2.2.1 Cold Main Pipework

Please refer to local code for cold mains pipe work installation. 

Run the cold main through the building to the place where the KINGSPAN TRIBUNE is to be installed. Take care not to run 

the cold pipe near hot water or heating pipe work so that the heat pick-up is minimized. Identify the cold water supply pipe and 

fit an isolating valve (not supplied). A quarter turn full bore valve is ideal as it does not restrict the flow as much. Do not use 

“screwdriver slot” or similar valves.

Thermal Expansion:

Determine if a check valve exists in the cold inlet water line (These may be incorporated in a pressure reducing valve, water 

softener, water meter or as a separate back flow preventer).

If a check valve exists then this will cause a closed water system meaning that thermal expansion may cause a pressure build 

up within your hot water tank. In such a case an expansion tank must be fitted to allow for any excess pressure caused by 

thermal expansion. Please see figure.2 for reference.

Water pressure:

If the incoming water pressure is over 80 PSI a pressure reducing valve (Water pressure regulator) must be fitted. This is to be 

located on the inlet water line before the tank so that the inlet pressure to the tank does not exceed 80 PSI.

Make the connection to the cold feed of the tank. 

Select a suitable position for the expansion tank. Mount it to the wall. Use the flexible hose or pipe to connect to the expansion 

relief valve.

 

 

 Page 5 of 12

Figure.2 Schematic of layout

2.2.1 COLD MAIN PIPEWORK 

Balanced supply allows the 

TRIBUNE to provide balanced 

pressure to the remainder of the 

dwelling. Mixing device should 

be used to prevent scalding and 

control temperature of water 

from the outlet taps.

Содержание Tribune

Страница 1: ...IMPORTANT NOTE TO THE INSTALLER Read these instructions before commencing installation Installation Manual For Kingspan Tribune USA Issue 4 Sept 2010 Part No BOOKSTAINULT Page 1 of 12 Tribune ...

Страница 2: ...ate this water heater if it is not working properly or if it has been damaged or dropped 8 This water heater should be serviced only by qualified service personnel Contact nearest authorized service facility for examination repair or adjustment SAVE THESE INSTRUCTIONS DANGER Very Hot Water can cause serious injury or death Ensure that you comply with the instructions contained within this manual a...

Страница 3: ...t maximum of 2 The pan should be connected to drain by a bore drain Consult a certified plumber for more information The KINGSPAN TRIBUNE should be located near to a drain to allow the drainage of water during maintenance and as an outlet for the safety equipment located on the unit The KINGSPAN TRIBUNE tank can supply outlets above it or at some distance from it Site the unit to minimise dead leg...

Страница 4: ...s allows a variety of heat sources to be used In the single coil configuration this can be connected to a boiler or solar circuit Twin coil tanks the lower coil is connected to a solar circuit and the top coil to a boiler system Figure 1 shows a schematic of the tank configuration Page 4 of 12 Figure 1 Single and Twin coil configurations ...

Страница 5: ...d water system meaning that thermal expansion may cause a pressure build up within your hot water tank In such a case an expansion tank must be fitted to allow for any excess pressure caused by thermal expansion Please see figure 2 for reference Water pressure If the incoming water pressure is over 80 PSI a pressure reducing valve Water pressure regulator must be fitted This is to be located on th...

Страница 6: ...e The hot water tank has a NPT female connection to accommodate this apparatus in the top of the tank CAUTION To reduce the risk of excessive pressures and temperatures in this water heater install temperature and pressure protective equipment required by local codes but no less than a combination pressure valve certified as meeting the requirements for Relief Valves and Automatic Gas Shutoff devi...

Страница 7: ...r the immersion heater current load The unit must be grounded to a properly installed ground circuit using an appropriate field terminal Check the immersion heaters are 240V and rated at 4500W this should be stated on the case Figure 3 shows the layout and wiring schematic of the heating element To access the wiring terminals firstly remove the temperature dial by gently pulling of the dial comple...

Страница 8: ...pen every other hot faucet in turn to purge all remaining air 3 1 FILLING If the tank is to be heated by an indirect boiler consult the boiler manufacturers commissioning instructions and fill the primary circuit accordingly Two port valves and tank thermostats may need to be used to control input into the KINGSPAN TRIBUNE unit 3 2 INDIRECT UNITS During heat up there should have been no sign of wa...

Страница 9: ...3 4 INSTALLATION CHECKLIST FLOW CHART Page 9 of 12 Figure 4 Check list of installation steps ...

Страница 10: ...me as the annual boiler or solar system service 1 Lift the lever on the expansion relief valve on the inlet control set and allow water to flow for 5 seconds Release and make sure it resets correctly Repeat with the pressure temperature relief valve In both cases check that the discharge pipe work is carrying the water away adequately If not check for blockages etc and clear WARNING THE WATER DISC...

Страница 11: ...er than by kingspan It has not been misused tampered with or subjected to neglect It has only been used for the storage of potable water It has not been subjected to frost damage The unit has been serviced annually The guarantee period starts from the date of purchase and no registration is required The guarantee is not transferable and rests with the original householder The system is fed from a ...

Страница 12: ......

Отзывы: