MQZCV48 Facing Requirements
Required Non-Combustible Areas
NOTE: ANY MATERIALS COVERING THE FACE OF THE
FIREPLACE MUST BE NON-COMBUSTIBLE (i.e. brick,
stone, tile, concrete board). FIREPLACE WITH SCREEN
ONLY (AS SHIPPED) SHOWN HERE.
Refer to
BASIC FINISHING
Sections for important finishing
details.
Notice: Granite or other facing materials are not covered
by the fireplace warranty. Natural stone and other facing
materials may crack regardless of how they are installed.
Notice: DurockR Brand Cement Board:
The manufacturer
recommends
CGC SheetrockR Brand DurabondR 90
Setting- Type Drywall Compound
rather than a ready-mix
product for finishing.
When finishing the wall around the fireplace, it is critical that
the wall covering be fastened properly. It is acceptable to pre-
drill holes and use self-tapping screws which may be used to
fasten a backer for tile, marble, etc. Screws being installed
through non-combustible board should be self-tapping type
with a maximum length of 2 inches.
Do not drill or install longer screws (over 2”) as this may
damage internal components.
Only
non-combustible
materials may be used over the face
of the appliance.
We recommend that CONCRETE BOARD (non-combustible
material) be tied in to the entire perimeter of the fireplace for
durability.
Finishing Recommendations
(Obtained from professional
construction contractors and finishers):
Frame unit with metal studs (minimum 20 gauge).
Wooden
studs may be used, but may cause drywall screws to pop
or pull due to wood studs drying out.
Minimum of 1/2” CONCRETE BOARD cement board (this
non-combustible
panel is ULC listed as a wall shield/floor
protector) and fasten to the entire perimeter framing.
Use fiberglass (mesh) tape for all joints in area of the
fireplace.
Use Yellow joint mud (contains high amounts of glue) – two
coats, finishing with one coat of green topping mud, sand and
prep for painting.
If not using a surround, a metal “L” Trim may be used to finish
perimeter of CONCRETE BOARD.
OTHER NOTES:
-
A full single shee
t of non-combustible board (no joints)
above the unit is recommended if possible.
-It is preferred to attach the non-combustible board to
framing
only
and not directly to the unit to allow for expansion and
contraction during normal operation.
-Lighter colored painted surfaces may discolor due to heat
exposure.
45-3/16” x 39-3/4”
Opening in Facing
Materials is required
for Screen to fit
56” MIN for NG
68” MIN for LP
Plus Rise of
1/4” Per Foot*
Refer to BASIC FINISHING Sections for important finishing details.
Non-Combustible Material
Screwed to Framing
Screwed to Framing
Optional Recess
3/4” MAX Combustible
Material
Framing
FIREPLACE OPENING
Screwed to Framing
1-3/16” MIN from
opening
1-1/16” MIN from
opening
15
Содержание MQZCV48LP
Страница 20: ...ZCV48 Fireplace Opening Required Clearance ZCV48 Fireplace Opening Required Clearance 20...
Страница 52: ...Gas Conversion for Modulator PART C 52...
Страница 57: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 57...
Страница 58: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 58...
Страница 65: ...Proflame 2 Remote Control 65...
Страница 67: ...67...