Vent Termination
WARNING:
WHEN THE
HORIZONTAL VENT
TERMINATION IS
ACCESSIBLE A
CERTIFIED GUARD
(SAFETY CAGE) SHALL
BE INSTALLED.
V
Vent Terminal
Air Supply
Area Where Terminal Not Permitted.
A - Clearance above grade, veranda, porch, deck, or balcony 12
inches (30cm) minimum.1-2
B - Clearance to window or door that may be opened. 12 inches (30cm)
minimum for appliances 100 000 Btuh (30 kW) and lower, in Canada.
9 inches2 (23cm) for appliances 50 000 Btuh and lower, in USA.
C - Clearance to permanently closed window minimum 12 inches
(30cm) recommended to prevent condensation on window, in
Canada. 9 inches2 (23cm) for appliances 50 000 Btuh and
lower, in USA.
D - Vertical clearance to ventilated soffit located above the termina-
tion within a horizontal distance of 2 feet (60cm) from the center
line of the termination. 18 inches (46cm) minimum.5
E - Clearance to unventilated soffit 12 inches (30cm) minimum.
F - Clearance under veranda, porch, deck or balcony 12 inches1
(30cm) minimum.4 US5
G - Clearance from a perpendicular inside wall or outer corner to
the edge of the vent terminal plate is 3” (minimum).
H - Clearance to each side of center line extended above
meter/regulator assembly 3 feet (91cm) within a height 15
feet (4.5m) above the meter/regulator assembly.
I - Clearance to service regulator vent outlet 3 feet (91cm)
minimum.1 US5
J - Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance: In Canada, 6 inch-
es (15cm) for appliances
≤
10,000 Btuh (3kW), 12 inches1
(30cm) minimum for appliances >10,000 Btuh (3kW) and
≤
100,000 Btuh (30kW), 36 inches (91cm) for appliances
>100,000 Btuh (30kW). In the USA, 6 inches2 (15cm) for appli-
ances
≤
10,000 Btuh (3kW), 9 inches (23cm) for appliances
>10,000 Btuh (3kW) and
≤
50,000 Btuh (15kW), 12 inches
(30cm) for appliances >50,000 Btuh (15kW).
K - Clearance to a mechanical air supply inlet 6 feet (1.8m) mini-
mum.1,in Canada. In USA, 3 feet (91cm) above if within 10
feet2 (3m) horizontally.
L - Clearance above paved sidewalk or a paved driveway located
on public property 7 feet (2.1m) minimum.3
M - Clearance above highest point of exit on roof 18 inches
(45cm).
N - Clearance to perpendicular wall 24 inches (60 cm).
(Recommended to prevent re-circulation of exhaust products.
For additional requirements check local codes.)
Measure to the edge of the termination plate.
Measure to the edge of the round termination.
NOTE: Clearances are to the edge of terminal plate, add 6-
3/4” to clearances to arrive at center line.
NOTE: Local Codes or Regulations may require different
clearances.
Termination
It is imperative that the vent termination be located observing the
minimum clearances as shown. There must not be any obstruc-
tion such as bushes, garden sheds, fences, decks or utility build-
ings within 24” from the front of the termination plate.
Do not locate termination where excessive snow or ice build-up
may occur. Be sure to check vent termination area after snow
falls and clear to prevent accidental blockage of venting system.
When using snow blowers, make sure snow is not directed
towards vent termination area.
General Venting Information
The gas fireplace is approved to be vented either through the
side wall or vertically through the roof.
This appliance is approved with Kingsman flex vent system.
ONLY VENTING COMPONENTS SPECIFICALLY APPROVED
AND LABELED FOR THIS FIREPLACE MAY BE USED.
Venting terminal shall not be recessed into a wall or siding. If fin-
ishing the outside wall with vinyl or wood siding it is recommend-
ed that a Siding Shield be installed, Part Number ZDVSSLR.
1 - In accordance with the current CSA B149.1, Natural Gas
and Propane Code.
2 - In accordance with the current ANSI Z223.1/NFPA 54,
National Fuel Gas Code.
3 - A vent shall not terminate directly above a sidewalk or
paved driveway that is located between two single family
dwellings and serves both dwellings.
4 - Permitted only if veranda, porch, deck, or balcony is fully
open on a minimum of two sides beneath the floor.
5 - Clearance in accordance with local installation codes and
the requirements of the gas supplier.
46
Содержание ZRB46
Страница 31: ...Gas Conversion for Modulator PART C WARNING WARNING 31...
Страница 41: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 41...
Страница 42: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 42...
Страница 53: ...5 1 1 2 1 2 10 5 8 1 1 4 8 1 8 12 1 2 16 58PVH Dimensions 13 13 10 5 8 11 13 11 11 11 3 8 5 8 1 8 11 1 8 53...
Страница 63: ...PVCM Schematic Millivolt 63...
Страница 67: ...PVCM Schematic IPI 67...
Страница 68: ...68...