Product Installation Manual
9
如图
1
所示:
As shown in the figure 1
:
附
2
:接线盒样式
2
安装说明
Appendix 2: Installation Instructions
for Junction Box Style 2
6
、现将接线盒取出,将安装底板用
2
颗
M8X25
螺栓固定在电池架的档条
A
上
的安装孔上
(M8
螺栓朝上
)
;
6
Now take out the junction box, and fix the mounting base plate on the
mounting hole of the battery rack Bar A with 2 pcs M8X25 bolts (M8 bolts
face up);
7
、将
M8
螺母拧下,把电池端引出的输出线铜鼻子套在
M8
螺杆上,然后拧
紧螺母
(
含弹垫、平垫
)
;
7
Unscrew the M8 nut, fit the copper nose of the output wire from the battery
end onto the M8 screw, and then tighten the nut (including elastic cushion
and flat cushion);
8
、将下端
M10
螺栓及螺母拧下,与客户设备相连的输出线的一端用
M10
螺
栓及螺母紧固在铜排上面;
8
Unscrew the M10 bolt and nut at the lower end, and fasten one end of the
护罩
Shield
M10X25
护罩支撑板
Shield support plate
连接铜排
Connection copper bar
高压磁瓶
High-voltage magnetic bottle
连接板
Connecting plate
M5X25
M8X25
M12X35
M10X20