Filtering unit

 

BIG-5000/Ex

 

08.10.2019 

 

 

B2x 

Maximum load power on the output 25W 

HV 

Selection of the supply voltage for inputs / outputs 

By means of the jumper, select suitable input and output voltage 

JP1 

Select the supply voltage between 

115VAC 

and 

230VAC

 

JP2 

Select the supply voltage between 

24

115

230V

 

– exclusively at supply 

115VAC 

or 

230VAC

 

JP3 

Select the output voltage 

– between AC and DC – exclusively at 

JP2

 adjusted for 

24V

 

CAUTION

:  Set  the 

F08

  into  the  same  value  of  the  output  voltage,  that  has  been  selected  via  bridges 

–  to 

establish the threshold of short-circuit. 
Otherwise, this would result in any malfunction or damage of the micro-controller. 

 

7.3  Startup of the system

 

Connect the elements strictly according to the diagram, using cables selected with reference to current-carrying 
capacity of the receivers. 

 

Switch on the protections in the switchgear 

A1

 

Check if the 

F1

 fuse in the micro-controller 

A2

 is not damaged. 

 

Apply the supply voltage with the 

S1

 disconnector in the switchgear 

A1

 

Switch on the system with the 

S2 

switch. 

 

The fan can be safely started with the green button 

S3.2

 

– under the condition that the red lamp 

ALARM

 (on 

the 

A1

 switchgear door) in not on. 

 

When  the  green  lamp  (built  in  the  double  button 

S3

)  is  lighting 

–  this  is  the  information  that  the  fan  is  in 

operation and the filter regeneration system is switched on; {To make sure, the filter regeneration system is 
functioning 

– after the first device startup, examine the device,  check (after the ALARM state emerges) the 

communicates  emerging  on  the  micro-controller  display}.  Additionally,  after  the  first  start-up,  check  the 
rotation sense of the fan impeller. 

 

To switch off the fan 

– press the red button 

S3.1

 

The green lamp (build in the button) goes off 

– subsequently, proceeds the final filters regeneration – at any 

time the fan can be started again. 

 
7.4  Alarms

 

In the device can appear states of alarms, caused by: 

 

activation of the motor protective switch 

 

interruption of the sensors on the decompression membrane, 

 

alarm from the micro-controller (controlling the function of the electromagnetic valves) 

– description in 7.2.2 

These alarms are signalised by the red lamp 

H2

 (placed on the door of the switchgear 

A1

). When the alarm 

occurs, it is important to disconnect the power supply by means of the 

S1

 disconnector.  Next, find the fai-

lure/damage,   find out its/their reason  and  remove the malfunction.  After the failure is removed correctly, 
and the power supply is applied again 

– the filtering unit can be operated again. 

 

excessive overheating of the motor windings 

– 

PTC

 sensor. 

 
The appliance stops working, but the signalling of activation of the protection 

– relay TP – is possible to localise 

– after the time passed when the switchgear 

A1

 opens. Signal from the 

PTC

 sensor flows to the resistance relay 

PT

The  normal  status  of  the  resistance  relay 

PT-1

  is  signalised  by  the  green  diode 

OK

.  In  case  when  the  motor 

windings become overheated, (after the resistance  of the 

PTC

 sensor exceeds  3,3k

), the relay converts into 

status of 

“failure”. Subsequently, the contact of the relay will switch, whereby the red diode 

PTC

 is lighted. The 

diode 

OK

  goes  off. When  the  motor  windings  cool  down,  after  the  resistance  of  the 

PTC

  sensor  drops  below 

1,8k

, the resistance relay returns to normal status. 

When in the 

PT

 the mode of 

“memory” is switched on, (despite the motor windings cool down)  – the status of 

“failure” will remain until the button DELETE (KASOWANIE) is pressed by the operator. 
In the normal status of the resistance relay 

PT

, when the DELETE (KASOWANIE) button is pressed and hold for 

1 second 

– switches on the test of the device (for the time when the button is hold). If the test is switched on, while 

the device runs in mode “memory”, the status of “failure” will be stored.  
In order to return to “normal” state – press the button DELETE (KASOWANIE). The red 

PTC

 diode is blinking, 

this indicates the state:  the sensor 

PTC

 has short-cut or disconnected. This situation occurs when the resistance 

at the input (of the 

PTC

 sensor) decreases below 40

 or increases above 7k

. In these cases, the device gets 

into state of “failure”. The memory of the status “failure” is maintained, also after the supply voltage fades. 

