Filtering unit BIG-1000
11 of 19
NOTICE
Filter regeneration takes place automatically while the fan is running. Regeneration takes
place every
4 minutes
, and the process lasts as long as the fan is running.
Stopping the fan
A.
Press the
S2.1 “STOP”
button located in the centre of the control panel. The fan will coast to a stop.
The green light
S2.H2
will go out.
Turning off the device
A.
Set switch
S1
to the
OFF
position. The white lamp
S1.H1
will go out.
Working time control
There is a working time counter on the electric unit door, which allows you to check the time of use of the
appliance.
When cleaning, filter replacement or other maintenance work, it is advisable to make a note of the number of
operating hours. This will help in the future to predict the moment of service work and plan it when it is not in use.
Modification of process Times
The
BIG-1000
device is equipped with a
modular clock
that controls process times during the operation: i.e.
time opening of air pulse valve
T1
and time between valve openings
T2
– see Picture 6.
! CAUTION
The compressed air consumption depends on the set process times. Whenever process
times change, you
NEED
to adjust your compressed air consumption!
It is
NOT
recommended to modify the time parameters!
FRONT VIEW
A
– Time scales rotary selector (
T1
)
B
– Time multiplier (
T1
)
C
– LED
D
– Time scales rotary selector (
T2
)
E
– Time multiplier (
T2
)
TIMESCALES
Incrementation of
A
and
C
scales:
1sec; 10sec; 1min; 10min; 1hours; 10hours; 100hours
MULTIPLIERS
Incrementation of
B
and
D
scales
:
0.1; 0.2; 0.4; 0.6; 0.8; 1
EXAMPLES
Example 1: T1 = 0,5 sec: set
B
= 1 sec and
A
= 0.5
T1
= 1 × 0.5 =
0.5 sec
Example 2: T2 = 4 min: set
D
= 10 min and
C
= 0.4
T2
= 10 × 0.4 =
4 min
Picture 6 Modular timer
A
B
C
D