Klimawent BIG-5000/Ex Скачать руководство пользователя страница 10

Klimawent

 – the warranty of highest quality at attractive price 

 

 

 

10 z 16 

Filtering unit

 

BIG-5000/Ex

 

08.10.2019 

 

The 

A3

 terminal box connects the cable to the sensors on the venting panel, with the output cable, (going out of 

the Switchgear 

A1

).  When the cable on the panel is interrupted  (during the explosion),  the device automation 

disconnects the fan and the system of regeneration of filters.  Any electrical connections ought to be performed 
in conformity with the above placed Connection Diagram 

– see Fig. No.7, and 8. 

Motor in ATEX execution is secured with the motor switch with protection against the blocked startup, overload, 
short-circuit- and fade of one phase.   Additionally, the motor is protected  by  the 

PTC

 sensor, installed directly 

within its windings, as a protection against the excessive overheating. 
 

7.2  Use of the A2 micro-controller 

 

press 

C

 

– to get access to the functions 

F01 

– F13 

 

press 

C

 one more time 

– to select the requested function 

 

press 

A

 

– to enter into the selected function 

 

press 

A

 or 

C

 

– to introduce changes of the settings  

 

press 

B

 

– to return to the functions 

F01 

– F13

 

 

press 

B

 one more time 

– to return to the mode of display of work parameters. 

 

Table No.2  

–  Functions F01 – F13 

F01 

external enter 

– ON;  2 – OFF 

F02 

time of impulse 

0,05 

 5,00 [s] 

F03 

time of break between the impulses 

 999 [s] * (B3x) 

F04 

quantity of enters 

0-48 

F05 

quantity of regeneration cycles 

– after the fan is stopped 

 99 

F06 

manual activation 

– selected / A – activation from the external signal 

F07 

control from the signal 

dP

 

not active 

– OFF;  2 – ON 

F08 

output voltage  

24V,  115V,  230V  *(HV) 

F09 

zero point trimming 

– for 

dP

 

not active

 

0,00 *(C8) 

F10 

regeneration disconnection pressure 

– from 

dP

 

not active

  0,01 

 9,99 kPa 

F11 

pressure of regeneration start 

– from 

dP

 

not active

 

0,01 

 9,99 kPa 

F12 

maximum pressure for the alarm 

– from 

dP

 

not active

 

0,01 

 9,99 kPa 

F13 

control with the regeneration process 

– via contact;  1 – by readout from 

dP

 

dP

 

– converter of the difference of pressures 

 
7.2.1  Description of the displayed messages of the micro-controller A2  
Table No.3  

–  Messages from the display 

OFF 

the regeneration is stopped (for the open 

D6

 input) 

-0- 

final regeneration 

– after the fan is disconnected (input D1a is open) 

1.00/P 

final regeneration 

– for the signal of low pressure difference – from dP (display light is pulsing) 

A01 

number of the activated electromagnetic valve 

… 

final regeneration is in progress 

– after the fan is disconnected (blinking points) 

1.23 

readout 

– difference of pressures [kPa] 

readout 

– difference of pressures – beyond the scale 

Pushbutton 

B

 

– reset of ALARM on the micro-controller 

Pushbutton 

C

 

– enter the menu 

 

7.2.2  Description of the displayed ALARM messages on the A2 micro-controller

 

1.50/H 

ALARM of the preset maximum pressure difference (parameter 

F12

) the display is blinking; check the 

coil of the electromagnetic valve and the frequency of regenerations; 

E1/05 

overload of the output 

05

 

– the display is blinking;  check the connections of the electromagnetic valve, 

the  state  of  the  coil  of  electromagnetic  valve,  examine  the  occurrence  of  eventual  water  in  the  con-
nection plug 

 

7.2.3  Description of the displayed messages on the A2 micro-controller

 

B1b 

selection of the quantity of enters 

means selection of enters 

– started from the keyboard in the mode “settings”;   

if 

0

  or 

AUTO

  is  selected,  in  this  function,  the  micro-controller  automatically  choses  the  outputs  from 

electro-valves and ignores the outputs without the overload; 

B2x 

time of activation of output 

(

time

 

of impulse

from 0,05 up to 5,00 seconds 

B3x 

time of interval 

– from 1 up to 999 seconds 

if the time of impulse is less than 1 second 

– it is possible to set any interval time – within the indicated  

range;   
if the activation time is more than 1 second 

– the minimum adjustable interval time is:  

                                minimum interval time = 5 x impulse time (

B2x

 
 

 

Содержание BIG-5000/Ex

Страница 1: ...ION 4 ASSEMBLY AND STARTUP 6 OPERATIONAL USE 8 TROUBLESHOOTING GUIDE 13 MAINTENANCE AND REPAIR 13 OCCUPATIONAL HEALTH AND SAFETY 14 TRANSPORT AND STORAGE 14 TERMS OF WARRANTY 15 DECLARATION OF CONFORM...

Страница 2: ...afety of machinery Safe distances to prevent hazard zones from being reached by up per and lower limbs EN 60079 0 2013 03 A11 2014 03 Electrical appliances in areas of gas explosion hazard Part 0 Gene...

Страница 3: ...tional use it is important to prevent ignition sources i e sparks cigarette butts embers from getting into the filtering unit 3 3 Operator should wear antistatic clothes while emptying the waste conta...

Страница 4: ...er They have been classified as zone 22 Fig No 2 Classification ATEX internal zones STRUCTURE ADN FUNCTION 5 1 Structure BIG 5000 Ex filtering unit consists of three functional assemblies Regeneration...

Страница 5: ...ils described in separate Use and Maintenance Manual In Fig No 3 is illustrated the filtering unit along with the fan chamber Connection between these two units is an example as applied in the test st...

Страница 6: ...arge dimensions At the upper part of the regeneration chamber are installed lifting hooks for lifting and positioning during the transport and assembly activities After the chamber of filters is conne...

Страница 7: ...n sorts Any activities related to the installing necessarily must be performed by a specialised assembly team after being instructed Having completed the assembly check the conductivity between the su...

Страница 8: ...ned to operate the filtering unit providing automatic regeneration of surfaces of the filters by means of cyclical impulses of compressed air The control system consists of subsequent assemblies switc...

Страница 9: ...Q1M motor protective switch F1 F2 overcurrent disconnectors T1 transformer K1 electromagnetic relay K1T K2T time relays K1M contactor PT resistance relay Fig No 10 Switchgear A1 control unit Fig No 1...

Страница 10: ...from dP not active 0 01 9 99 kPa F13 control with the regeneration process 0 via contact 1 by readout from dP dP converter of the difference of pressures 7 2 1 Description of the displayed messages o...

Страница 11: ...of this function the display shows the dP readout and while the fan is stopped or the pipe conduits are not connected if the dP readout does not have the value 0 00 kPa this can be adjusted with pushb...

Страница 12: ...the door of the switchgear A1 When the alarm occurs it is important to disconnect the power supply by means of the S1 disconnector Next find the fai lure damage find out its their reason and remove t...

Страница 13: ...Dust emerges outside the devi The cartridge filter is not tightly con Replace the cartridge filter or ce nected of damaged improve its mounting The dust is of another sort than stated Contact the manu...

Страница 14: ...system During these activities it is important to wear antistatic clothes While emptying the waste container of the dust during the dismantling of the container and its mounting the waste container mu...

Страница 15: ...d device is indicated in the Card of Warranty The warranty does not comprise mechanical damage and malfunctions caused by User device failures caused during the use which is in contradiction with the...

Страница 16: ...of the European Parliament and of the Council of the 26 February 2014 on the harmo nisation of the laws of the Member States relating to the equipment and protective systems intended for use in potent...

Отзывы: