5) Execute the
PLS
instruction to configure PTO0 and start it.
3.2.4.2.4 PWM Operations
Following takes PWM0 as an example to introduce how to configure and operate the
PTO/PWM generator in the user program.
There are two procedures for using PWM: Configure related control registers and initialize
PTO. Execute PLS instruction.
Use SM0.1 (the first scan memory bit) to call a subroutine that contains the initialization
instructions. Since SM0.1 is used, the subroutine shall be executed only once, and this reduces
CPU scan time and provides a better program structure.
Execute PWM
1) Set control byte SMB67 according to the desired operation.
For example, SMB67 = B#16#D3 indicates:
Enable the PTO/PWM function
Select PWM operation
Select 1μs as the time base
Allow updating the pulse width value and cycle time value
2) Set SMW68 according to desired cycle time.
3) Set SMW70 according to desired pulse width.
4) Execute the
PLS
instruction to configure PWM0 and start it.
Changing the Pulse Width for the PWM Output
The following steps describes how to change PWM output pulse width.
1) Set control byte SMB67 according to the desired operation.
For example, SMB67 = B#16#D2 indicates:
Enable the PTO/PWM function
Select PWM operation
Содержание HP043-20DT
Страница 8: ...Kinco HP User Manual 8 1 4 4 Dimension Dimension 132 102 40 1mm Cutout size 119 93mm...
Страница 22: ...Kinco HP User Manual 22...
Страница 23: ...Kinco HP User Manual 23...
Страница 25: ...Kinco HP User Manual 25...
Страница 26: ...Kinco HP User Manual 26 2 It will show settings when mouse at the right side of Window then click settings...
Страница 27: ...Kinco HP User Manual 27 3 Click update and recovery in the PC settings...
Страница 28: ...Kinco HP User Manual 28 4 Click restart now at advanced startup 5 Click advanced options...
Страница 29: ...Kinco HP User Manual 29 6 click startup settings 7 Click restart...
Страница 31: ...Kinco HP User Manual 31 10 Figure as below after successful...