General Vent Installation Information

Installation Of Side Wall Venting

1. The minimum distance from the bottom of fireplace to centre of vent is 33 inch 

(81 cm) (See Figure 1). Cut a hole through the wall allowing for a 11” x 11”
(inside diameter) in combustible walls for wall thimble or an 8” diameter hole in a
non-combustible wall (See Figure 2).

2. Note clearance to combustible above 90 degree bend is 2

1

/

2

”. For minimum 

enclosures see Page 7.

3. Select the approximate vent length, precise measurements are not needed as your

flex pipe can be expanded to twice its shipped length for ease of installation.

4. To install wall thimble centre over 11” x 11” (inch) framing from both sides of

wall and secure. Route flex vent pipe through wall thimble (See Figure 1).

5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of

pipe. First attach the four inch (4”) flue pipe to the vent termination with sealant
and secure with 4 screws provided.  At this time make sure the spacer springs are
attached to the (4”) flex pipe as required.  Then attach the seven inch (7”) pipe by
the same method.

6. Mount vent termination and seal to wall using caulking around the wall thimble to

weather proof. After installing the vent termination, double check to make sure the
pipe extends properly through wall thimble and into vent termination.

7. Before joining pipes to fireplace flue, apply a bead of high temperature sealant

(Mill Pac) to end of pipe. First attach the four inch (4”) flue pipe to fireplace with
sealant  and secure with 4 screws provided.  At this time verify that the spacer
springs are attached properly to the (4”) flex pipe as required. Then attach the
seven inch (7”) pipe by the same method.

8. Support horizontal pipes every two (2) feet (61 cm) with metal strap bands. Re-

check fireplace to make sure it is levelled and properly positioned and secured.

9. Support vertical pipes to maintain a minimum of 1” or greater clearance to com-

bustibles with metal strapping bands.

10. If finishing the outside wall with vinyl or wood siding it is recommended that a

Siding Shield be installed, Part Number ZDVSSLR.

FIGURE 1

FIGURE 2

MINIMUM OF
1.0" TO
COMBUSTIBLES

33.0"

MINIMUM

COMBUSTIBLE AIR INLET

FLUE GAS OUTLET

34.0"

15.25"

FRAMING DETAIL

11.0"

11.0"

8" DIA

33.0" TO CENTERS
MINIMUM

THROUGH COMBUSTIBLE
WALL

THROUGH NON-COMBUSTIBLE
WALL

RIGID OR HARD PIPE

When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal DV and or
Selkirk Direct Temp a Duravent hardpipe adapter must be used (part # ZDVDFA  for fireplaces and part #
ZDVDKA for Stoves, Serenity and ZDV3624B). Follow installation instructions provided by Simpson
Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel Direct, Metal Fab Sure-Seal DV for installation of
pipe and adhere to the clearance to combustibles provided in this manual. Apply a bead of Mill Pac high
temp sealant to all joints of pipes, adapters and termination, when using Kingsman Flex(Z-Flex)Venting
venting and Simpson Duravent venting. 

NOTE:

Increase framing depth by one inch when using hardpipe.

Flex Pipe Venting

Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the lengths. Pipe can
be expanded to twice their lengths e.g. 4ft. to 8ft. Fully expand pipe and cut off excess.
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an installation
attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 4” flex in the center of 7” flex.
When forming bends place spring in bend or before and after. (See Fig. 1).
Horizontal runs require support metal straps every 2 feet. In off set installation support straps should be
used to stabilize pipe.
Expand 4” and 7” flex pipe to the point that the 7” protrudes approximately 2 to 3 inches past outer wall and
the 4” flex protrudes approximately 2 to 3 inches past the 7” flex. See Fig. 1. Attach the 4” pipe to the termi-
nation first and secure with sealant and screws then attach the 7” flex to the termination with caulking and
screws. Termination may then be moved back to the outer wall and attached to home screwing into the
framing. Silicone around termination to waterproof. If siding shield is going to be used attach this using
same attaching hole as the top of termination after termination has been caulked for water proofing.

Use Hi Temp Sealant

Apply a bead of mill pac high temp sealant to all joints and use four screws to secure each pipe at fireplace,
termination and any joint if joining any sections of pipe.

NOTE: 

It is critical to the proper and safe

operation of this fireplace that on all connec-
tions the inner liner and the outer casing are
both caulked with liberal amounts of sealant.
Do not use any kind of tape or silicone other
than that recommended in this manual, Mill
Pac Sealant

FRAMING DIMENSION
Combustible Wall

Cut a 11” hole through exterior wall and frame

as shown below.

Non combustible Wall

Cut or drill 8” or 204mm diameter hole.

OPTIONAL
CLAMPS

FIGURE 1

MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS

OPTIONAL
CLAMPS

SEAL WITH HIGH TEMP. SEALANT

SEAL WITH HIGH TEMP. SEALANT

WARNING: 

DO NOT mix parts from different systems unless stated in the manual.

This gas appliance is approved to be vented either through the side wall or vertically through the roof.  

Only Kingsman Flex(Z-Flex)Venting Kits and

components specifically approved and LABELED for this stove may be used

.  This appliance is also approved for use with Simpson-Duravent Direct

Vent system (Model DV-GS Series), Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.

Simpson Dur a-Vent for  Masonr y Chimney Conver sion Kits may be used with this appliance Use your existing masonry chimney and route
the exhaust gases intake air through the side of the masonry chimney. Use Simpson Dura-Vent kit numbers 46DVA-KMC or 46DVA-KCT.
Termination Cap, Kingsman/Dura-Vent adapter, and 4” flex are sold separately.

Simpson Dur a-Vent for  Factor y built metal Chimney Conver sion Kits may be used with this appliance. Use your existing through the ceil-
ing, wood stove chimney and route the exhaust gases and intake air through the existing wood burning metal chimney. Use Simpson Dura-Vent
Kit numbers 46DVA-KCA for 6 5/8” to 8 5/8” OD sized chimney, 46DV-KCB for 8 3/4” to 10 1/2” OD sized chimneys and 46DVA-KCC for
10 5/8” to 13” OD sized chimneys. Kits 931, 932, and 933 include a cap adapter and Retro Connector. Termination Cap, Kingsman/Dura-Vent
adapter, and 4” flex are sold separately.

Содержание ZDV3620

Страница 1: ...e vapors and liquids in the vicinity of this or any other appliance What To Do If You Smell Gas Do not try to light any appliance Extinguish any open flame Do not touch any electrical switch Do not us...

Страница 2: ...tory However due to the high temperature sili cone components the paint will cure when heat is applied to the appliance as it is first used The following information applies to the curing process to g...

Страница 3: ...ly 11 Fan kit installation 12 Millivolt system lighting burner control 13 Vent termination 14 Venting graph 15 General vent installation information 16 Installation of side wall venting 16 Venting ver...

Страница 4: ...is of the home with 8 ga copper wire using a serrated or star washer to penetrate paint or protective coating to insure grounding Use carriage bolt at the attachment point see diagram above to secure...

Страница 5: ...n under water Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water 12 WARNING Do not opera...

Страница 6: ...terminal must be used and if applicable a Product approved air intake must be used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructi...

Страница 7: ...nt system does not exceed 20 feet 6 1m When you install your fireplace as in position B D or E a minimum of 6 inches 153mm clearance must be maintained from the perpendicular wall and the front of the...

Страница 8: ...appliance on the bottom sides and top of fireplace 4 When installing horizontal with a 90 degree bend maintain a minimum of four 21 2 inches above the bend in enclosures 5 Hearth is not mandatory but...

Страница 9: ...tel such paint or lacquer must be heat resistant 250 F to prevent discoloration Warning Combustible objects must not be placed on a non combustible mantel unless the non combustible mantel meets the m...

Страница 10: ...solution 8 The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 5...

Страница 11: ...of log must be shifted to the left against tab for proper log placement 4 Front log should be placed in front of burner up against log grate 5 Place right and left logs across front and back log in t...

Страница 12: ...eed switch from the wall mount Turn the variable speed wall controller to its minimum setting fully clockwise Use the set screw on the side of the variable speed controller to increase or decrease the...

Страница 13: ...pilot screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA 1...

Страница 14: ...al codes V NOTE Clearances are to the edge of terminal plate add 6 3 4 to clearances to arrive at center line NOTE Local Codes or Regulations may require different clearances Termination It is imperat...

Страница 15: ...f bends required 2 Having determined the vertical distance determine the maximum horizontal section allowed 3 Vent table has been established for 90 horizontal vertical runs With use of flex pipe dist...

Страница 16: ...xpanded to twice their lengths e g 4ft to 8ft Fully expand pipe and cut off excess Do not use more than 2 couplers to extend short pipes Single sections are preferred in an installation attaching at t...

Страница 17: ...of the roof slope under the shingles Both the sides and the lower edge lay on top of the shingles NOTE At the top edge of the flashing plate lift the shingles and nail the plate to the roof deck then...

Страница 18: ...ilder Antique Brass Z36GBC Grill Kit Classic Builder Chrome Z36GBP Grill Kit Classic Builder Polish Brass Z1GBL Grill Kit Black Z1GAB Grill Kit Antique Brass Z1GPB Grill Kit Polish Brass Z36GCR Grill...

Страница 19: ...DVSS Siding Shield ZDV48GP Galvanized Pipe 7 Dia x 48 Vertical Installations ZDVAAF Flashing 7 c w Storm Collar 1 12 to 7 12 ZDVAF2 Flashing 7 c w Storm Collar 8 12 to 12 12 ZDVAF3 Flashing 7 c w Stor...

Страница 20: ...minals at wall switch If burner comes on replace defective Switch ON wall switch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Gener...

Страница 21: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: