Gas fired appliances may be used only for supplemental heat and/or decorative purposes and under no circumstances shall they 
provide a primary heat source. 

 

If the factory-built fireplace has no gas access hole(s) provided, an access hole of 1.5in [37.5mm] or less may be drilled through 
the lower sides or bottom of the firebox in a proper workmanship like manner. This access hole must be plugged with non-
combustible insulation after the gas supply line has been installed. 

 

Cutting any sheet-metal parts of the fireplace, in which the gas fireplace insert is to be installed, is prohibited. 

 

This appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.  

 

Installer must mechanically attach the supplied label to the inside of the fireplace into which the gas fireplace insert is installed. 

 

 

Warning: 

This fireplace has been converted for use with a gas fireplace insert only and cannot be used for burning wood or solid 

fuels unless all original parts have been replaced, and the fireplace re-approved by the authority having jurisdiction.

 

 

NOTE: It is recommended that a Carbon Monoxide (CO) Detector be installed in or near bedrooms and on all levels of your home. 
Place a detector about 15ft [4.5m] outside the room that houses your gas appliance. 

Certified for installation in a bedroom or bed/sitting room. In Canada must be installed with listed millivolt thermostat (Thermostats are not 

permitted for vented [Decorative] gas fireplaces installed in the U.S.A.).  In USA see local codes. 

 

Operations and Maintenance Instructions 

For safe installation and operation note the following: 
• 

The Burner/Log Assembly has been engineered and permanently adjusted for proper flame control. 

• 

Periodically remove the logs from the grate assembly and vacuum any loose particles from the grate and burner areas. See Log 
Placement page to remove logs. Vacuum burner parts and replace logs. 

• 

Never use your gas fireplace as a cooking device. 

• 

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify      
proper operation after servicing. 

 

Installation Requirements for the Commonwealth of Massachusetts 

In the Commonwealth of Massachusetts, the installer or service agent shall be a plumber or gas fitter licensed by the 
Commonwealth. 
When installed in the Commonwealth of Massachusetts or where applicable codes; the unit shall be installed with a CO 
detector per the requirements listed below. 

1. 

For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent 
terminal and the air intake is installed below four feet above grade the following requirements must be satisfied: 

A. 

If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm 
shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 
(2005 Edition). 

B. 

A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall: 

 

Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services 
both the appliance and the carbon monoxide detector; 

 

Have battery back-up power; 

 

Meet ANSI./UL 2034 Standards and comply with NFPA 720 (2005 Edition); and 

     Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR. 

C. 

A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. 
Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall 
remain with the appliance or equipment at the completion of the installation. 

D. 

A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of 
vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent 
Directly Below”. 

2. 

For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment where the bottom of the vent 
terminal and the air intake is installed above four feet above grade the following requirements must be satisfied: 

A. 

If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm 
shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 
(2005 Edition). 

B. 

 A carbon monoxide detector shall: 

 

Be located in the room that houses the appliance or equipment; 

 

Be either hard-wired or battery powered or both; and 

 

Shall comply with NFPA 720 (2005 Edition). 

A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in 
strict compliance with the manufacturer instructions. A copy of the installation instructions shall remain with the appliance or equipment 
at the completion of the installation. 
 

 

For the state of Massachusetts a 

T-handle gas shut-off valve

 must be used on a gas appliance. This T-handle gas shut-off valve must be listed and 

approved by the state of Massachusetts. This is in reference to the state of Massachusetts state code CMR238. 

 

6

Содержание VFI25

Страница 1: ...ractory materials from any masonry solid fuel fireplace The VFI25 Fireplace Insert was designed for installation in a zero clearance type listed solid fuel burning factory built fireplace It may be ne...

Страница 2: ...use odours It is recommended that you burn your gas fireplace or stove for a minimum of four hours at a time with the fan off after the curing of the paint has been completed These odours can last upw...

Страница 3: ...C6 Placement Guidelines 12 Burner System Maintenance 13 VFI25 Conversion Kit Instructions Part A 13 VFI25 VFI30 Conversion Kit Instructions Part A 14 Gas Conversion for Top Convertible Pilot Series 01...

Страница 4: ...nt see diagram above to secure the appliance to the floor Bedroom approved Warning Do not compromise the structural integrity of the manufactured home wall floor or ceiling during installation of appl...

Страница 5: ...ing the appliance 15 Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequ...

Страница 6: ...domestic hot water equipment where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied A If there is not one alread...

Страница 7: ...liners Removal of the smoke baffle is necessary in most cases Clearance from the front of the unit to a combustible floor is 0 15 metres 6 inches Clearance from adjacent side wall is 7 inches from si...

Страница 8: ...run through a masonry chimney or other approved venting system the chimney must be inspected cleaned and repaired if necessary A chimney which was used for a solid fuel fireplace must be professionall...

Страница 9: ...in place 19 is required 6 If the lintel is wider than 12 305mm then the height of the solid fuel fireplace must be at least 25 63 5 cm to allow for an offset elbow See Figure 2 If providing an offset...

Страница 10: ...solid fuel fireplace Make sure that the fireplace is completely cool and has not been used for a few days 7 Make sure that the solid fuel fireplace base is level and if not make any necessary adjustm...

Страница 11: ...s Place log 2 on rear log holder and center it Step 3 Place Log 3 onto the notched areas as shown Place Log 4 onto the notched areas as shown Refer to step 2 for notched area locations Step 4 Place la...

Страница 12: ...ocations Fill the exposed areas of the ember plates and front burner tube with ember rocks Do not place ember rocks on rear burner tube Step 4 Place lava rock around the sides and front of the burner...

Страница 13: ...n on the unit at least once a month and inspect the flame pattern to ensure there are no problems with the burner tube The pilot flame should also be inspected monthly to ensure proper operation Flame...

Страница 14: ...pplied with the Conversion Kit IMPORTANT Always check for gas leaks with a soap and water solution DO NOT USE OPEN FLAME FOR LEAK TESTING WARNING This conversion kit shall be installed by a qualified...

Страница 15: ...e new injector is proper for the application The injector size is stamped on the side of the injector near the top LPG injectors have a groove machined around their circumference near the top while NG...

Страница 16: ...Gas Conversion for Modulator PART C 16...

Страница 17: ...orward and drill out rivets Step 2 Seal rivet holes with two supplied screws ZDV6000 ONLY Step 3 Center legs of Grate Bar on either side of burner support and fasten with supplied self drilling Screws...

Страница 18: ...ot be allowed to contact glass and unit should be allowed to run for a minimum of 10 minutes area of sensing tube will become quite hot A minimum draft pressure of 02 inches of water column is require...

Страница 19: ...ame size is factory set The pilot flame should be at least 1 5 inches 4 cm long The flame should be impinging on the pilot generator Pilot size can be adjusted through the pilot adjust screw If the pi...

Страница 20: ...of a filmy residue It is therfore rec ommended that the glass be cleaned two or three times initially with non abrasive common household glass cleansers and warm water After that the glass can be cle...

Страница 21: ...he firebox and lifting the complete burner assembly from the unit and replacing defective component and re installing Check for gas leaks after replacing burner assembly WARNING No substitute material...

Страница 22: ...all panels All brass trims D E and F are installed with 5 16 x 6 32 self tapping screws attach part D E and F to outer edge of surround Than place On Off switch into slot upper right corner after tri...

Страница 23: ...ass Trim Top 1 E 3000 305 3000 315 3000 330 Brass Trim Left 1 F 3000 306 3000 316 3000 329 Brass Trim Right 1 G 3000 307 3000 317 3000 324 Brass Panel Top1 Gl n a n a 3000 327 Brass Panel Bottom 1 H 3...

Страница 24: ...H Wiring Diagram SIT 820 639 and 820 640 True Millivolt Systems This System does not have a thermocouple For units with serial number greater than 13930 see 820639 820640 systems Wiring diagram with T...

Страница 25: ...t Antique Brass V25T2129C Trim Kit Chrome V25T2129P Trim Kit Polish Brass Size 21 High x 29 Wide V25S2738B Surround Kit Large Flat Black V25T2738A Trim Kit Antique Brass V25T2738C Trim Kit Chrome V25T...

Страница 26: ...are not available for Deluxe Surrounds V25ADDX Arch Door Frame Deluxe Black 352 V25ADTH Arch Door Frame Top Half Black 353T V25ADDA Arch Door Frame Double Arch Black 354 V25ADDD Arch Door Frame Double...

Страница 27: ...36WR Thermopile GOAI 524 1001 P069SI Electrode Sparker 915 069 TC SIT 1001 P216SI Thermocouple 290 216 TC SIT 1001 P165SI Orifice Pilot NG 977 165 TC SIT 1001 P167SI Orifice Pilot LP 977 167 TC SIT 10...

Страница 28: ...d Assembly 2000 079 Gasket for Flue 2500 BNGSI Burner Assy c w Valve Natural Gas 2500 BLPSI Burner Assy c w Valve Liquid Propane 3000 930 Spill Safety Switch 36T21 3000 940 Glass Robax 23 22 x 11 75 3...

Страница 29: ...screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA 16 FT C...

Страница 30: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: