KP310V1.0 Controller Operation Manual
- 18 -
Communication
33
Communication
Address
●○○○○●
0-32
1
1
Communication address with the
PC
Maintenance
34
Fuel filter
maintenance
time
●○○○●○
0-65535
0.1Hr 5000
Engine Fuel filter replace
countdown
35
Air filter
maintenance
time
●○○○●●
0-65535
0.1Hr 5000
Engine Air filter replace
countdown
36
Oil filter
maintenance
time
●○○●○○
0-65535
0.1Hr 5000
Engine Oil filter replace
countdown
Programmable Input Set
37 Remote
set
●○○●○●
0-5
1
4
0-Remote Start Normally Open
1-Remote Start Normally Closed
2-Remote Stop Normally Open
3-Remote Stop Normally Closed
4-Remote Start & Stop Normally
Open
5-Remote Start & Stop Normally
Closed
38
Remote start
delay
●○○●●○
0-65535
0.1s
50
In remote mode, timing from give
start signal to successfully start.
39
Remote Stop
Delay
●○○●●●
0-65535
0.1s
50
In remote mode, timing from give
Stop signal to successfully stop.
40
Remote start
Times
●○●○○○
1-10
1
3
In remote mode, start times in the
normal range
41 Input
1
Type
●○●○○●
0-3
1
0
0-Warning Normally Open
1-Warning Normally Closed
2-Stop Normally Open
3-Stop Normally Closed
42
Input 1 Fault
Delay
●○●○●○
0-65535
0.1s
0
Set input 1 Fault Delay timing
43 Input
2Type
●○●○●●
0-3
1s
0
0-Warning Normally Open
1-Warning Normally Closed
2-Stop Normally Open
3-Stop Normally Closed
44
Input 2 Fault
Delay
●○●●○○
0-65535
0.1s
0
Set input 2 Fault Delay timing
Programmable Output Set
45
Set Output 1
●○●●○●
0-16
1
0
0-Reserved
1-Genset Stop
2-Genset Preheat