background image

 

 

Venting 

 

 

A.  Clearance above grade, veranda, porch, deck, 

or balcony 12in [30cm] min.

[1,2]

 

B.  Clearance to window or door that may be 

opened. 12in [30cm] min. for appliances 
100,000BTUh [30kW] and lower, in Canada. 
9in

[2]

 [23cm] for appliances 50,000 BTUh and 

lower, in USA. 

C.  Clearance to permanently closed window min. 

12in [30cm] recommended to prevent 
condensation on window, in Canada. 9in

[2]

 

[23cm] for appliances 50,000 BTUh and lower, 
in USA. 

D.  Vertical clearance to ventilated soffit located 

above the termination within a horizontal 
distance of 2ft [60cm] from the center line of the 
termination. 18in [46cm] min.

[4]

 

E.  Clearance to unventilated soffit 12in [30cm] min. 
F.  Clearance under veranda, porch, deck or 

balcony 12in [30cm] min.

[3]

 (US

[4]

G.  Clearance from a perpendicular inside wall or 

outer corner to the edge of the vent terminal 
plate is 3in [7.6cm] min. 

H.  Clearance to each side of center line extended 

above meter/regulator assembly 3ft [91cm] 
within a height 15ft [4.5m] above the 
meter/regulator assembly. 

I. 

Clearance to service regulator vent outlet 3ft 
[91cm] min.

[1]

 (US

[4]

J.  Clearance to non-mechanical air supply inlet to 

building or the combustion air inlet to any other 
appliance: In Canada, 6in [15cm] for appliances 

10,000 BTUh [3kW], 12in

[1]

 [30cm] minimum for 

                                                           

1

 In accordance with the current CSA B149.1, Natural Gas and 

Propane Code. 

2

 In accordance with the current ANSI Z223.1/NFPA 54, National 

Fuel Gas Code. 

3

 Permitted only if veranda, porch, deck, or balcony is fully open 

on a minimum of two sides beneath the floor. 

4

 Clearance in accordance with local installation codes and the 

requirements of the gas supplier. 

appliances >10,000 BTUh [3kW] and 

100,000 

BTUh [30kW], 36in [91cm] for appliances 
>100,000 BTUh [30kW]. In the USA, 6in

[2]

 

[15cm] for appliances 

10,000 BTUh [3kW], 9in 

[23cm] for appliances >10,000 BTUh [3kW] and 

50,000 BTUh [15kW], 12in [30cm] for 

appliances >50,000 BTUh [15kW]. 

K.  Clearance to a mechanical air supply inlet 6ft 

[1.8m] min.

[1]

 in Canada. In USA, 3ft [91cm] 

above if within 10ft

[2]

 [3m] horizontally. 

L.  Clearance above paved sidewalk or a paved 

driveway located on public property 7ft [2.1m] 
min.

[5]

 

M.  Clearance above highest point of exit on roof 

18in [45cm]. 

N.  Clearance to perpendicular wall 24in [60cm]. 

(Recommended to prevent re-circulation of exhaust products. For 
additional requirements check local codes.)

 

 

                                                           

5

 A vent shall not terminate directly above a sidewalk or paved 

driveway that is located between two single family dwellings and 
serves both dwellings. 

37

Содержание Marquis Serenity MQZDV1917

Страница 1: ...al installations the venting must be a minimum of one foot vertical off the flue before going horizontal Installation Instructions Listed Certified for USA and Canada Model Number MQZDV1917 Stock s MQ...

Страница 2: ...Fan Installation 20 22 Baffle Replacement Guide 22 Gas Line Installation 23 Burner Removal Servicing Guide 24 Brick Liner Installation Guide 25 Porcelain Liner Installation Guide 26 Millivolt System L...

Страница 3: ...use odours It is recommended that you burn your gas fireplace or stove for a minimum of four hours at a time with the fan off after the curing of the paint has been completed These odours can last upw...

Страница 4: ...ILE HOMES Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrical Code in Canada An appliance must be grounded to the steel chassis of...

Страница 5: ...g the appliance 15 Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequen...

Страница 6: ...PA 720 2005 Edition B A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall Be powered by the same electrical circuit as the appliance or equipment s...

Страница 7: ...ed Locating the Appliance The appliance can be located in the configura tions shown in Figure 2 Note that an Island installation with a top vent is possible as long as the horizontal portion of the ve...

Страница 8: ...on and greatly reduces carbon deposits and cleaning of glass Does not apply to Back Flue models Framing for your Gas Fireplace Stand off Locations This section will cover four different types of insta...

Страница 9: ...the unit Using the holes on the Front Tabs fasten the appliance to the Cabinet with the appropriate eight 8 screws Clearance to Combustibles Table 1 Clearance to combustibles for fireplace appliance B...

Страница 10: ...General Framing Installations Figure 5 General framing installation 10...

Страница 11: ...will be This formula is illustrated in Figure 5 Absolute Minimum Ceiling Height Min Ceiling Height Raised Height For cabinet installations It is necessary that the appliance be installed from the rea...

Страница 12: ...Figure 7 Cabinet installation Note that the unit MUST be installed from the back of the cabinet Figure 8 Dimensions for facing material cutout 12...

Страница 13: ...fireplace vent opening When using paint or lacquer to finish the mantel such paint or lacquer must be heat resistant 250 F 121 C to prevent discoloration Example If a mantel is desired to extend 4 1...

Страница 14: ...ith a sidewall i e a wall perpendicular to the face of the unit must adhere to the clearances imposed by the illustration shown in Figure 10 Figure 10 Sidewall clearance requirements Sidewall Clearanc...

Страница 15: ...n in the Dimensional Overview section NOTE Only one 2x4 stud header may be used in the frame Please refer to Figure 5 on page 10 or Figure 11 below To ensure the Front Surround covers the maximum area...

Страница 16: ...en the finished NOTE This Surround is capable of extending 5 8 away from the front of the unit Hence a wider range of facing materials can be accommodated without relocating the unit 4 To remove the F...

Страница 17: ...hown in Figure 14 3 Using the thumb screws washers and locking nuts provided fasten the Access Panel Grill to the Finishing Surround frame Observe the locations of the screw washer and nut Torque the...

Страница 18: ...efore recommended that initially the glass be cleaned two or three times with non abrasive common household glass cleansers and warm water After that the glass should be cleaned two or three times a s...

Страница 19: ...ion of the frame is IN FRONT of the Upper Mounting Tab and the lower portion is BEHIND the Lower Mounting Tab Figure 17 Arch Door installation 3 Swing the right side of the Arch Door into the unit Pos...

Страница 20: ...he fan directly simply connect the TERMINAL B wires to the thermal switch Thermodisc terminals 2 To have a unit mount variable control controlling the fan speed in conjunction with thermal switching s...

Страница 21: ...an kit power cord from the receptacle and the two 2 leads from the variable speed control thermal switch Remove the Burner Pan assembly Refer to the Burner Removal Servicing Guide section 2 Lift the f...

Страница 22: ...Please make note of their location before beginning the replacement procedure IMPORTANT Examine the condition of the mounting holes and screws It is required that these areas are sealed properly If t...

Страница 23: ...olution 8 The appliance and its individual shutoff valve must be disconnected from the gas supply pip ing system during any pressure testing of that system at test pressures in excess of 1 2psig 3 5 K...

Страница 24: ...llation is the reverse of these steps NOTE Before reinstallation ensure that all old sealant material is scraped off and removed from the fire box bottom and burner pan Verify that the sealing area is...

Страница 25: ...rner tube by sliding it towards the right hand side 4 If the Upper Clips 2 and Lower Panel Brackets 2 are preinstalled then remove them 5 Tilt the Back Panel backwards and slide it into place The Back...

Страница 26: ...bly by unfastening the two 2 screws holding it in Remove the two 2 back screws of both the Lower Latch assemblies NOTE These screws will be used to fasten the Liner Holder brackets 2 Place the rear po...

Страница 27: ...above on this label If you don t smell gas then go to the next step 7 Now push in the control knob slightly and turn 4 counter clockwise to the PILOT position 8 Push in the control knob all the way a...

Страница 28: ...d also be inspected monthly to ensure proper operation Flame should appear similar to the above picture Conversion Kit Instructions PART A Kit Number Description Pilot Orifice Burner Orifice Brass 100...

Страница 29: ...ght and remove it from the assembly Make note of where the Air Shutter is and the screw used to secure it 3 Remove the main orifice using a 1 2 wrench and replace it with the new conversion kit orific...

Страница 30: ...e new injector is proper for the application The injector size is stamped on the side of the injector near the top LPG injectors have a groove machined around their circumference near the top while NG...

Страница 31: ...Gas Conversion for Modulator PART C WARNING WARNING 31...

Страница 32: ...the remote Contrary to this feature is a Manual HI LO Control Knob The Modulating Servo Motor requires the Remote system to be present Backup Battery Pack This component permits the IPI system to oper...

Страница 33: ...ol wiring harness instead of the main IPI harness From the Remote wiring harness use its male plug in connector and connect it to the female plug in in the main IPI harness Now the circuit is complete...

Страница 34: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 34...

Страница 35: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 35...

Страница 36: ...ent LIGHTING INSTRUCTIONS 1 STOP Read the above safety information on this label 2 Remove batteries from Receiver and or Battery Backup Pack 3 Turn off all electric power to the fireplace 4 This firep...

Страница 37: ...combustion air inlet to any other appliance In Canada 6in 15cm for appliances 10 000 BTUh 3kW 12in 1 30cm minimum for 1 In accordance with the current CSA B149 1 Natural Gas and Propane Code 2 In acc...

Страница 38: ...Top of horizontal is 1 1 2 3 8cm Top of 90 degree elbow in an enclosure over 44 112cm is 2 1 2 6 4cm Venting terminal shall not be recessed into a wall or siding Venting Routes and Components Since it...

Страница 39: ...2 20 6 1 8 2 4 20 6 1 18 5 5 20 6 1 9 2 7 20 6 1 19 5 8 20 6 1 10 3 0 20 6 1 20 6 1 20 6 1 11 3 4 20 6 1 25 7 5 15 4 6 12 3 7 20 6 1 30 9 0 10 3 0 13 4 0 20 6 1 40 12 2 0 0 Table 2 Horizontal Vent Ta...

Страница 40: ...alling the pipe expand it com pletely and then cut off the remaining length A flex pipe can be expanded to twice their shipped length e g 4ft to 8ft Do not use more than 2 couplers to extend short pip...

Страница 41: ...ealant NOTE It is critical to the proper and safe operation of this fireplace that on all connections the inner liner and the outer casing are both caulked with liberal amounts of sealant Do not use a...

Страница 42: ...ent Termination must not be recessed into wall or siding Figure 26 Side wall hole dimensions for flush wall installations For other installations where the unit is far away from the wall ensure that t...

Страница 43: ...uring the flex and rigid pipe are secured 4 flex pipe must be secured the same way with 4 screws but must penetrate the 4 flex and 4 section of termination Attach 7 rigid pipe to 7 termination with se...

Страница 44: ...the plate to the roof deck then cement the shingles to the plate with a suitable waterproof mastic Ensure that the chimney is plumb Square up the flashing plate and nail in place to the roof deck Use...

Страница 45: ...re to do so will result in improper combustion and emission of harmful gases and can lead to personal injuries Figure 29 Log C 19 parts list Figure 29 Log C 19 parts list Figure 31 Step 1 Place LOG 1...

Страница 46: ...e 35 Step 5 Place Ember Rocks on the front burner tube and ember plate as shown DO NOT PLACE EMBER ROCKS ON THE REAR BURNER TUBE Figure 36 Step 6 Place Lava Rock on the bottom of the firebox IN FRONT...

Страница 47: ...9FK Fan Kit w Variable Speed Temperature Sensing MQ19PL Porcelain Reflective Panel Liner MQ19RL Brick Liner Z1MT Thermostat Millivolt Wall Mount Z80PT Thermostat Programmable Digital Millivolt Millivo...

Страница 48: ...zontal Square Termination Vent Starter Kit 3 Length Horizontal Vent Termination Wall Thimble Wall Thimble 36 Flex Pipe Mill Pac FDVVT40 Vertical Vent Termination FDVHT Horizontal Round Termination FDV...

Страница 49: ...ge Check generator with millivolt meter Take reading at generator terminals of gas valve Should read 325 millivolts minimum while holding valve knob depressed in pilot position and wall switch off Rep...

Страница 50: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: