Kinco-HP
User Manual
44
cycle time and the pulse width.
The unit of cycle time and pulse width time is microsecond(us) or millisecond(ms). The
maximum value of cycle time is 65535. If the pulse width time is greater than the cycle time
value, the duty cycle is set to be 100% automatically and the output is on continuously. If the
pulse width time is 0, the duty cycle is set to be 0% and the output is off.
PTO
PTO provides a square wave (50% duty cycle) output, and you can control the cycle time and
the number of the output pulses. The unit of cycle time is microsecond(us) or
millisecond(ms).The maximum value of cycle time is 65535.The range of pulse number is
2~4,294,967,295.If the specified pulse number is less than 2, then KInco-K2 will set related
error bit and prohibit the output.
PTO function provides single segment of pulse and multiple segment of pulse.
Single segment pulse
In single segment pulse mode, it only executes pulse train output once after executing PLS
instruction.
Multiple segment pulse
In multi-segment pulse mode, CPU automatically reads the configurations of each PTO
segment from a profile table located in V area and executes the related PTO segment.
The length of each segment is 8 bytes, including a cycle time value (16-bit, WORD), a
reserved value (It is not used now,16-bit, INT), and a pulse number value (32-bit,
DWORD).Thereof, all the pulse output frequency are the same in same segment. It uses PLS
instruction to start multiple segment pulse.
In this mode, the starting address of the profile table is stored in SMW168 (corresponding to
PTO0) ,SMW178 (corresponding to PTO1) and SMW268(corresponding to PTO2).Time base
is configured by SM67.3 (corresponding to PTO0) ,SM77.3 (corresponding to PTO1) and
SM87.3 (corresponding to PTO2). The time base can be in either microsecond or millisecond.
All cycle values in the profile table must use same time base, and cannot be modified when the
profile is executing.
The following table describes the format of the profile table.
Содержание HP043-20DT
Страница 8: ...Kinco HP User Manual 8 1 4 4 Dimension Dimension 132 102 40 1mm Cutout size 119 93mm...
Страница 22: ...Kinco HP User Manual 22...
Страница 23: ...Kinco HP User Manual 23...
Страница 25: ...Kinco HP User Manual 25...
Страница 26: ...Kinco HP User Manual 26 2 It will show settings when mouse at the right side of Window then click settings...
Страница 27: ...Kinco HP User Manual 27 3 Click update and recovery in the PC settings...
Страница 28: ...Kinco HP User Manual 28 4 Click restart now at advanced startup 5 Click advanced options...
Страница 29: ...Kinco HP User Manual 29 6 click startup settings 7 Click restart...
Страница 31: ...Kinco HP User Manual 31 10 Figure as below after successful...