PCR-LE2 series

This product conforms to IEC Overvoltage Category II (energy-
consuming equipment that is supplied from a fixed installation).

WARNING

Risk of electric shock.
• This product conforms to IEC Safety Class I (equipment 

that has a protective conductor terminal). Be sure to 

earth ground the product to prevent electric shock.

• Connect the protective conductor terminal to earth 

ground.

• Turn off the circuit breaker of the switchboard before 

you connect the power cord.

• Do not use the product with the terminal box covers 

removed.

Risk of electric shock or fire.

• For the connected switchboard, select a breaker that 

has a cut-off current that can handle the maximum in-

put current of the product

• Have a qualified engineer connect the power cord to 

the switchboard.

CAUTION

If the voltage distortion of the AC power line is large, the 

product may malfunction. The PCR-LE2 Series cannot be 

connected to a generator or a similar device.
Inside the product, protective circuits such as input fuses are 

connected to match the polarity of the input terminal. Be sure 

to match the colors of the wires and the input terminals to 

connect the wires correctly.

Single-phase, 200 V input (PCR6000LE2 only):
   L, N, and

 (GND)

Three-phase, 200 V input: R, S, T, and

 (GND) 

Three-phase, 400 V input: R, S, T, N, and

 (GND) 

- Note -
The POWER switch can be used to disconnect the product from 

the AC power line in an emergency (On the PCR27000LE2, the 

MASTER POWER switch and the two SLAVE POWER switches 

must be turned off.). Provide enough space around the POWER 

switch to ensure that it can be turned off at any time.

A power cord is not supplied with the PCR-LE2 Series.
Input power cords are available as options. When you are wiring 
the switchboard, attach crimping terminals that match the screws 
of the switchboard that has been connected by a qualified engi-
neer.
If you will not use one of the optional input power cords, prepare a 
power cord that meets the following specifications.

Cable

Nominal cross-
sectional area

Input 
terminal

Single-phase, 
200 V input

PCR6000LE2 Three single-core 

cables

14 mm

2

 or more M8

Three-phase, 
200 V input

PCR6000LE2 Four single-core cables 8 mm

2

 or more

M5

PCR9000LE2

14 mm

2

 or more M5

PCR12000LE2 

22 mm

2

 or more M8

PCR18000LE2

38 mm

2

 or more M8

PCR27000LE2

60 mm

2

 or more M8

Three-phase, 
400 V input

PCR6000LE2 Five single-core cables 5.5 mm

2

 or more M5

PCR9000LE2

5.5 mm

2

 or more M5

PCR12000LE2 

8 mm

2

 or more

M8

PCR18000LE2

14 mm

2

 or more M8

PCR27000LE2

38 mm

2

 or more M8

Connecting power cords to the PCR6000LE2 

or PCR9000LE2

 

Check that the AC power line meets the nominal in-

put rating of the product.

The product can receive a nominal power supply voltage:
Single-phase, 200 V input (PCR6000LE2 only):

 

  

200 Vac to 240 Vac

Three-phase 200 V input: 200 Vac to 240 Vac (Line Voltage)
Three-phase, 400 V input:  220 Vac to 240 Vac (Phase Voltage)

Frequency: 50 Hz or 60 Hz.

 

Check that the POWER switch is turned off.

 

Pull out the terminal block tray.

 

Securely connect the power codes to corresponding 

terminals of AC INPUT terminal block.

Single-phase
200 V input
(PCR6000LE2 only)

N

L

T

S R

Three-phase
200 V input

T

N

S R

Three-phase
400 V input

M8

M5

M5

 

Turn off the switchboard’s breaker.

 

Securely connect the power codes to corresponding 

terminals of switchboard's breaker.

 

Return the terminal block tray to its previous position.

If you do not insert the terminal block tray all the way into 
its storage compartment, an electric current will not flow 
through the PCR-LE2 Series even if the POWER switch is 
turned on.

 

Turn on the switchboard’s breaker.

Connecting the power cord

Содержание PCR12000LE2

Страница 1: ...and waveform can be changed over time Power supply environment testing can be automated In addition to the AC output sequences DC output single phase output or single phase three wire output only and...

Страница 2: ...used in the explanations in the manual WARNING Indicates a potentially hazardous situation which if ig nored could result in death or serious injury CAUTION Indicates a potentially hazardous situatio...

Страница 3: ...istance Using Power Line Abnormality Simulations In AC mode you can simulate power supply line errors by stop ping the PCR LE2 output and decreasing and increasing the voltage to simulate voltage dips...

Страница 4: ...t least 20 cm of space between the air inlet outlet and the wall or obstacles Fix PCR6000LE2s and PCR9000LE2s to the floor using L shaped or other similar brackets Base Hold Angles OP03 KRC are availa...

Страница 5: ...block tray in place Stopper 5 Connect the wires and cables to the terminal block and connectors as necessary 6 Return the stopper to its previous position 7 Return the terminal block tray to its prev...

Страница 6: ...the switchboard attach crimping terminals that match the screws of the switchboard that has been connected by a qualified engi neer If you will not use one of the optional input power cords prepare a...

Страница 7: ...ncy 50 Hz or 60 Hz 2 Check that the POWER switch is turned off 3 Unfasten the screws two locations of the AC INPUT terminal block cover and remove the cover 4 Connect the power cords according to the...

Страница 8: ...rs are detected the home position the basic screen appears 0 00 A 0 0 V pk rms AC LOAD 99 00 Hz RANGE L RESP M OUTPUT OFF Turning on the POWER switch on the PCR12000LE2 PCR18000LE2 or 27000LE2 The PCR...

Страница 9: ...ber 63 Output on off state If the POWER switch is turned off immediately after the settings have been changed the last settings may not be stored CAUTION Risk of malfunction After turning the POWER sw...

Страница 10: ...uirements of single core wires that are used to connect to the load Nominal cross sectional area mm2 AWG reference cross sectional area mm2 Allowable current A at Ta 30 C 86 F 0 9 18 0 82 17 1 25 16 1...

Страница 11: ...ill not flow through the PCR LE2 Series even if the POWER switch is turned on Single phase three wire output or three phase out put 1 Check that the POWER switch is turned off 2 Check that the breaker...

Страница 12: ...0 mm2 AWG0 2 or less flip the terminal cover upside down and attach it Single phase output 1 Check that the POWER switch is turned off 2 Check that the breaker of the switchboard is off 3 Unfasten the...

Страница 13: ...shock Before you install the switch between the OUTPUT ter minal block and the load be sure to turn the POWER switch off and turn off the breaker of the switchboard The current rating of the switch mu...

Страница 14: ...s does exceed the limit defined in the SJ T11363 2006 standard The PCR LE2 series is subject to export control laws Trademarks All company names and product names used in the PCR LE2 manual are tradem...