background image

PCR-LE2 series 

1

PART NO. Z1-006-120, IB027733
Dec. 2014

PCR6000LE2

PCR9000LE2

PCR12000LE2

PCR18000LE2

PCR27000LE2

Setup Guide

AC Power Supply PCR-LE2 

seriess

Thank you for purchasing the PCR-LE2 Series AC Power Supply.
The PCR-LE2 Series is a special version of the PCR-LE Series that 
can produce highly pure AC signals through the combination of 
its high-speed linear amplifier and arbitrary waveform synthesizer. 
It features switchable single-phase, single-phase three-wire, and 
three-phase outputs.

Checking the Package Contents

When you receive the product, check that all accessories are in-
cluded and that the accessories have not been damaged during 
transportation. If any of the accessories are damaged or missing, 
contact your Kikusui agent or distributor. We recommend that you 
save all packing materials, in case the product needs to be trans-
ported at a later date.

Accessory

Setup Guide (1pc.)

[Z1-006-120]

Quick Reference

Safety information

(1pc.) [Z1-005-040]

English: 1pc. [Z1-006-102]

Japanese: 1pc. [Z1-006-100]

CD-ROM (1 pc.)

[SA-6060]

Heavy object warning label

PCR6000LE2/PCR9000LE2 only

[A8-900-158]

If necessary, attach 

to the product.

Features

The PCR-LE2 Series is equipped with the following features.
•  Switchable between single-phase output, single-phase three-

wire output, and three-phase output
Three types of output are available on a single unit.

•  Various power supply simulations

Power line abnormalities such as outages and voltage dips can 
be simulated. This is a basic feature for power-supply-environ-
ment testing.

•  Various measurements

The rms voltage and current, the peak voltage and current, the 
active power, apparent power, and power factor of the output 
can be measured. Harmonic analysis (up to the 40th harmonic) 
can be performed on the output current.

•  DC output

The PCR-LE2 Series can generate DC output (single-phase out-
put or single-phase three-wire output only) and AC + DC output 
(single-phase output only). This makes it possible to use the 
PCR-LE2 Series in a wide variety of fields, including chemistry 
and physics.

•  Sequences

The output voltage, frequency, and waveform can be changed 
over time. Power-supply-environment testing can be automated.
In addition to the AC output sequences, DC output (single-phase 
output or single-phase three-wire output only) and AC + DC out-
put (single-phase output only) sequences are also available. A 
variety of standard tests can also be performed.

•  Sensing and regulation adjustment

Even if the load device is at a remote location, the PCR-LE2 Se-
ries can stabilize the voltage across the load by correcting for 
voltage drops.
There are two types of sensing: hard sensing (single-phase 
output only) and soft sensing. The different types of sensing are 
used depending on the load conditions and how you will use the 
PCR-LE2 Series.

•  Output current control

The output limit function can be used to limit the output current 
(rms) to a fixed value to perform continuous operation. Continuity 
tests on electrical equipment (such as switchboards, breakers, 
and wiring devices) can be performed under stable conditions.

•  Power management function (power saving function)

A sleep function, which turns the power units off to reduce power 
consumption when output is not generated for the specified 
length of time, and a power-saving function, which operates the 
power units at the bare minimum settings as required by the sup-
ply load, are available.

•  Memory function

Up to 99 entries of output frequency, voltage (AC or DC), and 
waveform bank settings can be saved to the internal memory.
The contents of internal memory, panel settings, power line ab-
normality simulations, sequence data, and waveform bank data 
can be saved to a USB memory device.

•  External communications

The PCR-LE2 Series can be controlled remotely through its 
RS232C interface. If an optional interface board is used, the 
PCR-LE2 Series can be controlled remotely through USB, GPIB, 
and LAN interfaces.

•  External analog signal control (optional)

The EX05-PCR-LE/EX06-PCR-LE option enables you to control 
the PCR-LE2 Series output using external analog signals.

KIKUSUI ELECTRONICS CORP.

1-1-3, Higashiyamata, Tsuzuki-ku, Yokohama, 224-0023, Japan
TEL: +81-45-593-7570 Fax: +81-45-593-7571

WEBSITE

http://www.kikusui.co.jp/en

The newest version of the operation manual can be 
downloaded from Download service of Kikusui web-
site.

Printed in

 Japan © 2013

PCR-LE2 manual

Содержание PCR12000LE2

Страница 1: ...and waveform can be changed over time Power supply environment testing can be automated In addition to the AC output sequences DC output single phase output or single phase three wire output only and...

Страница 2: ...used in the explanations in the manual WARNING Indicates a potentially hazardous situation which if ig nored could result in death or serious injury CAUTION Indicates a potentially hazardous situatio...

Страница 3: ...istance Using Power Line Abnormality Simulations In AC mode you can simulate power supply line errors by stop ping the PCR LE2 output and decreasing and increasing the voltage to simulate voltage dips...

Страница 4: ...t least 20 cm of space between the air inlet outlet and the wall or obstacles Fix PCR6000LE2s and PCR9000LE2s to the floor using L shaped or other similar brackets Base Hold Angles OP03 KRC are availa...

Страница 5: ...block tray in place Stopper 5 Connect the wires and cables to the terminal block and connectors as necessary 6 Return the stopper to its previous position 7 Return the terminal block tray to its prev...

Страница 6: ...the switchboard attach crimping terminals that match the screws of the switchboard that has been connected by a qualified engi neer If you will not use one of the optional input power cords prepare a...

Страница 7: ...ncy 50 Hz or 60 Hz 2 Check that the POWER switch is turned off 3 Unfasten the screws two locations of the AC INPUT terminal block cover and remove the cover 4 Connect the power cords according to the...

Страница 8: ...rs are detected the home position the basic screen appears 0 00 A 0 0 V pk rms AC LOAD 99 00 Hz RANGE L RESP M OUTPUT OFF Turning on the POWER switch on the PCR12000LE2 PCR18000LE2 or 27000LE2 The PCR...

Страница 9: ...ber 63 Output on off state If the POWER switch is turned off immediately after the settings have been changed the last settings may not be stored CAUTION Risk of malfunction After turning the POWER sw...

Страница 10: ...uirements of single core wires that are used to connect to the load Nominal cross sectional area mm2 AWG reference cross sectional area mm2 Allowable current A at Ta 30 C 86 F 0 9 18 0 82 17 1 25 16 1...

Страница 11: ...ill not flow through the PCR LE2 Series even if the POWER switch is turned on Single phase three wire output or three phase out put 1 Check that the POWER switch is turned off 2 Check that the breaker...

Страница 12: ...0 mm2 AWG0 2 or less flip the terminal cover upside down and attach it Single phase output 1 Check that the POWER switch is turned off 2 Check that the breaker of the switchboard is off 3 Unfasten the...

Страница 13: ...shock Before you install the switch between the OUTPUT ter minal block and the load be sure to turn the POWER switch off and turn off the breaker of the switchboard The current rating of the switch mu...

Страница 14: ...s does exceed the limit defined in the SJ T11363 2006 standard The PCR LE2 series is subject to export control laws Trademarks All company names and product names used in the PCR LE2 manual are tradem...

Отзывы: