6
PCR-LE2 series
This product conforms to IEC Overvoltage Category II (energy-
consuming equipment that is supplied from a fixed installation).
WARNING
Risk of electric shock.
• This product conforms to IEC Safety Class I (equipment
that has a protective conductor terminal). Be sure to
earth ground the product to prevent electric shock.
• Connect the protective conductor terminal to earth
ground.
• Turn off the circuit breaker of the switchboard before
you connect the power cord.
• Do not use the product with the terminal box covers
removed.
Risk of electric shock or fire.
• For the connected switchboard, select a breaker that
has a cut-off current that can handle the maximum in-
put current of the product
• Have a qualified engineer connect the power cord to
the switchboard.
CAUTION
If the voltage distortion of the AC power line is large, the
product may malfunction. The PCR-LE2 Series cannot be
connected to a generator or a similar device.
Inside the product, protective circuits such as input fuses are
connected to match the polarity of the input terminal. Be sure
to match the colors of the wires and the input terminals to
connect the wires correctly.
Single-phase, 200 V input (PCR6000LE2 only):
L, N, and
(GND)
Three-phase, 200 V input: R, S, T, and
(GND)
Three-phase, 400 V input: R, S, T, N, and
(GND)
- Note -
The POWER switch can be used to disconnect the product from
the AC power line in an emergency (On the PCR27000LE2, the
MASTER POWER switch and the two SLAVE POWER switches
must be turned off.). Provide enough space around the POWER
switch to ensure that it can be turned off at any time.
A power cord is not supplied with the PCR-LE2 Series.
Input power cords are available as options. When you are wiring
the switchboard, attach crimping terminals that match the screws
of the switchboard that has been connected by a qualified engi-
neer.
If you will not use one of the optional input power cords, prepare a
power cord that meets the following specifications.
Cable
Nominal cross-
sectional area
Input
terminal
Single-phase,
200 V input
PCR6000LE2 Three single-core
cables
14 mm
2
or more M8
Three-phase,
200 V input
PCR6000LE2 Four single-core cables 8 mm
2
or more
M5
PCR9000LE2
14 mm
2
or more M5
PCR12000LE2
22 mm
2
or more M8
PCR18000LE2
38 mm
2
or more M8
PCR27000LE2
60 mm
2
or more M8
Three-phase,
400 V input
PCR6000LE2 Five single-core cables 5.5 mm
2
or more M5
PCR9000LE2
5.5 mm
2
or more M5
PCR12000LE2
8 mm
2
or more
M8
PCR18000LE2
14 mm
2
or more M8
PCR27000LE2
38 mm
2
or more M8
Connecting power cords to the PCR6000LE2
or PCR9000LE2
1
Check that the AC power line meets the nominal in-
put rating of the product.
The product can receive a nominal power supply voltage:
Single-phase, 200 V input (PCR6000LE2 only):
200 Vac to 240 Vac
Three-phase 200 V input: 200 Vac to 240 Vac (Line Voltage)
Three-phase, 400 V input: 220 Vac to 240 Vac (Phase Voltage)
Frequency: 50 Hz or 60 Hz.
2
Check that the POWER switch is turned off.
3
Pull out the terminal block tray.
4
Securely connect the power codes to corresponding
terminals of AC INPUT terminal block.
Single-phase
200 V input
(PCR6000LE2 only)
N
L
T
S R
Three-phase
200 V input
T
N
S R
Three-phase
400 V input
M8
M5
M5
5
Turn off the switchboard’s breaker.
6
Securely connect the power codes to corresponding
terminals of switchboard's breaker.
7
Return the terminal block tray to its previous position.
If you do not insert the terminal block tray all the way into
its storage compartment, an electric current will not flow
through the PCR-LE2 Series even if the POWER switch is
turned on.
8
Turn on the switchboard’s breaker.
Connecting the power cord