in EVO-T) motor inverters or EC motor in EBM
fan motors.
• Power supply and control of the water heating coil circu-
lation pump (1x230VAC).
• The control system’s controller.
• Control of the electric heater (0÷10VDC signal and re-
turn alarm signal), the electric heater has to be equipped
with its own power supply and control system (can be
control the electrical heater through Aout1 as a PWM
amplitude 10VDC, the choice we make in the service
Menu/configuration/electric heater).
• Control of DX cooler (level 1, 2 and 0÷10V DC), the cool-
er has to be equipped with its own power supply and
control system.
• 24 VAC power supply and control of the air supply, air
exhaust, recirculation and cross-flow recovery dampers.
• 24 VAC power supply and control of the water heating
and cooling coils’ valve actuators.
3. FIRST START-UP
In order to start up the system for the first time:
a) Read this manual and application diagram for a venti-
lation system, where the control system is to be applied.
b) Carry out electrical connections in line with the applica-
tion diagram and guidelines listed in this manual.
c) Check, if the sensors and functional elements (actuators,
inverters, etc.) are connected correctly.
d) Turn on the power supply of the control cabinet and set
the application code in the service menu according to the
application diagram (point 4).
e) Set up the system in the service menu (point 9.4).
f) Deactivate the service mode.
g) Turn on the Modbus RTU controller communication
with the EC EBM fans or inverters of air supply and AC air
exhaust fans (if equipped) (point 10.5).
h) Check if the sensor readings and locations are correct.
i) Check operation of the actuators (using Service menu/
output forcing). While testing please pay attention to free
motion of dampers, full open/close state of the actuators.
j) Set the master sensor in “Settings/Temperatures/Master
sensor” menu (point 9.3).
k) Check if any alarms are triggered. If so, they must be
cleared (point 8.4).
l) Start the system (point 8.1).
m) Check again if any alarms are triggered. If so, they must
be cleared (point 8.4).
n) Choose an appropriate menu language at the controller
Regardless the controller’s factory settings please check
the adjustment of the system in terms of temperature ad-
justment, cooling the electric heater (if equipped).
Selection of temperature controller settings should be
carried out so that the system introduces the corrections
as soon as possible, without over-regulation (decrease
the Kp parameter and/or increase the Ti parameter in
order to slow down the system response).
Appropriate selection of PI controller settings, operat-
ing the AHU in accordance to performance determined
in the AHU specification sheet, appropriate selection
of AHU components (recommended analog control
of each heat/cool exchanger), system operation at a
premise with no sudden temperature changes due to
presence of other equipment generating high amount
of heat/cool, enable stable control of lead temperature
with ±0,1K accuracy.
In order to check current accuracy of temperature control
please go into “Service menu/Lead temperature history”
(where last 15 measurements of lead temperature sensor
with selected time period are stored) as well as the “Devia-
tion” is provided, which determines the max. difference of
current set temperature and last 15 measurements from
the master temperature sensor.
Содержание EVO -T
Страница 2: ...SERWIS SERVICE 48 587839950 51 48 587839888 48 510098081 serwis klimor com...
Страница 39: ...37...
Страница 41: ...39...
Страница 54: ...52 AUTAMATYKA STEROWNICE AUTOMATYKI DO CENTRAL EVO T EVO T COMPACT DOKUMENTACJA TECHNICZNO RUCHOWA NOTATKI...
Страница 55: ...53 NOTATKI...
Страница 56: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Страница 91: ...89 CONTROL AUTOMATION CONTROL...
Страница 106: ...104 AUTOMATION AND CONTROL SYSTEM FOR UNITS EVO T EVO T COMPACT OPERATION AND MAINTENANCE MANUAL NOTES...
Страница 107: ...105 NOTES...
Страница 108: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Страница 109: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Страница 115: ...113 5 7 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Страница 120: ...118 EVO T EVO T COMPACT I II Tsup 22 C III IV Troom 4 C TsetStdby 20 C Tsup V t Troom TsetStdby 8 4 Re8 C 3 OK 5 PT5...
Страница 123: ...121 A_Col dRec PT4 24 24 A_Code 3 A_In_ Emul PT1000 A_Out Force 9 9 1 No 16 8 2 8 3 PL RU 9 2 1 2 3...
Страница 143: ...141 PWM SSR P3 24 P1 P2 0 10 0 10 N P2 P1 10 1 N 10 6 N 60 N 25 3 P 36 12 Pn 20 Pn 2 DIP 2 PWM P3 PWM N P1st Pn P3 66...
Страница 145: ...143 26 2S 27 2S...
Страница 146: ...144 EVO T EVO T COMPACT 28 EH M 18kW 1 PE_ PE_ Max 18...
Страница 147: ...145...
Страница 148: ...146 EVO T EVO T COMPACT 29 EH M 36 kW 3 Max 12 Max 12 Max 12 PE_ 0 5mm2 blue 0 5mm2 white...
Страница 149: ...147 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2...
Страница 150: ...148 EVO T EVO T COMPACT 30 4S 31 4S...
Страница 155: ...153 1 2 3 40 15 1 8 HMI HMI OK C HMI 15 1 9 HMI 3 C Alarms history 41 42...
Страница 159: ...157 48 Panel HMI 15 2 6 HMI HMI HMI HMI HMI OK C HMI 15 2 7 SLIDEBAR ALARMS Alarms history 49 50 ON OFF...
Страница 161: ...159 16...
Страница 162: ...160 EVO T EVO T COMPACT...
Страница 163: ......