 

CAUTION

:

 

When the extraction fan is not functioning correctly, please contact the Deliverer. 

 

7.5  Removal of dust

 

The dust must be emptied systematically, when the waste container is filled up. User has to give instructions to 
the operating personnel, that 

while disconnection of the waste container from the hopper (by means of the 

blocking lever) they must take precautions

. In case when the waste container is not sufficiently supported from 

Содержание BIG-5000/Ex

Страница 1: ...ION 4 ASSEMBLY AND STARTUP 6 OPERATIONAL USE 8 TROUBLESHOOTING GUIDE 13 MAINTENANCE AND REPAIR 13 OCCUPATIONAL HEALTH AND SAFETY 14 TRANSPORT AND STORAGE 14 TERMS OF WARRANTY 15 DECLARATION OF CONFORM...

Страница 2: ...afety of machinery Safe distances to prevent hazard zones from being reached by up per and lower limbs EN 60079 0 2013 03 A11 2014 03 Electrical appliances in areas of gas explosion hazard Part 0 Gene...

Страница 3: ...tional use it is important to prevent ignition sources i e sparks cigarette butts embers from getting into the filtering unit 3 3 Operator should wear antistatic clothes while emptying the waste conta...

Страница 4: ...er They have been classified as zone 22 Fig No 2 Classification ATEX internal zones STRUCTURE ADN FUNCTION 5 1 Structure BIG 5000 Ex filtering unit consists of three functional assemblies Regeneration...

Страница 5: ...ils described in separate Use and Maintenance Manual In Fig No 3 is illustrated the filtering unit along with the fan chamber Connection between these two units is an example as applied in the test st...

Страница 6: ...arge dimensions At the upper part of the regeneration chamber are installed lifting hooks for lifting and positioning during the transport and assembly activities After the chamber of filters is conne...

Страница 7: ...n sorts Any activities related to the installing necessarily must be performed by a specialised assembly team after being instructed Having completed the assembly check the conductivity between the su...

Страница 8: ...ned to operate the filtering unit providing automatic regeneration of surfaces of the filters by means of cyclical impulses of compressed air The control system consists of subsequent assemblies switc...

Страница 9: ...Q1M motor protective switch F1 F2 overcurrent disconnectors T1 transformer K1 electromagnetic relay K1T K2T time relays K1M contactor PT resistance relay Fig No 10 Switchgear A1 control unit Fig No 1...

Страница 10: ...from dP not active 0 01 9 99 kPa F13 control with the regeneration process 0 via contact 1 by readout from dP dP converter of the difference of pressures 7 2 1 Description of the displayed messages o...

Страница 11: ...of this function the display shows the dP readout and while the fan is stopped or the pipe conduits are not connected if the dP readout does not have the value 0 00 kPa this can be adjusted with pushb...

Страница 12: ...the door of the switchgear A1 When the alarm occurs it is important to disconnect the power supply by means of the S1 disconnector Next find the fai lure damage find out its their reason and remove t...

Страница 13: ...Dust emerges outside the devi The cartridge filter is not tightly con Replace the cartridge filter or ce nected of damaged improve its mounting The dust is of another sort than stated Contact the manu...

Страница 14: ...system During these activities it is important to wear antistatic clothes While emptying the waste container of the dust during the dismantling of the container and its mounting the waste container mu...

Страница 15: ...d device is indicated in the Card of Warranty The warranty does not comprise mechanical damage and malfunctions caused by User device failures caused during the use which is in contradiction with the...

Страница 16: ...of the European Parliament and of the Council of the 26 February 2014 on the harmo nisation of the laws of the Member States relating to the equipment and protective systems intended for use in potent...

Отзывы: