KP310V1.0 Controller Operation Manual
- 13 -
6.3 Emergency stop alarms
After detecting the emergency stop alarms, relevant LED twinkles, and genset will be stopped
instantly. Buzzer will give alarms.
No.
Type
Description
1
Over
Frequency
If genset frequency is larger than the set value, over frequency LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
2
Under
Frequency
If genset frequency is lower than the set value, under frequency LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
3
Over
Voltage
If genset voltage is larger than the set value, over voltage LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
4
Under
Voltage
If genset voltage is lower than the set value, under voltage LED
twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
5
Over
Frequency
If genset frequency is larger than the set value, over frequency LED
twinkles, genset will be stopped instantly.
6
Under
Frequency
If genset frequency is lower than the set value, under frequency LED
twinkles, genset will be stopped instantly.
7
Low Oil
Pressure
If oil pressure is lower than the set value, low oil pressure LED
twinkles, genset will be stopped instantly.
8
High Water
Temperature
If water temperature is higher than the set value, high water temperature
LED
twinkles, genset will be stopped instantly.
9 Start
failure
If genset failed to start in the set time, start failure LED
twinkles,
genset will be stopped instantly.
10
Emergency
Stop
While press the emergency stop button, emergency stop LED
twinkles, genset will be stopped instantly.
Note:
1
、
“Over frequency” protection can be disabled if “over frequency alarm delay time” is set as 0.
2
、
“Under frequency” protection can be disabled if “under frequency alarm delay time” is set as 0.